HomeMy WebLinkAboutPermit Field Test & Inspection Report 1998-11-16 ~ . L "~;l Information ",..,. .To Build On Engineering. Consulting. Testing . Pittsburgh Testing Laboratory Division f~ REPORT OF FIELD COMPACTION TESTS * TESTED FOR: NOEL CORLISS NOEL CORLISS CONCRETE 90858 LALONE ROAD SPRINGFIELD, OR 97478 PROJECT: RESIDENCE - KEVIN PRIDGIN 1480 LEXINGTON AVENUE, EUGENE PERMIT NO. 98-00337-01 DATE: November 16, 1998 OUR REPORT NO.: 722-80276-1 PAGE 1 OF 2 TEST DATA: (1) EUGENE SAND & GRAVEL 3/4"-0 (CLIENT SUPPLIED PROCTOR) VALUE OPT. MOIST. - 11.5 MAXIMUM I I COMMENTS' Min I TEST TEST SOILIC LAB DRY * WATER WET DRY c6~~;g~N Spec. 95% NO. DEPTH ELEVATION NUMBER DENSITY CONTENT DENSITY DENSITY 1 6' FG 1 124.5 5.4 113.7 107.9 ;['8 6""7";11 - B I 2 6" FG 1 124.5 5.9 117.9 111.3 I @9'P.t4jlll - B I 3 6" FG 1 124.5 5.4 125.3 118.9 I 95.5 1 - A I 4 6"-. . FG 1 124.5 5.8 120.6 114.0 ;J9,ioA6;' 1 ". B 5 4" FG 1 124.5 9.4 132.7 121. 3 97.4 1 - A - C I .. J 6 6" FG 1 124.5 9.3 130.7 119.6 96 .1 1 - A .- C TEST LOCATION: OVEREXCAVATION OF BUILDING PAD TO SOUTH OF EXISTING RESIDENCE 1 PAD A, SOUTH SIDE 2 PAD A, EAST SIDE 3 PAD B, WEST SIDE 4 PAD B, EAST SIDE 5 PAD A, EAST SIDE 6 PAD A, SOUTH SIDE NOTES: TESTS PERFORMED PER ASlM 02922-91 & ASTM 03017-88(93) "COMMENTS: DENSITIES SHOWl\1: Lbs. per cubic fool WATER CONTENT: Percent of dry weight PERCENT COMPACTION: Based on maximum dry dens~y obtained on sample indicated by soil 10 number. * (1) TEST INSTRUMENT: TROXLER REMARKS: PSI did not monitor the material placement. 1. FILL MATERIAL 2. BACKFILL 3. BASE COURSE 4. SUBBASE 5. SOIL CEMENT 6. OTHER A. TEST RESULTS COMPLY WITH SPECIFICATIONS B, PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS C. RETEST OF PREVIOUS TEST D. MOISTURE IN EXCESS OF SPECIFICATIONS E. MOISTURE BELOW SPECIFICATIONS STANDARD COUNT M: 736 ADJUSTMENT DATA M: D: 2758 D: . TECHNICIAN: MIKE DEWEY Respectfully submitted, , Professional Service Industries, Inc. cc: CITY OF EUGENE THESE TEST RESULTS AI"PL Y ONLY TO THE SPECIFIC LOCATIONS NOTED AND MAY NOT REPRESENT ANY OTHER LOCATIONS OR ELEVATIONS. REPORTS MAY NOT BE REPRODUCED. EXCEPT IN FULL. WITHOUT INRITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES, INC. PSI A-l0o.2 (3)F Professional Service Industries, Inc.. 2710 West 5th Avenue. Eugene, OR 97402. Phone 541/484-9212. Fax 541/344-2735 ~ . l ra~;l Information ,,~. .To Build On Engineering' Consulting . Testing . Pittsburgh Testing Laboratory Division .' REPORT OF FIELD COMPACTION TESTS TESTED FOR: NOEL CORLISS NOEL CORLISS CONCRETE 90858 LALONE ROAD SPRINGFIELD, OR 97478 PROJECT: RESIDENCE - KEVIN PRIDGIN 1480 LEXINGTON AVENUE, EUGENE PERMIT NO. 98-00337-01 DATE: November 16, 1998 OUR REPORT NO.: 722-80276-1 PAGE 2 OF 2 TEST DATA: (1) EUGENE SAND & GRAVEL 3/4"-0 CLIENT SUPPLIED PROCTOR VALUE OPT. MOIST. = 11 TEST NO. TEST DEPTH ELEVATION SQILID NUMBER MAXIMUM LAB DRY * DENSITY WATER CONTENT ~ DRY PERCENT DENSITY DENSITY COMPACTION COMMENTS. 7 4" FG 1 124.5 10.1 134.3 122.0 98.0 1 - A - C TEST LOCATION: OVEREXCAVATION OF BLDG. PAD TO THE SOUTH OF EXISTING RESIDENCE 7 PAD B, WEST SIDE NOTES: TESTS PERFORMED PER ASTM 02922-91 & ASTM 03017.88(93) .COMMENTS: DENSITIES SHOIJIJN: Lbs. per cubic foot WATER CONTENT: Percent of dry weight PERCENT COMPACTION: Based on maximum dry densijy obtained on sample indicated by 501110 number. * (1) TEST INSTRUMENT: TROXLER REMARKS: PSI did not monitor the material placement. FG = FINAL GRADE % COMPACTION REQUIREMENT PROVIDED BY CLIENT. TECHNICIAN: MIKE DEWEY 1. FILL MATERIAL 2. BACKFILL 3. BASE COURSE 4. SUBBASE 5. SOIL CEMENT 6. OTHER A. TEST RESUL T5 COMPLY WITH SPECIFICA liONS B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS C. RETEST OF PREVIOUS TEST D. MOISTURE IN EXCESS OF SPECIFICATIONS E. MOISTURE BELOW SPECIFICATIONS STANDARD COUNT M: ADJUSTMENT DATA M: D: D: Respectfully submitted, Professional Service Industries, Inc. CC: CITY OF EUGENE THESE TEST RESULTS APPLY ONLY TO THE SPECIFIC LOCATIONS NOTED AND MAY NOT REPRESENT ANY OTHER LOCATIONS OR ELEVATIONS. REPORTS MAY NOT BE REPRODUCED, EXCEPT IN FULL, \NlTHOUT V\lRITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES, INC. PSI A.10G-2 (3jF Professional Service Industries, Inc.. 2710 West 5th Avenue. Eugene, OR 