At your request, the Building Division of the City of Springfield madeanoccupancy
inspection on June 16,1980, at 161 North 17th Street, Springfield,Oregon.
The follow'ing'items must be installed, repaired or replaced to conform to the
Uniform Housing Code as adopted by the City of Springfield:
STRUCTURAL AN DF AND LIFE SAFETY
1. Chimney support is of insuffic'ient sjze or strength to carry imposed load
of masonry chimney. (Section 1001 Uniform Housing Code)
2. Dwel I ing un'it shal l be prov'ided with heatinq facil ities capabl e of maintain'inq
a room temperature of 700-F at a point 3 feet above the floor in all habitable
rooms. (Section 1001 Uniform Housing Code and Section 1311 Structural Speciaf ity
Code )
3. W'indows must be openable to provide necessary vent'ilat'ion and means of egress
(Section 801 and 503 Uniform Hous'ing Code)
ELECTRICAL SAFETY
1. Install not less than a No.6 copper grounding conductor from service panel
neutral bus to an outs'ide grounding e'lectrode. (Section 250.94 National Electrical
Code )
?. .Install not less than No. 6 copper grounding condutor from serv ice panel
rovedneutral bus to an interior cold water p'ipe, terminating with an ap
service ground'ing c1amp. (Section 250-94 Nat'ional Electrical Code
3. Remove sp]iced conductors through I iv'ing room I ight f ixture. (Section 410-30 (c),
410-39, and 300-15 (a) National Electrical Code)
4. Remove kinked conduit below service pane1. (Section 348-9 National Electrical
Code )
5. Install cover on washer outlet. (Section 370-18 (c))
6. Install not larger than 125 amp main breaker in pane1. I\0. 1 aluminum service
conductor. (Section 230-90 (a))
p
)
Occupancy Inspection
Page 2.
SAIIITATIOII:
1. l,Jater heater will require a new pressure relief valve, with drain, and
piped to the exterior of the bu'ilding. (Sect'ion 1007 Plumbing Spec'iality Code)
2. 3/4 inch gate valve shut off requ'ired on cold water suppl-v. (Sect'ion 1005
Plumbing Special ity Code)
3. Water closet in bath does not meet min'imum clearance requirements. (Sect'ion
907 Pl umbi nq Special i t-v Code)
All necessary permits shall be obtained before work starts and all work shall be
accomplished according to applicable codes and inspected before a Certificate of
Compf iance wiiI be issued.
Please direct.all inquiries to the Springfield Building Div'ision at 726-3753.