Daily Field Report
Client: Ms. Kristen Karle Project: The Royal Building Date: 01-30-07
St. Vincent de Paul 501 Main Street Project No,: 2067145
P.O. Box 24608 Springfield, Oregon Report No.: E15238
Eugene, Oregon 97402 Inspector: M. Meyer
10 No.: 0877905-84
ICC
Inspection of: Masonry Weather: Clear Continuous Inspection: 0
Contractor: Meili Construction BP No.: COM2006-00624 Periodic Inspection: Ii!
Performed inspection on the reinforcing steel in the 8" CMU walls on line G, from 1 to 6
(12'0" to 16'0"). Reinforcing steel was checked for grade, size, lap, spacing, quantity
and clearances, where applicable. Cells were relatively clean and free of excessive
mortar projections. Observed the placement of 5.0 yards of MBI 7.5 sack grout (Mix
712-G). Grout was placed by pump and was mechanically consolidated. Grout slump
:1:9"; grout temperature 550F; and air temperature 440F. Note: Grout was not placed in
last :1:5' at both ends of wall to avoid filling bond beams containing #6 horizontal rebar
for lintels on iines 1 and 6 which are not yet constructed.
~
To the best of our knowledge, the work inspected was in accordance with revised plans
dated 08-30-06 and applicable workmanship provisions of the I.B.C., except if noted
above. Curt Dawson (Meili Construction) was asked to notify our office when additional
services are needed.
Reviewed By:
A.'-I,~
Michael L. Mefer-
Technical Manager
c: Meili Construction - Curt Meili (e-mail)
Melli Construction - Curt Dawson (e-mail)
Bergsund Delaney Architecture & Planning (e-mail)
Hohbach-Lewin Structural Engineers (e-mail)
City of Springfield
MLM:jm
This report andlor enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc.'s written authorization.
750 rwv Carel Avenue . Corvallis, Oregon 97330 . phone(541)757-4698' fax (541)757-2991
29540 BAirpatRoad' Eugene, Oregon 97402, phone(541)68<h'l849' fax (541)684-3851