97402. Phone 541/484-9212. Fax 5411344-2735 DEC 16 '98 15:51 FR TO 6826806 P.02/03 , . . REPORT OF FIELD COMPACTION TESTS TESTED FOR: NOEL CORLISS NOEL CORLISS CONCRETE 90858 LALONE ROAD SPRINGFIELD. OR 97478 PROJECT: RESIDENCE - KEVIN PRIDGIN 1480 LEXINGTON AVENUE, EUGENE PERMIT NO. 98-00337-01 DATE: November 16, 1998 REVISION #1 OUR REPORT NO.: 722-80276-1 PAGE 1 OF 2 TEST DATA: (1) EUGENE SAND & GRAVEL 3/4"-0 (CLIENT SUPPLIED PROCTOR) VALUE OPT. MOIST. = 11.5 MAXIMUM I COMMENTS. TEST TEST 60lLID lAB CRY . WATeR WEr DRY C6~~~~N Spec. 95t Min NO. OGPTH ELEV",TION NUMBER DENSITY CONTENT DENSITY O~S1TY 1 6' FG 1 124.5 5.4 113.7 107.9 86.7 11 - B -1 2 6" FG 1 124.5 5.9 117.9 111.3 89.4 1 .. B 3 6" FG 1 124.5 5.4 125.3 118.9 95.5 1 - A 4 6" FG 1 124.5 5.8 120.6 114.0 91. 6 1 - B I 5 4" FG 1 124.5 9.4 132.7 121.3 97.'1. 1 - A - C 1.6... 6" FG 1 124.5 9.3 130.7 119.6 96 .1 11 .. A - C TEST LOCATION: OVEREXCAVATION Of' BUILDING PAD TO SOUTH OF EXISTING RESIDENCE I 1 I PAD A. SOUTH SIDE I I 2 I PAD A. EAST SIDE I I I _.....-...... I 3 PAD B. WEST SIDE --,...~.,,- I 4 PAD B. EAST SIDE I 5 PAD A. EAST SIDE 16 PAD A. SOUTH SIDE NOTES: TESTS PERFORMED PER ASTM 02922.91 & ASTh1 03017.88(9J) "COMMENTS: otNslTlC' SHO~: Lbs. P.8r cubic fgol WA'fe:R CONTeNT: Psroenl ofdrv I/I$ighl pl:l'ZCENT COMPACTION: Base6 on rmuimum dry ~~~Tbtyn~':n't~~ on !l~mple inrjic-..lc:d by . (1) TEST INSTRUMENT: TROXLER REMARKS: PSI did not monitor the material placemene. ,. FILL MAlERIAL 2. BACKFILL 3. BASE COURSE 4. sueBAS~ 5. SOIC C....NT 6. OniER ... TE'Tm~TS Cg,MPL Y WITH 5P'CIFlc~TIONS B. pe~c MP~'rlTJW ooe. NoT COMPLY 8: ~s ~ :~ee~VIJlii~ecIFlc"TloNs E. MOISTURE BEt8w SP~CIFICATIONS STANDARD COUNT M: 736 ADJUSTMENT DATA M: 0: 2758 0: TECHNICIAN: MIKE DEWEY Respectf"lly submitted. ProfessiDnal Service Industries, Inc. ce, CITY OF EUGENE TIiESETEST RESULTS ,lPp\'VOI'CLvfQfHi5PiClFlC: LOCATTOHCNO'TliDAHDMAV NOT REPRESENT AN'(aTHEI\ UlCllnol'l::i 101'1: ELl!VAnOrols,' R6pORTIi: 1oU.'r' IoIOT Iii A&:PA(JIJUC:~D. EXOEPT IN FULL, ~OUT wIUTTEN PEfU,I:J3IoN 110'1' PROI'DSIONAL ~V1r;e: INPUSTIIJEa". INC. I':JI....l000Z{Jll' DEe 16 '98 15:52 FR TO 6826806 P.03/03 '" . . .. REPORT OF FIELD COMPACTION TESTS TESTED FOR: NOEL CORLISS NOEL CORLISS CONCRETE 90858 LALONE ROAD SPRINGFIELD. OR 97478 PROJECT: RESIDENCE - KEVIN PRIDGIN 1480 LEXINGTON AVENUE, EUGENE PERMIT NO. 98-00337-01 DATE: November 16. 1998 REVISION #1 OUR REPORT NO.: 722-80276-1 PAGE 2 OF 2 TEST DATA: (1) EUGENE SAND & GRAVEL 3/4" - 0 CLIENT SUPPLIED PROCTOR VALUE OPT. MOIST. = 11 7 4" I 1 I FG 1 124.5 10.1 134.3 122.0 98.0 1 - A-C. T!;S,'T TE'ST NO, DEPTH ELEV^T10N 50lLID NUMBER MAXIMUM LAB DRY * DENSITY WATER CO""'NT 'M!r DENSITY DAV OENSllY PERCiN'T COMPAcTION COMMENTS. 1 I I I I '--1 TEST LOCATION: OVEREXCAVATION OF BLDG. PAD TO THE SOUTH OF EXISTING RESIDENCE 7 PAD B. EAST SIDE I I I NOTES: TESTS PERFORMED PER ",,1M 02822-91 & ""1M 030'7-88(9') -eoMPolENTs: OENSmES SHO\IVN: lbs. per cubic fgot WATER CONTENT: Percent of drY welgh1 PEFi!CENT COMPACTION: Based on ma;xlmurn dry =frf&nc:,~~~d on ample Indk::3ted by . (1) TEST INSTRUMENT: TROXLER REMARKS: PSI did not monitor the material placement. FG = FINAL GRADE % COMPACTION REQUIREMENT PROVIDED BY CLIENT. TECHNICIAN: MIKE DEWEY 1. PILL MATERIAl Z. BAC1<FILL 3. BASE COURSE .. SUBBASE 5. SOIL e'Ef;;lENi 8. OTHER A. TEST ~EsUL TS COMPLY WITH SPECIFICATIONS 8. p'eRCfNT COMPACTION DOES NOT eoMPL Y WITH SPECIFICATIONS C. RETEST OF PREVIOUs TEsT D, MOISTURE IN EXCESS Q~SPEcIF'CATlONS e. MOISTURE BELOW SPEelFtcATIONS STANDAPD COUNT M: ADJUSTMENT DATA M: D; D: Respectfully submitted, Pro'esslon~1 Service Industries, Inc. cc: CITY OF EUGSNE TJ.llO&e'TJ:;8T IlEl:IJLT:t: "PPLV OWLVTo fHIi :;PECIFlClOCATIONaNCT&:DAloIPM4'l' NeT ftURESENT ^N'r'OTMER LOC4T10N,. 