REPORT OF 4 X 8 CONCRETE
TEST SPECIMENS
Test Methods ASTM C31/C172/C192/C617/C1064/C231/C143
Date Molded 08/06/2008
Permit # COM2008-00471
Chent SAFEWAY STORES INC - PHIL JUTTELSTAD
PrOject SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Address 1891 PIONEER PKWY E - SPRINGFIELD, OR
Job Nnmber S0805400
JurisdictIon SPRINGFIELD
Contractor JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
Subcontractor
Concrete Suppher
Trnck# 242158
Weather CLEAR
Cast By M
KNIFE RIVER (METRO OPERATIONS) - QUALITY CONTROL
SPENNER
Load # 1
Tlcket#
3222087
Test Time
5 20 AM
Air Temp at Samphng Time
65
Cyhnders were cast for the followmg locatIons
ENTRY FOOTING
Total Concrete Placement LocatIOn
ENTRY FOOTING DELI SLAB
Strength ReqUIrement
MIX Nnmber 243NE50VO
AdmlX/Amt NC2
Register Number 0006168
3500
pSI rc @
Conc Temp
28 Days Slump
~ Cement Type I
5 000" % Air 1 00%
MaxAgg 3/4"
Cubic Yards. 4
Lab LocatIOn' SALEM
Set Test @ Date Test Total Area VOlt Type Of Tested
No Davs Rec'd Date Load PSI F ractn re Bv
7 08/07/2008 08/13/2008 52855 12 56 4210 2 SRT
28 08/07/2008 I 09/03/2008
28 I 08/0712008 I 09103/2008
HOLD 108/07/2008 I
I i
I I
I I
o Dlstnbute attachments Average rc@ 28 days
Please see reverse Side for additIOnal mformatIon
Job Number' S0805400 RegIster Number' 0006168
ProJect. SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Date Molded 08/06/2008
-l
X
AW
'YI;
< 1 In [25 mm]
Type 1
Rea<;onable well-formed
cones on both ends less
than I In [25 mm] of
cracking through caps
Type 2
Well-Fonned cone on one
end vertical cracks runnmg
through caps no well-defined
cone on other end
Type 3
Columnar vertical crackmg
through both ends no
\\-ell-formed cones
-\
r
I \
;-'
Type 4
DIagonal fracture with
no crackmg through
ends tap with hammer to
dl'\tmgUlsh from Type 1
Type 5
SIde fracture" at top or
bottom (occur commonlv
with unhonded caps)
Type 6
Similar to Type 5 but
end of cylmder IS pomted
Astensked C*) average umt PSI test results dId not meet lIsted acceptance cntena
Remarks
/
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/S03-6S7-6496
FAX/S03-384-04S9
FAX/S03-670-023S
FAX/360-696-9723
PrOject Manager'
BLEACH
ReViewed By, ReVlewed On 08/14/2008
Our report pertams to the matenal tested only The mfonnatlon contamed 10 thIs report IS provIded subject to aIL tenns and
condItIons of CTI's General CondItIOns In effect at the tIme thIs report IS prepared No party other than those to whom
CTI has dlstnbuted thIs report shall be entItled to use or rely upon the Infonnatlon contamed In thIs document
Carlson Testing, Inc.
Mam Office
POBox 23814
Tlgard Oregon 97281
Phone (503) 684.3460
FaA (503) 684-0954
Salem Office
4060 Hudson Ave NE
Salem, Oregon 97301
Phone (503) 589.1252
Fax (503) 589-1309
Bend Office
POBox 7918
Bend Oregon 97708
Phone (541) 330-9155
FaA (541) 330-9163
Daily Report of Proprietary Anchors
Chent SAFEWAY STORES INC - PHIL JUTTELSTAD
PrOject SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Address 189] PIONEER PKWY E - SPRINGFIELD, OR JUrisdictIOn
CT1 representatIve B PARRI SH OBOA 771
was on site thiS date AUQ 07. 2008 to perform Specmllnspectlon for
Permit COM2008-00471
DFS #(s)
