HomeMy WebLinkAboutPermit Correction Notice 1975-3-24 ~-~ ~ ~ Eaec~cal Inspection R~)Qrt ,/ ~ WIRING INSTALLER Unknown ADDRESS 1001 North 35th Street. SDringfield (CITY OR TOWNI ADDRESS OF INSTALLATION Same L.ABEL NO TYPE OF STRUCTURE ~ 1Ull1D; 11 USED HEIGHT WIRING METHOD: NON-METALLIC SHEATHED CABLE 0 ARMORED CABLE 0 CONDUIT 0 OWNER Huntington Wood Products Same ADDRESS CHANGES ORDERED l. Replace flex on inc line chain to planer 1Fl. 2. Replace lk" L B cover at planer feed. ~, .. 3. Replace cover on LL & LR at planer trans M.C.C. 4. Replace ~" L.B. cover at sweed M.C.C. 5. ReDlace box and cover at Dlaner bottom head orofile. 6. ReDlace cover on Dlaner feed motor. ., 7. Replace cover on 6 x 6JQbox at molder. 8. Remove ~" flex over lath in shop. 9. Remove angle flex connection and seal opening in disc. 10. Seal opening in double switch box at shop door. (Millwright) 11. Seal open K.O. in shop trans. (Millwright). l2. Mark all panels - Millwirght shop. 13. l4. r-,,' . Remove tirex cord.' on trim saw for stud stacker. Secure box on beam over stud stacker. l5. l6. 17. l8. 1..',; Replace l" E.B. cover over sorting chain. Support l" conduit over s,tud stacker. Seal ~" K.O. in control panel for stud stacker. Remove boxes and wires on floor of stud mill. 19. 20. 2l. ReDlace solenoid cover on No. 1 angle machine block conv. Repair loose connection to motor on stud mill decline chain. Support ~" conduit over stud green chain in mill. 22. Secure cover on saw file, gutter. 23. Repair stop button for resaw. COVER FINAl " 'NS"CTO'_~J<' . .~r-'~ ACCOMPANIED BY ~ 747-4221 DATF' 3-24-75 POWER CO, ICITY OR TOWN) , . \