Geoted1nical & Constr1.xfun Services
Daily Field Report
Ir~'ltflrt:"lrIMl'llIh'.IHIJI
Client: Ms. Kristen Karle Project: The Royal Building Date: 01-31-07
St. Vincent de Paul 501 Main Street Project No,: 2067145
P.O. Box 24608 Springfield, Oregon Report No.: E15238
Eugene, Oregon 97402 Inspector: M. Meyer
10 No.: 0877905-84
ICC
Inspection of: Masonry Weather: Clear Continuous Inspection: 0
Contractor: Meili Construction BP No.: COM2006-00624 Periodic Inspection: Ii!
Performed inspection on the reinforcin9 steel in the 8" CMU walls on line G, from 1 to 6
(16'0" to top). Reinforcing steel was checked for grade, size, lap, spacing, quantity and
clearances, where applicable. Cells were relatively clean and free' of excessive mortar
projections. Observed the placement of 2.5 yards of MBI 7.5 sack grout (Mix 712-G).
Grout was placed by pump and was mechanically consolidated. Grout slump 8+"; grout
temperature 560F; and air temperature 440F. Note: Grout was not placed in last t5' at
both ends of wall to avoid filling bond beams containing 1#3 horizontal rebar for lintels on
lines 1 and 6 which are not yet constructed.
To the best of our knowledge, the work inspected was in accordance with revised plans
dated 08-30-06 and applicable workmanship provisions of the I.B.C., except if noted
above. Curt Dawson (Meili Construction) was asked to notify our office when additional
services are needed.
Reviewed By:
jlJ.~,
Michael L. Me r
Technical Manager
c: Meili Construction - Curt Meili (e-mail)
Meili Construction - Curt Dawson (e-mail)
Bergsund Delaney Architecture & Planning (e-mail)
Hohbach-Lewin Structural Engineers (e-mail)
City of Springfield
MLM:jm
This report and/or enclosed test data is the confidential property of the client to ...mom it is addressed and pertains to the specific
process and/or material evaluated. As such, information contained herein shall not be reproduced in part or full andlor any part
thereof be disclosed without FEI Testing & Inspection, Inco's written authorization.