SCOPE OF INSPECTION
Checked In WIth supermtendent or chent representative
Name RANDY
Company JAMES E JOHN CONSTRUCTION
2 InspectIon was "IRe" [i] Contmuous
o PcnodlC
PROPRIETARY ANCHORS
Yes NaNIA
1 Reviewed prevIOus inspection reports'?
2 Reviewed evaluatIOn report?
I ~ I I
Venfied followmg Items meet manufacturer1s
published installatIOn mstructlOns
3 Venfied mlmmum embedment depth of the I
anchors X
4 Venfied installatIon of the anchors x I
5 Venfied anchor diameter X I
6 Venfied steel grade X I
7 Venfied hole diameter X I
8 Venfied type of dnlJ bit used X I
I 9 Venfied hole cleamng method Ix I
110 Verified adhesive apphcatlOn Ix
III Venfied edge d"tance I X I
) 12 Verified spacmg Ix I I
, 13 Venfied InstallatIOn torque I IxJ
EvaluatIOn report number & date
E5R 2322
Name of product being Installed
HILTI RE 500
Batch Number 2212 L3
2205 L:J
ExpiratIon Date 5'09 5/09
CTIJob# 50805400
SPRINGFIELD
PO Number 108018
LocatIOn ofpropnetary anchors Inspected [to mc1ude gnd
lines, elevatlOns (floors) and draWing detaIls]
181 3'4" x 10" ALL THRREAD EMBED AT 8" INTO
CONCRETE SLAB AT GRIDS F TO G AT 2 TO 1 AT STORR
FRONT ANCHORS TO ANCHOR COT,TJMNS TO ST';:'\.R
CENTERS ARE AT 8" AND EDGE DISTANCE -NA ALL
WORK CONFORMS TO THE MANrTFAr.TrlRF'.RS
SPECIFICATIONS TO THE RF.ST OF MY KNOWT,EnGF', AU.
HOLES WERE CLEAN AND DRY
REPORT SUMMARY
Work Inspected was W Completed 0 In progress
2 Completed work Inspected was In complIance With
GJ Approved plans and speCIficatIOns 0 Shop drawmgs
o RFI 0 DeSign change 0 Submittal 0 N/A
Document #(s) 91 1
Dated 3/31/8
3 Noncompliance Item(s) were noted thiS date, details on
follOWing page(s) 0 Yes 0 No GJ NIA
4 Noncompliance Item(s) were remspected thiS date, detalls
on follOWing pagels) 0 Yes 0 No GJ N/A
D Conform 0 Remam In progress
Report(s) findmgs were discussed and left With
RANDY
of JAMES E JOHN CONSTRUCTION
Based on the Code, approval IS teqUlted ITom the BUilding OffiCIal before the SPECIAL INSPECTED Items noted above can
be covered Carlson Testing has no authonty to direct work of contractors or subcontractors
o See additIOnal teport pagels)
o Dlstnbute attachments
Page ~of _
DaIly Report ofPropnetary Anchors
cn Job # S0805400
For
08/07/2008
ProJect.
SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes
=
In some cases more than one box may be checked for a gIven Item on the front page
Our reports pertam to the matenal tested/mspected only informatIOn contamed herem IS not to be reproduced, except m
full, WIthout pnor authonzatlOn from thIs office
If there are any further questIOns regardmg thIs matter, please do not hesItate to contact thIs office
Respectfully submItted,
CARLSON TESTING, INC
"';Vt'
RevIewed By Steven Dugger
Review Date 08/] 4/2008
BP/KMF
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723
Carlson Testing, Inc.
Mam Office
PO Bo,23814
TIgard Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954
Salem Office
4060 Hudson Ave, NE
Salem, Oregon 97301
Phone (503) 589-1252
FaA (503) 589-1309
Bend 0 mce
PO Box 7918
Bend Orcgon 97708
Phone (541) 330-9155
Fax (541) 330-9163
Daily Report of Proprietary Anchors
Chent SAFEWAY STORES
PrOject SAFEWAY STORE
Address 1891 PIONEER
CTI representative P L
was on site thiS date
Permit COM2008-00471
DFS #(s)