011: l!l~vAT10N8. REI'ORTS MA~ NOT ee flfPkotlUC!llD, D:OV'T IN FUlL, W1l1OUT WRITTEN PiIV.l$:$lON D"I' PROFES5lo~ SERVICE INPUeTII:Jf$, INC. f':;I....1Up..J~W ** TOTAL PAGE.03 ** . . THIS SET OF APPROVED PLANS, SPECIFICATIONS AND ENGINEERING REVIEW SHEET SHALL BE KEPT ON THE SITE OF THE WORK AUTHORIZED HEREIN. Destroyed, lost or severely damaged approved documents sha 11 be replaced by submittal of duplicate documents to the Building Division for approval verification. A plan check .fee will be charged for said services. A reinspection fee pe~ U.B.C. Section 305(g) will be charged the permit holder if the approved documents are not on the site and readily avaiiable to the inspector per U.B.C. Section 305(g). ENGINEERING PLAN REVIEW Date: 01-22-98 Address: 1480 Map-Lot: 17033443-12800 Log No: 98-00337-01 LEXINGTON AVE EUG ~~ Owner: PRIDGEN, KEVIN & LYNNE J . SANITARY SEWERS - Existing: Y X Connect to on-site system. X Available: CONNECT TO EXISTING SYSTEM, SEWER CONN. RE'ORD NOT AVAILABLE ADDN NOT TO ENCROACH ON EXISTING SYSTEM. '. .' STORM SEWERS - Existing: N ... .. X Other: ADDITION LESS THAN 10% OF EXISTING. S~Q~~~~TER TO GO TO EXISTING SYSTEM. . ..:... ... ... ..... ~.. . . .. .... . . .... ...... . . .. ..... . . ...... . . .. .. . .... . .. . . .... . . ... . ... . . . . .... . . . .... ... .. . ... . ,~" .: .. . . . . ...... . .. . . . .... . . .... . ...... . . .... ~1 .. ."J 11;" . I ~ - -. . 'J: "'" 2: 1m ,..,. )Y" . . . .. : -'. . . J.. } ,. If' ./ '" I' J r i ~ ~. I ,---- I ------ I L_____ I '. I~----- ''''''...",,,,,,.,..,''",U_.,.,, ".."._-, ""."",,, " ,,", ", ~ .,J" / ,.. ---....- ..,.""..,.,,'...-..., , . / " ///1 " , , ".-l I-~-~ TO EXleT Q 'I' Q 'I' .J 41fJ 41fJ } 3'-12)" II&~.."" . , ~/ ~ ,,- ~' ~ .: ~ -"-'- -- j j . I I I j I I ~.~--_.~-- )"",.."..." -9 ., ")'~""._' , , I I I . , , . , . . , , l I I l , , Q , ~ -'- .' &oLE PLATE RIM JOleT SEALED TO MUD elLL t eUB FLOOR SILL SEALER UNDER 2 x /& P.T. MUD elLL FOUNDATION vENT DO NOT PLACE BACKFILL UNTIL AFTER ANCHORING eTEM WALL TO FLOOR ExiSTING! RIDCilE"\ ExiSTING VALLEY 1 II , I , , , , . , , ROOF SUfilFACE BEYOND , , , I I " , , , , ""h ' . , , --r , , , , , I I I I , J I I , . , l I l I , , , , , , J . I I , , , I , , , , , ] I , I . l , , I I I I I I I . , , , , I , I_ I I , J I j , . l I . ~ / . . . 1 I l I I - ->- - - - - ,,~ " " / " , , , , ~~ ~,lQ _ ii ~ ~~:r (QO~ ...J'<{ wI: u: 'Ii :. ,- .- l , , J. ''--' , , I I I I 1 I .... ~ -1 EAST ELEVATION stALE: 1/4"=1'-0" ExleTING VALLEY 'J ~ , , . ~ a;JJa;JJ [J ~ DO 2x4 LOOKOUTS ~ 'cil 48" O.C. MAX '" I \ 2X6 BARJ:::oE ~ ' RAFTER I I I 2x6 FASCIA TYPICAL " Q . ill Q , In ,.... Q , 0\ Q , !!! l J ~ I ---------------, I -- I -----l I -1\'- ----It'! ----- ---jlJ! . I I I I 8 I .' I I - I/'I lIT" io I " I II; ;; I/J :J1: / IE '''I ;1 L/ ~ ~8: :I( ( :UL-----____________.Jj j I' . , I II i--------------------" ~---------~~-~ -------- _J I I _...1 I I :/ I II I I I ; I 111 Ot:~; I II A I II 1 fl: 1III I L_ II L____~------------ ~2XII2) END JST, TYP. Vi IU / " / " "',.1 " ~"'K';; vr:;7f3{..wi$ ~tI""iZGp /1'1 G:>4~nN'" H"U0~ . $/;'c. 'fllp,!.( EXleT KITCI-IEN_ .-'CJ-- .:=1 = Q I N Q , ~ L z -= ,- ~ - - ---r . I I = r Q I .~';;.r~--,,> "'-~;~ ~.. WEST ELEVATION SCALE. 1/4"=1'-0" \ SOUTH ELEV A TJON SCALE: 1/4"="-0" ~ , 'I ~ EXleT 0 SATI-l FRAME-IN AND FINISH EXleTINc:s DOOR OPENING .Ie 5U6FLOOR ELEV EXISTING RllXilE _IE !!l ~ -!l - i:: !!l Q FASTEN NEW JOIST TO EXISTING JOIST U$1Nc:s (2) Rowe I/&c:l 'cil 12" OC. S T Ac.o:::.E~D ------------ 18" x 6" SC~ENED vENT, (3) PLC'S Q . i<1 r' rp II I =1===--- \ UTII-ITY \ VINYL 26 Eo. ~" ,,~ ," o@ I ? I I ':I'-~. ~ 1'-12)" Q . !!! Q . ~ -'iN -II . -II Q 'I' Q'I' 'l., I II _ _ !i ~ ~- -- II = = = ~ ~ .:..:..: -=. . - ".....L 3~ Eo. , Jrl 1 j 2xll2) RIM JeT. TYP. Q , In ~LOCATE VANITY 1 6---2-- ~ r I ,.. L=) 'cil 48" O.C. MAX 1 l 1 ~ <J)" IU~ O(ll ~ I 1< RID<:;!: LINE: ~ I I 2x4 RAFTERS t CLG JeTe 'cill/&" O.C. I ---- I I I 1 I CRIBWALL 2></& P.T. MUDS ILL SOL TED TO CONT 12" x /&"TI-lK FTG 2X6 STUDe 'cil 16" OC DI~CTL Y BELOW EA JOleT WI DBL TOP PLATE I t FULL DEPTH BLOCKING BTUN JSTe, TYP. I 3~It~t .1 6"-4l 1 - .- Q , N ~'I' . 0\ Q . ~ /&1fJ /&& ",. 2X6 BARerE RAFTER < r --, I II I ~t-' I r--., '\~r~- - . \1 "--- - ---',... " ~ Q ~r_. r ~ . i<1 . =lr-~'. ~=:;i= !, ,-1"\=18 l /I1/A/. PtJu/5/.[ Z-'f.& HP/?- / "'--.: ~ t .-Jl ~'I' 0\ j = r Q . ", ,II IIlI - - ..... 1" "--4X4 I"'.T, f>OST WI $IMP&oN PC44 (2) Pi.C'S ) 1eu5S ENE>IIVcee.",;t. il'U$)- I5c "'N 17?~ Sin:; A-r nNlG t7F FMN'IJ{/b IN5?=l7t",{ ROOF FRAMING PLAN_ SCALE: 1/4"=1'-0" FIELD VERIFY AND MATCH EXISTING DIMENSIONS NOTE. HEAL OF TRUSe &HALL BE ADJUeTE:D IN HEIGHT TO AJ..LOW FOR A MATCHBE1"U.II:EN NEW AND OLD ROOF LINES AND CEILING I-lEIGI-ITe. CONTRACTOR TO YERIFY ALL HEIGHTe AND eLOPE:e "0. .) 