Loading...
HomeMy WebLinkAboutPermit Correspondence 2002-9-12 ~lZ{OZ UU:i4 ~AA 7410896 JOHN HYLAND CONST ~ ROBERT LEBLEU SEP-12-02 THU 9:46 AM BA~R BARRETT TURNER FAX NO. 4IIt1 389 8033 . , -e ~OOZ p, 2 HEINSKlN SNGINBERING, INC. Electrical Engineers 37 NW Irving Avenue Bend, oregon,97701 Tel/Fax:541.385.7773 September 11, 2002 Todd Turner BaJbet, Barrett and Turner, AIA 960 S.W. Disk Dr, Suite A Bend, Oregon 97702 S~p , I ~ h-~ , "C(.~ Dear Mr. Tumer: ODOT SprlDgfield - Request for Information RFI 037 The switchboard will be modified by the manufacturer (Sqvare D) to allow installation in the c1assiIied area. A third section will be added to the switchboard wbich wiD allow the bottom 18 inches oflhe cabinet interior to be dear. The new lineup will be mounted on II three inch hous .:, ~ .,..:ng pad. All <:onduitS stubbed up into the bottom of the enclosure will be rigid steel without couplings to a point above 18 inches &om the finished Ooor. Sincerely, CJ-L-1" -.) ~ Dennis L. Heinekin 'I, ".. ""01 ,".,' ..-'....:r ')