Subject: GRANT OF TEMPORARY OCCUPANCY (15 DAYS)
Sears - 3030 Gateway Street, Springfield, OR.
Temporary Occupancy has been granted at the above address for a period of
15 days from the date of this notice.
This certificate is issued pursuant to the requirements of Section 307(d}
of the Springfield Building Safety Code Administrative Code, certifying
that portions of the building may be used prior to completion of the
items described below.
The following items shall be completed and inspected within the granted
period for Temporary Occupancy, after which permanent occupancy will be
granted:
1. Fire dampers in walls of the Small engine repair room #119 shall
be fastened to the structure on both sides of the damper in
accordance with the damper installation instructions, or an approved
alternative method.
2. Install a temperature mixing valve on the hot water line
supplying the rest room lavatories to limit the outlet temperature to
a maximum of 110 Degrees FahL-enheit. (Plumb. Specialty: Code Sec.912)
3. Provide protection on drains and angle stops on lavatoLY sinks
intended for handicapped use. (}I.NSI A1l7.1 Sec. 4 .19.4)
4. Install Convenience outlets within 25 feet of roof top HVAC
units above Auto Center. (Mech. Specialty Code Sec.509)
5. Install address numbers (4" high) at a,location readily visible
from the Street-side~parking area. (Str. Specialty Code Sec.513)
6. Complete installation of oil tanks. Coordinate permit and
inspection requirements with the City Fire Marshal.
7. Secure gas line. supports on roof in an appropriate manner.
.
.
8. Provide circuit identification labels and panel covers at all
electrical branch panels.
9. Complete all electrical lighting and trim,
10. Remove switches from drop lights in Auto Center, or replace light
fixtures with unswitched type.
11. The data processing room shall comply with Electrical Safety
S'pecial' Code (NEC) .requirements for disconnection of all equipment,
including the air conditioner. '
12. Provide and maintain a minimum of 36" in front of all electrical
panels. Electrical rooms and areas dedicated for electrical
equipment shall not be used for storage of combustibles.
13. Provide disconnects for exterior signs in an approved manner.
14. Install local disconnect for trash compactor to meet NEC
requirements.
~:~~