0 P'- ,.~~, ~f':' _ " ,,~ ':'~~i : iv:._:~. :t:S" " ~ ~ >:'~ )" 0" u ~ > . c o'>,c\'f~~ -.' <> "'i!.",'f:.l , , "!'~~ ,:l- t. ~i;';; ~h. ,,<,,'\~ '~~'j~~t? -F 1~.Jf, , > ..l~{"", ~ ~. ;3}~ >:;tY~ .~"Li}li ~,<~ . :'.1.;1: . . - ~~ , , ~fJf_;j ....\',,~ > :" ~~:;'~J ";;' - '~"{'...;2 -/. :. ,," ; c.~y,~.~ ,~ ~ ~ '::.,~t~ ,. '.," '.; , . , '~';'11' ,:;:~e 11~:'~;:~~ ;' ::. ;~~!{J ,-'~ PLOT SC.dle. , 1. 48 .. "".,.,~ o,~Qwn. .. RM~' ':;,~'~I .'..,~J ,~::et ~~J5>'~':j!1 . J1'.. ::,::<G;~~~' / Of ') . ,~ -. .f'(,~).,~, /~ 4' . Sheets '. ....Il)tlffc,,;'...i ,...... "'~1. ~'= ~..,,:~ . .... '. "-' " ~ "~~ {~"r "<,' " ~.~ " {., "". " ;;, > ~ '" ~ I "j, . '",""- '''-;;{ll'''~"",~' 'L ." ~':<.~: .~ _,,'. f ~ ~.; !:~'.,..j ~ ....v r.-r-;.r '~' "" ""!;.;j;'.. f L <,"" ~ ~ 1;- ~~ ",., :-4-~::-"_$~'.$:'<;_-::.. ..:~ f: .{ 1\ J. ~'.:: ~ C ",\).~ {'-~::~ ';~'-.~',~ijf~~t}:~":t":..:; !;~~~g~~,-r:;.~4~~~\&: ,,":."}~. MATCI4 EXISTINc:s AeF'l-lAL T SHINc:sI.Ee IS. FELT OYER 112" CDX PI. YWOOD WI PI. YCLIPS 'cil !-!ORI%. JOINTe MANUFACTU~R DEelc;NED TRUeS BAFFLE eIMF50N H23 TIlE FRIEZE BLOCKING wi 5C~ENED vENTe 6" x 22 GA GALv eTL DRIP FLASHING GUTTER ~\ -i~ i~f , 112" DIA ANCHOR SOL TS 'cil ~ /&'-12)" O.C., 1" INTO CONC~TE, NOT MO~ THAN 12" FROM CORNER PERIMETER DRAIN IF ~QUI~D - 4x4 f>OSTe WI SIMP&oN A6U44 (2) PLC'S ~INF. CONC. PAD 18" eGl x 112)" TI-lK wi (2) 1I4 BARS EW - 3 112" TI-lK CONC SLAB wi BRUSH FINleH 1/4" I FT SLOPE AWAY FROM BLDGo 8'-':I~" I .,2'-6" } l S'-/&" 1 'I 11'-/&" 2x/& FASCIA HOF1IZONTAL LAP SIDING OYER !-!OUSEWRAP OYER 112" CDX PLYWOOD MATCH EXISTING SECTION SCALE: 1/2"=1'-0" REF OWG: 1 , S'-4~" I ,~ '-- 3~" &1_lZ)1I &1_1&11 61-"'" " IS'-I2)" 11'-/&" l' " 2/&'-6" (EXleTING) " FOUNDATION PLAN SCALE' 1/4"=1'-0" FINlel4 FLOOR I" ORIENTED eTRAND SOARD R-2S INeULATION (LATH OR WI~ 5UF'F'ORTJ - FLOOR JOISTe PER PLAN z E ,u_~____~ I 666666~~66~666666}1 - 113 'cil 6'-12)" O.C. - 6: 1"_2" FROM ElXilE I: ~ 113 BA~ a 112)" MAX FRoM - TOP OF CONC~TE ,,,,.---- COMPACTED OR "T UNDleTUR6ED EARTH <<-0.~' - /& MIL BLACK POL YETHYLENE GROUND COYER, LAP AND WRAP UP 12" MIN. MATCH EXleTINc:s FL ELEV. !::! ".J;"} ~ C", .1~~_ 6" "- l~' " > 12" , " SECTION SCALE' 1/2"=1'-0" REF OWG: 1 C) '. 61_lZ)1I /&'-2~" IS'-I2)" 26'-/&" (EXISTING) SECTION 316 SMOKE DETECTORS 316 I Smoke deleclors required. Smoke detectors shall be inslalled in each <;lceplllg room, oULside of each separale sJeep- IIIg ~lrca 111 Ihc immcdi~llc vicinily of the bedroolTI<; and on cdch addiLIOI1.lI"IOry of Lhc dwelling, inLluding ba.scmcnL<; and ccJJars but nol includmg crawl spaces and uninhabIlable alLlcs In dwell- I ings or dwelling un.ls wuh spht levels. a smoke detector need be ' installed only on the upper level. provided the lower level is less lhan one full slory below the upper level, exeepl 111 at If there IS a door between levels. then a detector is required on each level. All ' delectors shall be interconnected such that the actuallOn of one alann will actuate alllhe alarms m the indiVidual unil and shall ' provide an alann whIch will be aud,ble m all sleepmg areas. All , detectors shall be approved and listed and shall be instJlled m accordance wah the mdlluracturcr's II1s1ructlOf1S. FLOOR PLAN SCALE: 1/4"=1'-0" LEGEND EXIST. WALL NEW WALL REMOVE EXIST. WALL ....l"~.l.OIAi~..'....~....... .'...'......""'...'!'.........-. C========::J o 316.1.1 Alleralilln!!,.J:ep9lr.~!I!.!~,!Ij.dli~'!!,1~. When aiLerJtlOns, , repairs or additions requiring a pennil occur. or when one or marc sleepIng rooms are added or created in existmg dwellings. the entne bUlldmg shall be provided wuh smoke detectors i localed as required for new dwellings; the smoke detectors are not required lo be inLerconnected unless other remodeling con- sideratIOns require removal of the appropriate wall and cetlmg covenngs to fac1l1tate concealed mterconnected wiring 316.2 Power source. RequITcd 'lmoke deteclors shall receive lheir pfJll1ary power from the bUilding wuing when such wrring is served from a commercIal source. and when pnmary power is imerrupted, shall receive power from a baltery. Wiring shall be permanent and withoul a disconnectmg SWItch other than those required for overcurrenl protecllOn Smoke detectors may be ballery operated wh~n installed in bUlldmgs withoul commercial power ~', -" ji , R-.38 BATTS !:>/8" GYP, BD. DOUBLE TOI"' PLArE 112" GYP. BD. R-21 KRAFt FACED BATTS 2X6 eruos 'ci 24" O.C- CD . . ,~_ f. ,'i.. ...' I' ".", . -'. , _~\:1;~:; ,~, .. ! .r .. y ,14 " '." .!.