November 16, 1994
David Gibson
761 West N SI.
Springfield, OR 97477
Subject: Occupancy Inspection at 630 Main SI.
>f
Proposed Use: Boxing Facility
Dear Mr, Gibson,
At your request, the Community Services Division/Building Safety conducted an inspection of
the building at the above address, The purpose of the inspection was to determine the
suitability of the building for the proposed use as indicated,
Based on the proposed occupancy, the existing conditions which are mentioned below do not
meet the minimum Building Safety Code requirements. Corrective measures must be taken
prior to occupancy to install, repair, replace or modify the following items in order for the
building to conform to applicable safety codes:
Front exit doors requiring a key or special knowledge or effort to open from the inside shall be
provided with a sign stating "THIS DOOR TO REMAIN UNLOCKED DURING BUSINESS
HOURS" in one inch high letters.
Provide one class 2A fire extinguisher mounted in an approved location, three to five feet from
finished floor for each 3,000 square feet of floor space, Emergency lighting and exiting shall
be checked by the fire department prior to occupancy issuance,
Plans shall be submitted for construction of the arena floor system, and building permits
obtained prior to commencement of work,
If you need any further information or have any questions regarding the above requirements,