HomeMy WebLinkAboutPermit Building 2004-5-19 (4)
:.
225 Fifth Street, Springfield, OR
541-726-3753 Phone
541-726-3676 Fax
541-726-3769 Inspection Line
'*:
. CITY OF SPRINGFIELD
Building/Combination Permit
PERMIT NO: 02-00980-01
ISSUED: 05/19/2004
APPLIED: 08/14/2002
EXPIRES: 11/19/2004
VALUE: $ 230,257.00
SITE ADDRESS: 630 Main St
ASSESSOR'S PARCEL NO.: 1703353108900
Spr
TYPE OF WORK: Commercial Miscellaneous
TYPE OF USE: Remodel Commercial
PROJECT DESCRIPTION: Remodel theater building. Phase I, Interior Demolition Only and reroof, existing
structural only. Phase 2, Remainder of structural, interior remodel & marquee
extension. Phase 2 will start in March 2004 and has been modified so that there will be
at least one more phase depending on funding.
Owner: Springfield Renaissance Dev.
Address: POBox 155 Springfield OR 97477
Phone Number: (541) 736-0503
I CONTRACTOR INFORMATION I
Contractor Type Contractor License Expiration Date Phone
Architect Poticha Architects (541) 686-9466
General CHAMBERS CONSTRUCTION
Electrical BUILDERS ELECTRIC INC 4296 12110/2007 541-485-0922
Engineer HOHBACH - LEWIN, INC 541-349-1701
Plumbing TWIN RIVERS PLUMBING 17695 03/11/2005 541-688-1444
I BUILDING INFORMATION I . ,:
\I
~' ~v
# of Units: ~ ,\X1,ilfli~ries: ~!4e'
Primary Occupancy Group: A-2.1 ~<<" k,~ tg'hll of Structure '~~"oor:
Secondary Occupancy Group: <$- S q, , e of Heat: ~fif> ~ ~oor:
Primary Construction Type ~r '\~ ~~<;5water Type: \cPO\0QS~ll'1..~s~~t:
Secondary Construction T~pe: sY:' ~<<,,<<:- ~~ Range Type: "lj~.;s.0 ~0~~~~~arport
# of Bedrooms: ~fV<<-' #' YJ~ {O~. Energy Path: ~o~ '0" 'lfS ~~~~o<'
_,~'" q,<<"~ -(J.,<<"~ ~ \J~_~<;5 Sprinkled Building: . 0\0 <,>,-00~" ov~ @a:~~t*,cf.d:
"'" ,.c..,: -~ -] Ov _~. ,<,>,< ."'~ _,0 ~ _,0
\~~'\~~~~\J ~~ I DEVELOPMENT I~~:{~?~.~~~~~,-e~~~~~\'
1:,<;5 ~ ,'l> ' ~. ~', 0<' !:l~' o~ ~. ~ O~ ~".)'I; REQUIRED PARKING
~ $;.0 '*' ~'l: ~~ ~,-0 eC$ !y
Frontyard Setback: ~ Overlay Dist? ~v <(. q) ~ ~ v0 O~ $\S Total:
Side 1 Setback: # Street Tree$-<R(Ui: -.\,0 .;s.e ~.;s.0 '{P'" Handicapped:
Side 2 Setback: Paved Drive RtIl!:;)<1l()' &.'~C?, \,0 ~0\ Compact:
Rearyard Setback: % of Lot Covera)le: v'li- ~'O0 v0
Solar Setbacks: ~-S
I PUBLIC IMPROVEMENTS I
Street Improvements:
Storm Sewer Available:
Special Instruction:
Sidewalk Type:
DownspoutslDrains:
Notes:
Pal!e 1 of6
Status
Issued
225 Fifth Street, Springfield, OR
541-726-3753 Phone
541-726-3676 Fax
541-726-3769 Inspection Line
Description
Tvpe of Construction
Use Bid Amount
Use Bid Amount
Bid Amount
Bid Amount
Fee Description
Commercial Plan Check
Fire & Life Safety Plan Review
+ 7% State Surcharge
+ 80/0 Administrative Fee
Additional Plan Check
Demolition
+ 7% State Surcharge
+ 8% Administrative Fee
Temp Power 200 amps or less
+ 7% State Surcharge
+ 7% State Surcharge
+ 8% Administrative Fee
+ 8% Administrative Fee
Building Permit
Miscellaneous Plumbing
+ 10% Administrative Fee
+ 7% State Surcharge
Backflow Device
Building Permit
Fixture
+ 10% Administrative Fee
+ 7% State Surcharge
Add, Aller, Extend Circ
Minimum/Adjustment Electrical
Total Amount Paid
.