<" , ~'-- ~ ,-- .... / I z w o 0::0 & (2.. [d.D- 10 ~Z 0::' W ::;a o I ZZ. o DO. 1-, 0.41 <'2 0:::, .x:o w~ -lW :z: > OW' W .OCL0. .. .~::> ~,~;W = . " U).. Z", (J). 0, ZO~ <(Z<( .-3 <( >, tL ,W .....J W ,., ~ ..,-.. '-' - Q '-'_ r. '-' u ~ .) _ ~ , \f u"... L 0 _ ... c: ~JI) ~ B ~ t::::5~ d~ IS . Oil o c, o c o. "'S~ 'wo~ ~ O,,"~O ~ll" ~ ~ @ a E2)~ {~li leJo . ~ ~ c::'::t '" 1"-. c .," , 0-0 ~ " ; ,: '30f-:i -, ';~t~~, "~~.~ :;:~' ,- ~;~ ~it;; ::,~)~{~ ~ -; L ,,1-\. -.f~.d ~ <;,~-~t~~~ .~ '-<~'~'il ~~:'~;f~r ,,~j '; ~ ..:~.~~~~ r....""'I . ~ ~.~~;~ , -"".j"'~* "', ~/~~ >;t'1~~: :.,}~ .>"--," 0; ~:,~~~~ '" , .,-:.~~~ .. <A'~ ...~~ "'....." ,,~~ ,._14: .. -:~ ;;~~ :',' -> . ,.~' ':i 'i~ If ? ~. . ~ '",-.../ J ...""I"""."L ...,...,'_~" DIVISION 0600 - CARPFNTRY 0601 GENERAL: A All structural dimension lumber shall be graded and marked as noted In Section 502 I. 502 II, 602 I and B021. B. Appro\'ed end-jomted lumber may be used mterchangeably with selld-sawn membere of the same species and grade. C All structural lumber sIZes have been designed using WWPA grading rules. 11 these members bear the stamp 01 a different grading ogenc)', adjustments to sizes may need to be mode 0602 POSTS: Pasts and columns shall be Douglas fir/Larch, Grade Select Structural F O.H C Posts shall be pressure treated If so noted on plans 0603 BEAMS, HEADERS AND STRINGERS: All members 2' to 4' thick and 5" or more WIde shall be Dougl08 11r fLerch, Beams and Stnngers Class, Grode II. All 6" thick members shall be Douglas fir fLareh. Beams and Stnngers Class. Grode Select Structural All door and wmdow headers sholl be 4x6 minimum unless noted otherWise Glued-laminated timbers shall be 24F-V4, Ofl grade unless noted otherWise 0604 STUDS: Studs shall be Douglas Ilr ILarch. Grade #2 of gll load bearmg walls with size and spacing as shown on plans. UtilIty grade lumber may be used for non-bearing studs 11 spaced per Table 6023d Cripples under headers shall be continuous to sole plate Top plates in load-bearing walls shall be doubled with JOints offset 4801 minimum Block 011 stud walls where required for sheathmg. Align load-bearing studs as noted in Section 602:3 4 InterIor nonbearmg partitions may be capped with a single top plate FoundatIon Cripple walls shall be constructed as noted In Section 6028 All wood members In contact With concrete sholl be pressure treated 0605 JOISTS. Floor and ceiling JOists shall be Douglas fir/Larch. Grode #2 All rim JOIsts and end JOists shall be caulked in place durlOg frammg. Double 011 end JOists and all JOists under parallel bearmg partitions Lap jOlsfs 6" mmlmum at mterlor bearing supports where pOSSible, otherWise proYlde 1-1/2:11 minimum bearing on 'Wood or mefal supports and 3" on masonry or use approved JOist hangers Floor openmgs shall be framed as noted In Section 5029 0606 RAFTERS. Rafters sholl be Douglas flr/Laroh. Grode #2 With Size and spacmg as shown on plans. All raffers shall be notched to prOVide full bearmg at supports 0607 TRUSSES: Manufacturer of wood floor or roof trusses sholl supply copies of truss details and deSign calculatIons to the bulldmg offiCial and owner Trusses shall be msfalled With 011 fasfeners. hangers and bracmg os reqUired by the manufacturer. Truss members shall not be drilled. cut, notched or altered In any manner unless so deSigned 060B SHEATHING: Rool and wall sheathing shall be 7/16' OrIented Sir and Boord 10SB) or 1/2" CDX Plywood With lace gralO perpendicular 10 supports and staggered Jamts. Floor sheathing sholl be os shown on plans All structural sheathmg shall be graded cnd marked QS noted In Section 503 and 610. Particleboard shall be graded and marked as noted m Section 611 If reqUired, dIaphragms and shear walls shall be constructed as reqUired by fhe engmeer or os shown on plans 0609 SOLE PLATES: Sole plates 10 contact With concrete sholl be pressure treated douglas fir/Larch 0610 NAILING: All nailing shall be as noted In Tables 