HomeMy WebLinkAboutPermit Correspondence 2002-9-12
~lZ{OZ UU:i4 ~AA 7410896 JOHN HYLAND CONST ~ ROBERT LEBLEU
SEP-12-02 THU 9:46 AM BA~R BARRETT TURNER FAX NO. 4IIt1 389 8033
.
,
-e
~OOZ
p, 2
HEINSKlN SNGINBERING, INC.
Electrical Engineers
37 NW Irving Avenue Bend, oregon,97701
Tel/Fax:541.385.7773
September 11, 2002
Todd Turner
BaJbet, Barrett and Turner, AIA
960 S.W. Disk Dr, Suite A
Bend, Oregon 97702
S~p ,
I ~ h-~
, "C(.~
Dear Mr. Tumer:
ODOT SprlDgfield - Request for Information RFI 037
The switchboard will be modified by the manufacturer (Sqvare D) to allow installation in the
c1assiIied area. A third section will be added to the switchboard wbich wiD allow the bottom 18
inches oflhe cabinet interior to be dear. The new lineup will be mounted on II three inch
hous .:, ~ .,..:ng pad. All <:onduitS stubbed up into the bottom of the enclosure will be rigid steel
without couplings to a point above 18 inches &om the finished Ooor.
Sincerely,
CJ-L-1" -.) ~
Dennis L. Heinekin
'I,
"..