. CITY OF SPRINGFIELD
Building/Combination Permit
PERMIT NO: 02-00980-01
ISSUED: 05/19/2004
APPLIED: 08/14/2002
EXPIRES: 11/19/2004
VALUE: $ 230,257.00
I Valuation Descrintion I
$ Per Sq Ft
or mulliplier
$1.00
$1.00
Square Footage
or Bid Amount
488,005.00
230,257.00
Value
Date Calculated,
Total Value of Project
$488,005.00
$230,257.00
$718,262.00
11105/2002
03/2312004
If ppt tIiII.I
Amount Paid
Date Paid
Receipt Number
$1,309.85
$806.06
$3.15
$3.60
$20.28
$45.00
$3.50
$4.00
$50.00
$3.15
$128.09
$3.60
$146.39
$1,829.90
$45.00
$177.54
$124.28
$28.00
$991.40
$756.00
$4.50
$3.15
$43.00
$2.00
8/14/02
8/14/02
10/14/02
10/14/02
10/14/02
10/14/02
1114/02
1114/02
11/4/02
1116/02
1116/02
1116/02
1116/02
1116/02
11/6/02
3/31104
3/31104
3/31104
3/31/04
3/31/04
5/19/04
5/19/04
5/19/04
5/19/04
10282
10282
1200200000000000058
1200200000000000058
1200200000000000058
1200200000000000058
1200200000000000183
1200200000000000183
1200200000000000183
1200200000000000200
1200200000000000200
1200200000000000200
1200200000000000200
1200200000000000200
1200200000000000200
1200400000000000423
1200400000000000423
1200400000000000423
1200400000000000423
1200400000000000423
2200400000000000611
2200400000000000611
2200400000000000611
2200400000000000611
$6,531.44
I Plan Reviews I
Pal!e 2 of6
. . CITY OF ~rKll~GFIELD
Building/Combination Permit
Status Issued PERMIT NO: 02-00980-01
225 Fifth Street, Springfield, OR ISSUED: 05/1912004
541-726-3753 Phone APPLIED: 08/14/2002
541-726-3676 Fax EXPIRES: 11/1912004
541-726-3769 Inspection Line VALUE: $ 230,257.00
Fire Marshal-CIIIP 10/21/2002 APP AG I. Plan Review - Phase I,
Demolition, Theater remodel,
Occupancy A2.1
I. Fire Department. Standpipes will
not be required due to limited
combustible load anticipated and
limited ceiling height in the
performance ares.
2. Provide installation, pressure
test, flush of fire line in accordance
with NFP A 24 from the point of
public connection forward to the
building sprinkler system.
3. Demolition procedures are to be
carried out in compliance with teh
code requirements as set forth in
Article 87 of the Uniform Fire Code
as adopted by the City of
Springfield.
Initial Review-CIIIP 08/15/2002 Appr LH
Structural Review 10/03/2002 10/03/2002 10 DLM FedEx'd the following to Tom
Rogers today I. Response to Plan
Review Comments from project
engineer, 2. Structural Plan
Revisions dated 9/19/02 (w/lIxI7
drawings), 3. Supplemnetal
Structural Calculations, 4.
Geotechnical report. dim
Structural Review 03/19/2004 03/2912004 APP JMP Received a fax from Steve McCallen
with Chambers with scope of work
and values for the phases. Phase I
has been completed. This permit is
for Phase II. Fees have been added
for building and plumbing. No
additional electrical application has
been received.
Structural Review 10/29/2002 10/23/2002 APP TR Structural modifications only. Fire
& Life Safety review is not
completed.
Structural-CII/P Pend TR Fed Ex'd Addendum and structural
calculations. Ih
Pal!e30f6
Status
Issued
225 Fifth Street, Springfield, OR
541-726-3753 Phone
541-726-3676 Fax
541-726-3769 Inspection Line
Structural-CIIIP
.
08/26/2002
Wait TR
Pal!e 4 of6
. CITY OF SPRINGFIELD
Building/Combination Permit
PERMIT NO: 02-00980-01
ISSUED: 05/19/2004
APPLIED: 08/14/2002
EXPIRES: 11119/2004
VALUE: $ 230,257.00
Preliminary plan review revealed
the following in part. See job file for
complete letter and code references.