INC - PHIL JUTTELSTAD
#1094 REMODEL - SPRINGFIELD
PKWY E - SPRINGFIELD. OR
SANETRA OBOA 447
05, 2008
to perform SpeCial Inspection for
Aua
SCOPE OF INSPECTION
Checked III with supermtendent or chent representative
Name RANDY
Company JAMES E JOHN CONSTRUCTION
2 Inspection was "IBe" GJ Contmuous
o Penodlc
PROPRIETARY ANCHORS
Yes NoN/A
1 Reviewed prevIOus inspection reports?
2 Reviewed evaluatIOn report?
I ~ I I
Verified followmg Items meet manufacturer's
published InstallatIOn m<;tructJOns
3 Venfied minimum embedment depth of the
anchors
4 Verified installatIOn of the anchors
5 Verified anchor diameter
6 Venfied steel grade
7 Venfied hole diameter
8 Venfied type of dnll bl! used
I 9 Venfied hole cleaning method
110 Verified adheSive applicatIOn
III Venfied edge distance
112 Venfied spacmg
I 13 Venfied installation torque
x
X
x
Ix
Ix
Ix
Ix
I x I
I,{ I
I x I
I I
EvaluatIOn report number & date
ESR #2322
Name of product being Installed
HILTI RE500 so
Batch Number 2212L3
ExpiratIOn Date .Q1.'? 0 0 9
JUrisdiction
cn Job # S0805400
SPRINGFIELD
PO Number
108018
LocatIOn ofpropnetary anchors Inspected [to Include gnd
hnes elevatIons (floors) and drawing details]
181 #4 DOWELS INTO EXISTING STEM WALL AT LINES C
@ 3, EMBED 4 1/2" 181 #4 DOWELS INTO EXISTING
FOOTING AT LINES C @ 3 EMBED 8"
REPORT SUMMARY
I
I
Ix
Work Inspected was GJ Completed D In progress
2 Completed work Inspected was In comphance with
GJ Approved plans and speCificatIOns D Shop drawings
D RFI D Design change D Submittal D N/A
Document#(s) j)ETATJ. 7'Sl 7 Dated 3'31/08
3 Noncompltance Item(s) were noted thiS date, details on
follOWing page(s) DYes D No GJ N/A
4 Noncompliance Item(s) were remspected thIS date, details
on follOWing page(s) DYes D No GJ N/A
D Conform 0 Remam In progress
,.
Report(s) findings were discussed and left with
RANDY
of JAMES E JOHN CONSTRUCTION
Based on the Code approval IS reqUired ITom the BUilding OffiCial before the SPECIAL INSPECTED Items noted above can
be covered Carlson Testing has no authonty to direct work of contractors or subcontractors
o See additional report page(s)
D Dlstnbute attachments
Page _of _
DaIly Report of Proprietary Anchors
en Job # S0805400
For: 08/05/2008
Project
SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes'
In some cases more than one bOA may be checked for a gIven Item on the front page
Our reports pertam to the matenal tested/mspected only Infonnal1on contamed herem IS not to be reproduced, except m
full, WIthout pnor authonzatlon from thIS office
If there are any further questIons regardmg thIS matter, please do not hesItate to contact thIS office
Respectfully submItted,
CARLSON TESTING, INC
RevIewed By Steven Dugger
RevIew Date 08114/2008
PLS/KMF
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAXj503-670-0235
FAXj360-696-9723
Carlson Testing, Inc.
Mam Office
PO Bo,23814
Tlgard Oregon 97281
Phone (503) 684-3460
FaA (503) 684-0954
Salem Office
4060 Hudson Ave NE
Salem Oregon 97301
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
PO Bo,7918
Bend Oregon 97708
Phone (541) 330-9155
Fax (541) 330-9163
Daily Report of Structural Steel
Chent SAFEWAY STORES INC - PHIL JUTTELSTAD
PrOject SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Address 1891 PIONEER PKWY E - SPRINGFIELD, OR Junsd.ctoon
cn representatIve J MERSEREAU OBOA 706
was on sIte thIs date Ju1 28, 2008 to perform SpecJallnspectlOn for
Permit COM2008-00471
DFS #(s)
