Loading...
HomeMy WebLinkAboutPermit Notice 1996-8-23 ( . . '. "" \ , .r . . /" ~.. \I if" /i J- . ~1 V CJl1 . . Co 197 I ~ ~J ([..au""-\- Engineering Branch 31 0 5th Street Springfield, Oregon 97477 (541) 746-0637 Fax (541) 746-0389 ~ Bob Barnhart City of Springfield Planning and Development 22S'f\{ Sth Street Springfield, OR 97477 ;&0'],07 9~-O"lbq Re: Building Permit # 96~]O'69 Inspection for compriance of requirements for a lateral force system, as listed on our engineering report of 8-23-96, Branch Engineering ,visited the site on 11-12-96. Our findings are as follows. 1) Threaded rod hold-down anchors have been embedded as required at location l'A~'The builder's manner of installation is inconsistent with our original report; however, his installation will provide more than the nescessary uplift restraint required. Hold-down anchors have been embedded as required at location "C". Hold-down anchors have been embedded as required at the amended location "0", as indicated on the amendment to our report, dated 11-7-96. - 2) 3) Hold-downs have been inspected at all locations and meet all requirements. Shears walls have been inspected at locations "C" and "0" and meet all . - requirements. 4) The shear wall at Location "A" require 5/8" gypsum wallboard sheathing on both sides(6d cooler nails 4" o.c. all edges, 8"0.c. field); this work has not been done to date. 5) An underfloor structural inspection was performed. All elements are in compliance with the CABO one and two family dwelling code. Please call me if you have any questions, Sincerely, .....--~.... .. .' . -. . ------) )(j , .'16 %. . . . ~~ " C.....l"" a.... '--" v,. ,-,' Rene Fabricant / TRANSPORTATION CIVIL SURVEYING