I) The occupant load of the stage
combined with the seating would
resull in an occupant load exceeding
300. The occupancy classification
for the building will be a group A
Division 2.1. Please make the
necessary modifications to the
construction documents for this
classification. 2) Please specify the
distance from the building to the
center of the alley. Ifless than 10
feet, openings in the wall need to be
protected. Due to the construction
of the alcove for the exit doors,
protection at the exterior wall is not
practical. As an equivalent
protection, all construction in the
alcove must be one hour rated with
3/4 hour doors. 3) Depending on
the distance to the center of the
alley, parapet construction, or
ceiling rating, provisions of the
OSSC may need to be addressed.
STRUCTURAL I) Calculation
page 23 specifies a 5x5x5/16 tube.
Where is the thickness of the tube
specified on the plans? 2) The floor
framing,plans do not correspond to
the structural calculations. Provide
revised calculations for review. 3)
Calculation page LI7 specifies an 18
inch footing for the interior CMU
wall, whereas detailll/S5.3 shows
12 inch thickness. Please clarify. 4)
Calculation pages L21 and L22 do
not use the verticle distribution
provisions of OSSC. Provide revised
calculations for review. 5)
Calculation page W3 specifies 4 inch
nail spacing for the subdiphragm.
Where is this noted on the plans? 6)
Calculation page RI and R2 indicate
the existing roof joists would be over
stressed approximately 80% with
code prescribed snow loads. Due to
the change of occupancy
classification, these joists need to be
.
. CITY OF ~rKll~\.Jl'l~LD
Building/Combination Permit
PERMIT NO: 02-00980-01
ISSUED: 05/19/2004
APPLIED: 08/14/2002
EXPIRES: 11119/2004
VALUE: $ 230,257.00
Status
Issued
225 Fifth Street, Springfield, OR
541-726-3753 Phone
541-726-3676 Fax
541-726-3769 Inspection Line
upgraded. 7) Detail9/S7.1, as
referenced on sheet S3.1, elevation
line 2.6, appears to have been
omitted. Provide a copy for review.
8) Provide a copy of the
geotechnical report for review.
To Request an inspection call the 24 hour recording at 726-3769. All inspection requested before 7:00 a.m.
will be made the same working day, inspections requested after 7:00 a.m. will be made the following work
day.
Ueollire~n~ne{'tions I
I Temporary Electric: Approval required prior to Utility Company energizing pole.
2 Footing: After trenches are excavated.
3 Foundation: After forms are erected but prior to concrete placement.
4 Framing Inspection: Prior to cover and after all rough in inspections have been approved.
5 Epoxy Anchors: To be done by Certified Spcial Inspector. Provide Inspection results to City Building Inspector.
6 High Strength Bolting: To be done during construction by a State Certified Special Inspector. Provide inspection
resulls to City Building Inspector.
7 Structural Masonry: To be done during construction by a State Certified Special Inspector. Provide results to
City Building Inspector.
8 Bolts Installed in Concrete: To be done by a State Certified Special Inspector. Provide inspection test reports to
City Building Inspector.
9 Structural Concrete: In excess of2500 psi. To be done during construction by a State Certified Inspector.
Provide results to City Buiding Inspector
10 Structural Welds: To be done during construction by State Certified Special Inspector. Provide inspection test
results to City Building Inspector.
II Underfloor Plumbing: Prior to insulation or decking.
12 Slab: To be made after all inslab building service equipment, conduit piping and other equipment items are In
place but prior to concrete.
13 Fire Department Sprinkler System: Prior to cover. Hydro pressure test, fire line flow test.
14 Final Fire Department. After all requirements of the Fire Department have been met.
15 Final Building: After all required inspections have been requested and approved and the building is complete.
16 Underslab Plumbing: Prior to filling the trench and including required testing.
17 Rough Plumbing: Prior to cover and including required testing.
18 Final Plumbing: When all plumbing work is complete.
19 Underslab Electric: Prior to cover
20 Rough Electric: Prior to Cover
21 Final Electric: When all electrical work is complete.
22 Structural Concrete: In excess of 2500 psi. To be done during construction by a State Certified Inspector.
Provide resulls to City Buiding Inspector
23 Backflow Device: Prior to covering and provide a copy of the test report on site at the time of inspection.
Pal!e 5 of6
.