SCOPE OF INSPECTION
Checked m With supermtendent, chent or shop rep
Name
Company
2 InspectIOn was "IBC" [iJ Contmuous 0 Periodic
3 Work performed D In the field [i] At fab shop
MASS FAB
4 If shop mspectlOn do they have fabrication and QC
procedures? [i] Yes D No D NIA
INSPECTION
1 Revle\\ed prevlOu~ inspectIon reports?
2 Venfied steel materials are In wmpilance b) reviewing
random samples of the mill test reports, "tee I ID
markings or other documentation
I 3 Yenfied weld filler matenals conform
4 Checked steel member" to see they ~ere fabncated and
erected In accordance with the wO'rkmanshlp and
tolerances required
5 Checked welded studs and structural connections "ere
lO<;tJlled as reqUired
16 Venfied hIgh strength bolt" and fasteners conform
17 Venfied the quality of weld" produced b)- "ciders
weldmg operators and tacker" conform
8 Venfied steellrame Jomt details for bracmg, stlffenmg
member locatIOns and apphcatlOn 01 Jomt detail" at each
connectIOn are m compliance bv random sampling
WELDER INFORMATION
Welders Name ON FILE
CertIfication #
Venfied the contractor's Weldmg Procedure
SpecificatIons are m conformance WIth
A WS reqUirement"
2 Venfied the e""entJaI vanables outlmed In the
Weldmg Procedure SpecIfh"atlons were
employed dunng executIon of the work
3 Venfied the weldabilltv of remforcmg steel
other than ASTM A 706
D See additIOnal report page(s)
Yes NoNIA
x
xl
x
I x I
I I x
I x I I
Yes No NIA
x
x
CTI Job #
SPRINGFIELD
S0805400
PO Number
108018
LocatIOn of steel inspectIOn [to mclude gTld Imes, elevations
(floors) and drawmg details]
PERFORMED CONTINUOUS VISUAL INSPECTION ON SHOP
WELDING COLUMN DETAIL 13/S3 12 (1 EA). 1 COLUMN
ENTRY #1, 1 COLUMN ENTRY #2, 1 EA MAJOR ENTRY
HEADER. 1 EA MINOR ENTRY COLUMN #1
x
REPORT SUMMARY
Work mspected was
[i] Completed D In progress
x
2 COf!}pleted work Inspected ,",as In compliance With
[i] Approved plans and specificatIOns D Shop drawmgs
D RFI 0 DeSign change D Submillal D NIA
Document #(s) Dated
3 Noncompliance 1Iem(s) were noted thIS date detaIls on
followmg page(s) DYes D No [i] NIA
4 Noncomphance Item(s) were remspected thIS date
on followmg page(s) DYes D No
o Conform 0 Remam In progress
detaIls
[i] N/A
Report(s) findmgs were dIscussed and left WIth
TERRY
of MASS FAB
x
Based on the Code appro\alls reqUIred from the BUilding OffiCial before the
SPECIAL rNSPECfED Items noted above can be cmered Carlson Testing
has no authonty to dIrect wor"- of contractors or subcontractors ~
Page 1 Af ---'-
o Distribute attachments
DaIly Report of Structural Steel
en Job # S0805400
For. 07/28/2008
ProJect. SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes.
In some cases more than one box may be checked for a gIven Item on the front page
Our reports pertam to the materIal tested/mspected only InformatIOn con tamed herem IS not to be reproduced, except m
full, wIthout prIor authorIzatIOn from thIs office
If there are any further questIOns regardmg thIs matter, please do not hesItate to contact thIs office
Respectfully submItted,
CARLSON TESTING, INC
RevIewed By Steven Dugger
RevIew Date 08113/2008
JJM/KK
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723
Carlson Testing, Inc.
Mam Office
PO Bo,23814
T.gard Oregon 97281
Phone (503) 684-3460
Fa>. (503) 684-0954
Salem Office
4060 Hudson Ave NE
Salem Oregon 9730 I
Phone (503) 589-1252
rax (503) 589-1309
Bend Office
PO Bo,7918
Bend Oregon 97708
Phone (541) 330-9155
Fax (541) 330-9163
Daily Report of Reinforced Concrete
Client SAFEWAY STORES INC - PHIL JUTTELSTAD
Pr~ect SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Address 1891 PIONEER PKWY E - SPRINGFIELD, OR
cn representative P L SANETRA OBOA 447
was on site thiS date Aua 05. 2008
Penn It COM2008-00471
DFS #(s)
JUrisdiction
CTI Job #
SPRINGFIELD
S0805400
to perform Spec.allnspectlOn for
SCOPE OF INSPECTION
Checked In WIth supermtendent or chent representative
Name RANDY
Company JAMES F. ,JOHN CONSTRUCTION
2 Type ofwor~ 0 Concrete GJ Remforcmg
3 Work mcluded 0 Samplmg W InspectIOn
4 InspectIOn was 'lEC' 0 Contmuous GJ PerlOd.c
5 Work performed GJ In the field 0 At precast shop
REINFORCING
I] ReViewed prevIous inspection reports?
