RFI #: 222 Date Created: 316/2008
Answer ,Company 'vI"
Robertson/Sherwood/Architects
. .;A'nswer~yllll!Jl~~ ~Auih~cr~11""r~"r7 ~~AI~itio'rea;Br ~I!
'RElndy N'lshlmura ~>> John ~~;~n~' ~~structlo~, Inc "'~~~e ~~; Houten .- .
POBox 7867
Eugene, Or 97401
Co-ResponqeJlt ~~ ~";'[;[~~~~ "
Keith Hubbard, Balzhlser & Hubbard Engineers
. 'AuthoFRFI'illlJ#mb'er':,,':
,"-.'" f~~=\>""
Subject
Computer Room 2135 NC and FM 200
'''~~:~ls,cip.line;~:'::~
Architectural
,H G!ltegory ~
Clanflcatlon needed
Cc: Company Name
#J7~:Conta~ct Name : . .~~Coples' Notes";;:,
Question'
Date~R.egtjlrea: 3/7/2!ill&;
RFP #80 extends the walls full height around the computer room to contain the air conditioning and the gases from the
FM 200 System
The south wall of Room 2135 does NOT have acoustical insulation which that would also act as thermal Insulation Should
this wall also have insulation?
If the walls have Insulation should there also be a vapor barner Installed on the warm air side of the wall?
If the room needs to be protected pressure-wise due to the FM 200 system, should the man door have a smoke seal and a
door bottom? Do the electncal outlets have a need to be fire caulked due to the smoke/gas potential?
While the FM200 gas by Itself IS not harmful as It IS the same gas used by people who use an Inhaler due to asthma, when
this gas comes Into contact with open flame It turns Into carbon monoxide
Just wanted to make sure to what extent we take this protection
Suggestion
Answe! Date Answ~ed:. 3!t11j20,Q8
Include thermal insulation and a vapor retarder In all of the walls that surround Room 2135 (the Insulation and vapor
retarder, which will be Installed on the "warm" side of the walls, shall extend up to the underside of the structure above)
Also, prOVide a smoke seal and door bottom sweep or seal Finally, caulk the electncal outlets to minimiZe smoke/gas
Infiltration
Add these costs to the proposal assOCiated with RFP #80
Prolog Manager
Printed on 3/6/2008