Status
Issued
225 Fifth Street, Springfield, OR
541-726-3753 Phone
541-726-3676 Fax
541-726-3769 Inspection Line
. CITY OF SPRlNuNJ!.LIJ
Building/Combination Permit
PERMIT NO: 02-00980-01
ISSUED: 05/19/2004
APPLIED: 08/14/2002
EXPIRES: 11/19/2004
VALUE: $ 230,257.00
By signature, I state and agree, that I have carefully examined the completed application and do hereby certify that all
information hereon is true and correct, and I further certify that any and all work performed shall be done in accordance with
the Ordinances of the City of Springfield and the Laws of the State of Oregon pertaining to the work described herein, and
that NO OCCUPANCY will be made of any structure without permission of the Community Services Division, Building Safety.
I further certify that only contractors and employees who are in compliance with ORS 701.005 will be used on this project.
I further agree to ensure that all required inspections are requested at the proper time, that each address is readable from the
street, that the permit card is located at the front of the property, and the approved set of plans will remain on the site at all
times during construction.
~ii~i?:~~-,,- ~
Pal!e 6 of6
5-IK-OLJ
Date
225 FIFTH STREET. SPRINGFIELD, OR 97477 . PIl:(541)726-3753 . Flo~if~~~~llr9i68ljassubmittedhasthefoIlOWlng
ELECTRICAL PERlIfIT APPLICATION appr~;a~, does not require specific land use
City Job Number 0'2...- 00 ~ eO - 0 \ Date 6 S ~ l '? -C>~ Zoning (l,(l...-.
,< ,,_, ,,",', ".__"OetA" - ,-?-':"'5-0:tk~""
3, ,:COMPLEl'ER ' C ' ULEBELOW',< . ' "",'
'''' '.'., ",.".-,-,,,.,.,j\{ltllo~ze{f~ature'" . " ,{, <";,,..?<=K ' ","
,.;.' ..,.....~.,...-';'"~'7~..,~..""'.,~ ....T. . _ ~. ~,."l'-':' "'.., :..~,....~..:, """1\
1. EL2f:A'!lP!'!.:Q!Sl.NSr*M"l1, o.!Y:" ic:D":,.iA
(;/3lS-" Met;: n"S€ ,,~, .
:t"': : .,,-.. '~'. " '".. . ~ ,", '" ';;. '. . "'. ..' . ,'....- ." , . ...
A, ,Ncw:Rcsideltiial"':Singlc'or Ji-Iulti-Faiitil\' per 'd,;'cUlng '~nit.; "
.. -,,'. <..._.::......::.. . ,'. .,.. "J ,.'~' . ~ -' , '.:'. ....l. ...... '.'
LEGAL DESCRIPTION
_l '1. Cl~ -:''5" '3> l b ~")oo
Service Included
JOB DESCRIPTION 1000 sq, ft, or less
\ ) ,^ .J, 0 11 r '''''') _ --1 r rl. f Each additional 500 sq. ft, or
r nv I \J) Y\ A '(1\ ) tar 1-. ec;\-Y\ C'cc portion thereof
Permits are non-transferable and expire if work is Each Manufact'd Home or
not started within 180 days of issuance or if work is Modular Dweiling Service or
Suspended for 180 days, Feeder
~::::'i~~'i;;''r'''::;sv '_1't,.,::~:.,\!:,,"""',-:::r, .~:'"' '.',-:f"{.~; ."""":'.:.'1.... ~ "r~--7''''.'' ,/.!.:":;. _H' ,-,-' ~"~"~. ,~:-. ~ "'$':: ". ..~ :";,', :f' ....'. ::""":'!-:'
:~~.:
"'-,CONTRACTORINSTALI:ATION ONLY B. ',SerVIces or, Feeders ~.Installahon.Allernhons or Relocation::
2. ~~"':I,!l,(-ii;{llr~.;~;.o;..::;"'~~,,~.-:';;'I.:,/,'~)<H"i.;~tO~',~,::::;:t...t'''':'.~,..",,~..,: ot:.' " . .'.'..,...... }"';', ...,t,,' ~h.'~' ,..~.':o'i;" ," . I"
Electrical Contractor RllI'ldpfS ' [iec+r, t InC 200 Amps or less $ 63,00