60230 and 6023a(l). Metal connectors shall be Installed With all nails. bolts or other fasteners as required by manufacturer 0611 BRACING. Walt and Cripple wall bracmg shall be proYlded os per Sect,on 602 9 and Table 602 9 0612 METAL CONNECTORS' Simpson strong tie. or approved equal 0613 BLOCKING: Full depth solid blockrng of utility grade lumber IS reqUIred 01 011 bearing walls and at the bearmg pomts 01 all jOists and rafters Cross brtdgmg between 2xl4 and larger rafters and 2xl2 and larger JOists 16 reqUired at lO'-Oft 0 C. maximum Bracmg between roof or floor trusses shall be mstalled as reqUired by manufacturer 0614 NOTCHING. Notchrng. cuttrng and d,,"rng of studs, plales, Joists or rafters shall oonform to Sections 5026. 5027. 6025. 602 51, B02 6 and B02 7 0615 DRAFTSTOPPING: Draftstopprng and Fife Blockrng .hall be constructed and mstalled as reqUired by SectIon 50211 and 6027 0616 FINISH CARPENTRY. A Stolrwoys sholl be constructed os shown on plans and os noted 10 Section 314 B Handrails and guardrails shall be constructed as shown on plans and as noted in SectIOn 315 0617 INTERIOR WALL COVERING: A. All mferlor structural components shall comply wlfh the Department of Housmg and Urban Development (HUD) formaldehyde emiSSion standards (#24 CFR part 32BO) of 2 ppm (pariS per millIOn) for plywood and 3 ppm for particle board. Plywood or particle board stamped" meets HUD reqUirements" or "HUD approved" etc. shall be acceptable. Intenor grade plywood. wafer board. particle board. Qnd orlenfed strand board made With phenOl-based resins and stamped llExposure t shall be acceptable. Exterior grade components made With phenol-based resms and stamped "Exterior- shall be ac,;epfable- - - B. All gypsum board Jomts Qnd ImperfectIons sholl be tilled and toped C All surfaces shall be sanded far pamt or wallpaper ar textured as speCIfied by owner. o All exposed lOt en or gypsum board corners shall be remforced With metal edge tnm. E. Gypsum board shall not be Installed untIl weather pratecilon IS prOVIded F. Support spacing ond the size and spacIng 01 fasteners shall comply With Section 70235 061B EXTERIOR WALL COVERING: Siding shall be os shown on plans With attachment per TobIe 7034 unless noted otherWise. Ponel type Siding shall have Shlplopped verflcal jomts over framing members and flashed or lopped honzontal jomts 0619 ATTIC ACCESS: A readily acceSSible framed aft,c access halch of not less than 22 mches by 30 Inches shall be proYlded to any attIc area havmg a clear height of over 30 inches DIVISION 0700 - THERMAL AND MOISTURF PROTECTION 0701 GENERAL: A These plans are Intended to comply With Prescnptlve Compliance Path I at Section E401 B All Insulatmg matertals to comply wl1h Sections 317. 319 and AppendiX E. C All msulatlon shall be applied umformly and In 0 manner to prevent compressIon InsulatIon shall be spht evenly around pipes. W!fes. ducts or other obstructrons and cut In around outlet boxes. o Extenor JOints around wmdows and door frames. between wall CaYltles and Window and door frames, between wall and foundation. between wall and roof. between wall ponels. at penetrations or utility serYlces through walls, floors and roofs and all other openings 10 the exterIor envelopes shall be caulked, gasketed, weather-stripped or otherWise sealed 0702 FLOOR INSULATIDN A R-25 fiberglass batt insulatIon, supported by lath or corrosIOn-proof Wire, sholl be lOst ailed fluih under floors oyer all crawlspaces. Support system {wood lath, corrOSIon-resistant Wire, or rot-resistant twme) IS required to hold insulatIOn In place WIthout compressing It. Use baffles If reqUired to malntam clearance around crawl space vents. Install 1 perm maximum kratt paper vapor retarder between 2x decking and underloyment. Separate vapor retarder Ii not requlfed In floors constructed wdh plywood or OSS sheathmg Ground cover of 6-mil black polyethylene With Jomts lopped 12" minimum 16 required of all crowl spaces. 