12 Forms clear of debrIS?
13 Type, grade, SIze, quant.ty, spacmg and
condItIOn conform?
4 Venfied forms will nommally result m
hardened concrete of the reqUlred
cross-sectIOnal dimenSIOns
5 Venfied locatIOn ofremforcmg steel, p.pes,
condUits and sleeves With respect to
mlmmum concrete cover
16 Venfied type and location of splices, length
of contact laps and mm diameter of bends
/7 Venfied support & anchorage of remforcmg
steel m the forms
18 Venfied structural embedments m the forms
WIth regard to fabncatlon quality and type
9 Venfied structrual embedments m the fonns
With regard to weld InSpection, quantity and
permits Issued
110 Venfied cast m place anchors
Descnptlon of structure Inspected [to mclude grid lmes,
elevatIOns (floors) and drawmg details]
Ves No N/A
I
1
I
x
x
}.
x
x
I X I I
I x I I
I I I x
ST,AR ON ~RAnF: FOR F'RF'.EZF.R A'T' T.TNF. F' R-(.; ra -'~,
AND FOOTING AT C ~ 3
PO Number
108018
CONCRETE
M.x DeSIgn approved? 0 Ves 0 No W N/A
2 Momtored loads arrlvmg atJob site for correct
M,x#
Slump % Air
3 Type of samples made? N/A
Number of sets Samples per set
4 Inspected placmg and consolidation of appro"
cubIc yards of concrete
LocatIOn of concrete placement [to mclude grid lmes, elevatIOns
(floors) and drawmg details]
After samples are te<;ted results wIll follo\\ on break report
x
REPORT SUMMARY
Wor~ mspected was GJ Comp!Jt~d _ D,In progres~ ,
2 Completed work Inspected was m compliance With
GJ Approved plans and specificatIOns 0 Shop drawmgs
o RFI 0 DeSIgn change 0 Submlllal 0 NIA
I y I
Document #(s) PLANS
Dated J..D.l./nA
3 Noncompliance Item(s) were noted thIS date, details on
followmg pagels) 0 Ves 0 No GJ N/A
4 Noncompliance .tem(s) were remspected thIS date details
on followmg page(s) 0 Ves 0 No GJ N/A
D Conform D Remam In progress
Report(s) findmgs were discussed and left With
RANDY
of ,JAMES E JOHN CONSTRUCTION
Based on the Code approval.s reqUired from the BUlldmg OffiCial before the SPECIAL INSPECTED Items noted above can
be covered Carlson Testmg has no authOrity to direct work of contractors or subcontractors
o See additIOnal report pagels) 0 D.stnbute attachments Page of
DaIly Report of Remforced Concrete
cn Job # S0805400
For' 08/05/2008
Project SAFEWAY STORE #1094 REMODEL - SPRINGFIELD
Notes
In some cases more than one box may be checked for a gIven Item on the front page
Our reports pertam to the materIal tested/mspected only InformatIOn contamed herem IS not to be reproduced, except m
full, wIthout prIor authorIzatIon from thIs office
Ifthere are any further questIOns regardmg thIs matter, please do not heSItate to contact thIs office
Respectfully submItted,
CARLSON TESTING, INC
ReVIewed By Steven Dugger
ReVIew Date 08/13/2008
PLS/KMF
SAFEWAY STORES INC - PHIL JUTTELSTAD
TO CITY OF SPRINGFIELD BUILDING DEPARTMENT
ASSOCIATED CONSULTANTS INC - MANOUCH YAGANEH
BENNER STANGE ASSOCIATES - JIM PARK
JAMES E JOHN CONSTRUCTION CO INC - KRIS SIMENSEN
FAX/503-657-6496
FAX/503-384-0459
FAX/503-670-0235
FAX/360-696-9723