20 I Amps to 400 Amps $ 75,00
40 I Amps to 600 Amps $125,00
601 Amps to 1000 Amps $163,00
Over 1000 AmpslVolts $375,00
Reconnect Only $ 50,00
$106,00
$ 19,00
$50,00
Address
ICJS Mack'\0I\
City
fl'5C'ne
Phone
4 ~:::d)1~;;:z
Supervisor License Number 3290 - S
Expiration Date 10, 1- 04
Constr, Contr, Number 4:;;lq ( 0
Expiration Date I'J. - r () - 01
....rc,....'...',..,,,.'.........e'-;lf. 'T.';J'"!''''T',-''''r~' ~)'~r,.".T';"'~~fI' .,.'"'....1?~.\. 'l"'~.. "R;1'''I-''''''''''l
S. .':t.(".:., -...' ,'. 'l~ -. .~ ....~.- ,~',I ,~;,..:..". -'J.{ 1'-". i.O"', "..' ... ;.,
C. ,i !~~J:>.or~ry.~~,r:vl~~~ or~'!.!.~er~:/::'~:~'~) '.'~"<::'~'\lii'/:~ :G'~~~~~' :;~'.~;~',b\~'~
Installation, Alteration or Relocation
200 Amps or less
201 Amps to 400 Amps
40 I Amps to 600 Amps
Over 600 Amps or 1000 Volts see "B" above,
f,'- ';'; -:::',.. ...... ' "J. rl~:: ~.\I'.::'(;~,:=::~:,.J :'~r'-:'<~k8~;' 'r':~:'::: ::~~f:H:~::,{~r:::-~i,~'.S~:,T~.W.. ~:~
D. . Branch CirCUits \I"~ . ""\1" .j....i:u\."~.i.. .' '~'. "I~.'~'1' . -, -O;,'~,,-.:, -~ I' )>111'",
..' '. ,I. . " .... ~ !"', ~~' ," '. ... . , ,,,~ ,.' "',' ':"'!1' ,,' ':'" ,"', I
$ 50,00
$ 69,00
$100,00
-
New Alteration or Extension Per Panel
One Circuit --L $ 43,00
iZ-:et--\. \).E-J Each Additional Circuit or with
, Service or Feeder Permit
43-
-:;:'?(Z..d{~ E"('C..l..-t::>
Owners Name W i \ \ 'S; h
Address 20 ~ ,tS5
City ~1t-lGEl~L-D Phone l3b - 0 563:>
$ 3,00
,~;.~' ..~.,..,,_.,~,.1'\ '",':<~:', ,'.-'Ct.';,.,..,,; ....~,....,."> '.. J' ", . ,'-' f",
E. ,Miscellnneous (Service/feeder not htcluded),-Ench Installation
" ....' , .".- "."...,. '. -'. . ." .
-'
....
Pump or irrigation
Sign/Outline Lighting
Limited Energy/Residential
Limited Energy/Commercial
$ 50,00
$ 50,00
$ 25,00
$ 45,00
OWNER INSTALLATION
The installation is being made on property I own which
is not intended for sate, lease or rent.
Owners Signature:
Minimum Electric Permit Inspection Fee is $45.00 + Surcharges
~~':I:: :-...:....-.; """":;1..;,'"; ......-."::F~...-'~..~~..-f~ .~ .~. 71:1:;..-
4.-;'SUBTOTAL,OFABOVElc', ~':.:;,; ,:<,:,";":
":.t'~.,". :"!;" ",~.':q':,~";,,,,<;~,, ". .:.
7% State Surcharge
10% Administrative Fee
4:--5" ,CO
:, ,lS"
~,SO
5'2..,65"'
Inspection Request: 726-3769
TOTAL
Shored Drive{T:)/Building Fonns/Elettrical Permit Application I-03.doc
225 Fifth Street
Springfield, Oregon 97477
541-726-3759 Phone
Job/Journal Number
02-00980-0 I
02-00980-0 I
02-00980-0 I
02-00980-0 I
Payments:
, Type of Payment
CreditCard
5/19/2004
.
RECEIPT #:
~~~R.'.!"'!.~~ -.-- i
Wit,
- '~,.~ i
. ~ ,f
~ty of Springfield Official Receipt
.elopment Services Department
Public Works Department
2200400000000000611
Description
Add, Alter, Extend Circ
Minimum! Adjustment Electrical
+ 7% State Surcharge
+ 10% Administrative Fee
Paid By
BUILDERS ELECTRIC
Received By
jmp
Page 1 of 1
Date: 05/19/2004
Item Total:
Check Number Authorization
Batch Number Number How Received
000837
026717 In Person
Payment Total:
8:49:33AM
Amount Due
43,00
2,00
3,15
4,50
$52.65
Amount Paid
$52.65
$52.65