0703 WALL INSULATION: A. (R-21) Kratt faced (LO perm maxImum) hIgh denSity fiberglass boft Insulaflon sholl be face stapled to inSide (warm) surface of studs 10 all walls separafmg heated from unheated spaces 0704 CEILING INSULATION. A (R-38) Fiberglass batt or loose fill fiberglass, cellulose or rock wool lOsulatlon shall be Installed on flat cetlmgs Loose fIll msulatlOn may be used only where roof slope IS 4/12 or greater and headroom at ridge IS at least 44 Inches. Loose fill insulation must be mstalled per label mdicatlons of pounds required per square foot or bogs per 1000 square feet B (R-30) Foil faced fiberglass batt msulatlon shall be Installed on sloped ceilings constructed wdh smgle rafters. C. (R-30) Kraft faoed fiberglass batt msulatlon shall be Installed on ceilings wdh a slope of greater than 2/12 and an attIc space above O. (R-30) Loose fIll fIberglass, cellulo$e or rock wool insulation may be used on sloped ceIlings prOVided slope IS 2/12 or less and headroom at ndge IS at leost 44 mches Loose fIll insulation must be Installed per label mdlcaltons of pounds reqUired per square foot or bags per 1000 square feet. E. (R-21) FOil faced fiberglass batt msulatlon may be Installed In partIally vaulted cellmg, and ceJlmgl totaling not more than 150 square feet In area for dormers. bay wmdows, etc. F All ceilings without an attIc space above sholl hove a vapor barfler WIth a maxImum 05 perm ratmg. GAIl atllc accesses and skylIght wells shall be Insulated to the some R-volue as the surroundmg ceiling AttiC access hatches sholl be weather-stripped H RIgid. weather-reSistant baffles shall be Installed to deflect soffIt ventilatIOn air above msulotlon and to keep msulatlon cleor from attic hatches. Non-combustible baffles shall be mstalled to prOVide 3" clearance around flues, metal chImneys, gas vents or fixtures that require clearances or ventilation tor fife safety. ....::.. '-.,/ BUILDING SPFCIFICATIONS _ .e,.___ 0706 ROOFING: A Roolmg materials and application 10 comply w,lh Chapter 9 B Roofing shall be applIed with all flashing and accessories recommended by manufacturer or 06 reqUIred for Q watertight aiSembly. Fmlsh roofmg matenals shall be approved by owner C. Guiter. sholl be Installed at lower edge of all roof slopes Downspouts from gutters to discharge IOta starmwater dram. Owner to approve style and color. 0707 VENTILATION: A Screened soffit, eave, ridge or roof Jack vents shall be supplied as shown on plans with a mInimum raflo of net vent openmg fa ventIlated area of I to 150 RatiO may be reduced to I to 500 If venfs are arranged as noted m SectIon 806 Screen sholl have 1/8" square openmgs of corrosion resistant wire B Crawl space shall be ventIlated by means of screened openings through foundatIon stem walls os shown on plans Total net openmg and arrangement of vents shall be as noted In SectIon 409 t Screen shall have 1/8" square openmgs of corrosion-reSIstant wire. 070B MUD SILL: Both top and bottom 01 mud Sill shall be caulked or gaskeled 0709 THERMAL BREAK: Concrete slabs on grade 10 conditioned spaces shall be thermally broken from slabs In adjacent uncondItIoned spaces DIVISION OBOO - DOORS. WINDOWS AND GLASS OBOI DOORS: A Door sizes shall be os noted on plans, With type, finishes and hardware as selected by owner. All egress doors shall be readily openable from the SIde from whIch egress IS to be made WIthout the use of 0 key or speCial knowledge or effort B Exterior doors (except main entry door) to have a maximum 020 U-Value. Main entry door (24 square feet maxImum) to hove a maXimum 054 U-Value. All exterior doors to have an air leakage rating of 0.37 cfm maximum per square foot of door area. All exterior doors shall be I 3/4" thick minimum and be weather-stripped (do not use sticky bock foam) C. Doors With more than 2: 5 square feet of glazmg must meet the U-Value requirements for wmdows Sltdmg glass doors shall be tested and certIfied as noted In SectIon 609. OB02 WINDOWS: A. Window brand and style shall be as directed by owner Sizes sholl be os noted on plans NOTE' SIzes of Windows shown on pions are nominal only Verify rough openmg reqUired before framing 8 All Windows shall be double glozed wlfh D maxImum 040 U-Value and shall meef the fenestration requirements of AppendiX C. All wmdows shall be fested and certified as noted In Sechon 608 All Wlndo""8 must be labeled With U-Value or U-Value closs except as noted In Secflon E4014 I O. Sleepmg rooms shall have at least one openable egress Window or door as shown on plans and a6 required by