HomeMy WebLinkAboutNotes Planner 1/4/2023LIMBIRD Andrew
From:
Sent:
To:
LIMBIRD Andrew
Wednesday, January 04,2023 1 1:07 AM
'DiverJean@gmail.com'
FW 22-000256-PRE - 1354 S 2nd St. - New house, Shop & future ADUSubject:
Hi Ramona, these comments from the Fire Marshal's office arrived late so I am forwarding them to you as
information. There is a new fire hydrant across South 2nd Street from your property at the intersection with Ash Street
so this issue has been addressed.
Andy
From: PH I LLI PS-M EADOW Eric S <EPhil lipsMeadow@eugene-or.gov>
Sent: Wednesday, January 04,202310:49 AM
To: Ll M BIRD And rew <alimbird @springfield-or.gov>
Cc: GORDON Gilbert <ggordon@springfield-or.gov>; PHILLIPS-MEADOW Eric S <EPhillipsMeadow@eugene-or.gov>
Subject: 22-00O256-PRE - 1354 S 2nd St. - New house, Shop & future ADU
**l WARNING: This email originated from outside of your organization. Please do not click on links or
attachments unless know the content is safe.**
Andy,herearemycommentsfortheDlMmeetingtoday. Sorry,butlcan'tattendtoday. Letmeknowiftheyhave
questions and I can connect with them.
Based on the north driveway they show we should have adequate fire access to the house and shop as long as it is an
adequately constructed compacted gravel section. Not sure where the future ADU is so I cannot speak to that.
l'm not sure were the closest hydrant is either.
General Fire Comments.
1.. A 20 foot wide (minimum) fire apparatus access road shall extend to within 150 feet of the most remote portion
of the building's exterior as measured by an approved route around the exterior of the building. Fire access
roads shall be capable of supporting and imposed load of fire apparatus weighing at least 80,000 pounds.
2. Fire hydrants shall be placed such that all portions of proposed buildings shall be within 600 feet of such
hydrants, as measured by an approved route around the exterior of the building (SFC 507.5.1). The fire flow for
new single-family dwellings shall be a minimum of 1,000 gallons per minute at a residual pressure of 20 psi for
structures up to 3,600 square feet.
Eric Phillips-Meadow
Deputy Fire Marshal
Eugene Springfield Fire
Cell - 541-780-4048
Dato Rsceived
[)!rnner: AL
Fire Marshal's Office Hours: Monday - Thursday 6:00am - 4:30pm
1
,k/@-