DAILY FIELD REPORT
Date Performed
May 1 , 2008
Report Number
722,70091,266
Client
Sycan Development Corporation
Mr Tim Hovet
840 Beltline Road Ste 202
Springfield, OR 97477
PrOject Name
Holiday Inn (Gateway)
919 Kruse Way
Springfield, Oregon
PrOject Location
PO No
Type of Structure
Type of InspectIOn
Permit No
Weather
COM 2006-01505
Inside
Fire Proofing
Field Observations and Comments
Performed Mll,Thlckness determination test on Blaze Shield II Fireproofing on beam and JOiSt at grldllnes Q 5 at Rand
10 to 148, beam W12x14 with 2 5/16" minimum and JOist with 3" minimum which meet and/or exceeded minimum
requirements To the best of our knowledge, the work Inspected above was In accordance with the bUilding department
approved deslqn drawlnqs, speCifications and apphcable workmanship orovlSlons of the International BUilding Codes
Inspector Verlyn Bearden, Certification #5300890,86
CCB # 176269
If you have any questions regarding thiS report, please feel free to contact us at 541,746,9649
Respectfully Submitted,
i5~~dU(~~~
Joseph Vardner, EIT
Branch Manager
c City of Springfield-Denny Wright
Mega Paclflc,Ron Miller
AAI Englneerlng-Harnd Afghan
AAI Englneerlng,Steve Young
RECEIVED
JUN 1 3 ZOOS
THIS REPORT IS PROVIDED FOR THE INFORMATION OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT BY ANY METHOD AND ITS TRANSMITTAL TO A THIRD
PARTY BY ANY MEANS EXCEPT IN FULL WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES IS PROHIBITED
ProfeSSional Service Industries Inc. l04Q-A Shelley Street. Springfield OR 97477. Phone 541(146-9649. Fax 541(146 7163