HomeMy WebLinkAboutPermit Fire 2018-07-09ELECTRIC
OR
MECHANICAL
GAS VALVE
TO ELECTRICAL
SHUTDOWNS AND FIRE
ALARM CONNECTION
(IF APPLICABLE)
MANUAL PULL TO BE
LOCATED ON A PATH
OF EGRESS 10-20'
AGENT CYLINDER AND
CONTROL HEAD TO BE
MOUNTED ACCESSIBLE
BELOW CEILING LEVEL
PIPING NOTES:
*ALL SUPPLY LINE TO BE : U2" SCH. 40 BLACK,
*ALL BRANCHLINE PIPE (TO NOZZLES) TO BE: 3/8" SCH. 40 BLACK.
*ALL FITTINGS TO BE MIN. 150# RATED. N.T.S.
ADDITIONAL NOTES (MIN. PIPING REQ):
'MINIMUM PIPING REQUIREMENTS WHEN PROTECTING RANGE, FRYER OR WOK:
PCL -300
-MINIMUM OF 300 ML AND (4) TOTAL FLOW POINTS ON SYSTEM.
-MINIMUM OF 239 ML AND (2) FLOW POINTS AT OR BEFORE THE RANGE.
GENERAL NOTES
PIPE/CONTROLS ISOMETRIC
1) SUPPRESSION SYSTEM TO BE CONNECTED TO BUILDING FIRE ALARM SYSTEM. (IF APPLICABLE)
2) APPLIANCES ARE ELECTRIC AND GAS -ALL FUEL TO COOKING APPLIANCES TO SHUT DOWN ON SYSTEM ACTUATION.
3) ALL ELECTRICAL POWER UNDER HOODS AND INTEGRAL MAKE-UP AIR TO SHUT DOWN ON SYSTEM ACTUATION.
4) EXHAUST FANS TO CONTINUE RUNNING.
5) FUEL AND ELECTRICAL SUPPLY RESET SHALL BE MANUAL.
6) ALL PIPE TYPE, LENGTHS AND NUMBER AND TYPE OF FITTINGS TO BE IN ACCORDANCE WITH THE MANUFACTURES UL LISTED DESIGN/ INSTALLATION
MANUAL.
7) UL LISTED GREASE TIGHT SEALS AT ALL HOOD PENETRATIONS.
8) CLASS "K" HAND PORTABLE FIRE EXTINGUISHER TO BE LOCATED BY MANUAL PULL NEAR EXIT. PLACARD MEETING REQUIREMENTS OF NFPA 10 & 96 TO BE
CONSPICUOUSLY LOCATED NEAR CLASS "K" EXTINGUISHER.
9) ALL HOOD FILTERS TO BE UL LISTED "BAFFLE TYPE."
GENERAL NOTES:
8 TOTAL (tOAVAILABLE)
3 FOR DU PLENUM, /5 FOR APPLIANCES
TOTAL VOLUME OF PIPE:
1,800 MLS. (1,910 MLS.MAX ALLOWED)
SYSTEMS DESIGNED IN ACCORDANCE WITH
PYRO-CHEM, KITCHEN KNIGHT II, RESTAURANT FIRE
SUPPRESSION SYSTEM MANUAL N0. PN551274 (5) REVISED
DECEMBER 1, 2009
2D DUCT NOZZLES
TO BE CENTERED IN DUCT
OPENING @0-6" INTO
DUCT OPENING
6'-0" HOOD
FUSIBLE LINK
DETECTION LINE
MAX. 100" PERIMETER
EXHAUST DUCT (TYP)
2H 1H 2L
48")
(24". 4811) (24" - 351r)
ABOVE
APPLIANCE
SHELF @MIN. 18" HEIGHT
W/ MAX. 11" OVERHANG
lam' rI oie �jo �j�
n
°Ilo
(MAX. VAT DIM 24"x24" (12" X 24")
18"X27 3/4") GRIDDLE 2 -BURNER
FRYER RANGE
HOOD/COOKLINE
FRONT VIEW
N.T.S.