Field Observations and Comments
Performed visual inspection of reinforcing steel and anchor bolts in the following locations: 10' 8" to 16' 0" elevation all
four perimeter walls. Reinforcing steel was checked for grade, size, lap, placement and clearances where applicable,
Reinforcing steel was placed in accordance with approved design drawings and specifications, All cells were
relatively clean and mortar projections are within the limits of the International Building Code. Performed continuous
inspection during the placement of grout in the locations listed above. Grout was placed by pump and mechanically
consolidated. All cells were grouted solid, Cast 1 set of solid test prisms. To the best of our knowledge, the work
inspected above was in accordance with the building department approved design drawings, specifications and
applicable workmanship provisions of the International Building Code. Contractor was advised of all on-site results
and asked to notify our office when additional services are needed.
Tvoe of Material Grout
Supplier ES&G
Mix # 17
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (psi)
Number of Samples
Total YardaCle Placed 20.25 yds
Inspector: Chris Thomason, ICC# 5069949-87
l"~;lInfom!,on
"..,. .To Build On
Engineering . Consulting. 7l!stlng
.
DAILY FIELD REPORT
Date Performed: February 5, 2007 Report Number: 722-60359-57
Client: Mr. Eric Patterson Project Name: Lithia Toyota -
Lithia Toyota Quick Lube
360 East Jackson Street Project Location: 863 Main Street
Medford, Oregon 97501 Springfield, Oregon
P,O, No,: Permit No,: COM 06-0868
Type of Structure: Weather: Clear
Type of Inspection: Structural Masonry
Prisms
ES&G
17
60"
62"
1:00 PM
2500
60"
62"
1:00 PM
1500=fm
3 (solid)
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Respectfully Submitted,
Professional SelVice Industries, Inc.
c: City of Springfield
John Hyland Construction
Doug Snider Architect
./
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y. THE REPRODUCTION OF THIS REPORT, BY ANY METHOD. AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED.
Professional Service Industries, Inc.. 1040A Shelley St.. Springfield, OR 97477. Phone 541n46-9649. Fax 541n46-7163