Section 3102 NOTE: Sizes of Windows shown on plans ore nominal only. Verify CLEAR OPENING dimenSIOns for egress Windows as reqUired by code E Windows shall be set onto 0 bead 01 caulking. F Skylights shall be constructed of double glazmg. wlfh lOner pone lempered, in a metal frame or as noted in Section 3086 wJth a mOll.lmum 050 U-Value Skylight area shall be not more than 2 per cent of heated floor area. G. Glass doors and enclosures for showers, hot fubs, whirlpools. saunas, steam rooms and bathtubs, glazmg 10 swmgmg or sliding doors and storm doors, and 011 9lazI09 and mirrors wtfhm 24" of doors or With," IS" of floors, ond all glazmg In railings and glOZing used in barners around sWimming pools and spas shall be tempered and permanently marked per Section 30S I I Exceptions are noted In Section 308.4 DIVISION 0900 - FINISHES 0'901 GENERAL: A All mterlor finIshes and materiols to conform to SectIOns 318 and 702 Wall and ceiling finishes shall have a flame-spread claSSification of not greater than 200 except as noted In Sed Ion 318.1 and a smoke densl1y not greater than 450. 8 All exterior finishes and materials shall conform to SectIon 703 and Table 7034 0'902 INTERIOR PAINT: Latex paint With colors sholl be approved by owner. 0903 EXTERIOR PAINT' Latex or stain with color to be approved by owner 0904 OTHER WALL FINISHES' Contractor to coordinate wdh owner where wall paper, paneling, or womscotflng are deSired 0905 FLOOR FINISHES. A Carpet shall be profeSSIOnally Installed With pad, tack strtp and metal trim os reqUired Carpet and pad shall be approved by owner. B. Cushion ymyl type shall be approved by owner. ~r DIVISION OIOO-GENERAL 0101 CODES' All construction methods. materials and workmanship shall comply WIth STATE OF OREGON 1996 EDITION ONE AND TWO F AMIL Y DWELLING SPECIALTY CODE comprised of the 1995 Edition of CABO One and Two Family DwelllOg Code w,th Oregon Amendments dated April I, 1996 0102 PERMITS: The owner WIll prOVide and pay for all permds and fees except where other prOVISion 1s made by contract 0103 UTILITIES. Owner to prOVide 0104 SUBSTITUTIONS: Certam processes, types of eqUIpment or kinds of materials are speCifIed by manufacturer1s nome, brand or cotalog number to establish Q baSIS of qualify or deSirabilIty for the purpose intended. ExclUSions of products of equal quality or deSirability to those speCified IS nof mtended. Sub-Contractors to secure approval of substitutIOns from owner Submit suffICient mtormatlon on speCifiC product or products for evaluation. Samples may be reqUIred. 0105 CHECKING: Contractor shall vefJ1y and coordmate all dimenSions and conditions on all draWing, and at construction sde before proceeding Discrepancies are to be brought to the attention of the owner. fhe designer, and/or the engineer as appropflate. and fully resolved before construction 18 commenced. 0107 CLEANING OF SURF ACES. All sur laces must be clean and In good condition af job completion 0108 COOPERATION. Contractor and subcontroc1ors shall fully cooperate In carrymg out the 'Work Contractor to do or be dIrectly responSible for all consfructlon braclOg. temporary shormg, furrmg and building 10, and prOViding all openings, chase1i, e1c , reqUired by vanous subcontractors Where work of one subcontractor IS Installed over surfaces applied by other trades, the commencement of work by the first mentIOned subcontractor constltufes acceptance of the surfaces. and cannot be used for an excuse should subsequent failures occur. DIVISION 0200 - SITE WORK 0201 EARTHWORK. A Excavations or fills shall be so constructed or protected that they do not endanger life or property B Remove trash. rubbish and other obstructions from SIte prior to star tlng ear thwork C. 00 excavatIOn work for structure and Of her work shown on the drawings. carefully tnmmed to lines and elevations reqUired for the work Permanent cuts and fills sholl not be steeper than 2 hOrizontal to I vertical unless approved by the bUilding offiCial D StockpIle excavated material for back1111 purposes of approved locations. Only clean, granular material is acceptoble for re-use E The bUilding offiCial may require a sOil test to determme the SOil's characterrstlcs F Lot shall be prOVided With adequate dramage and shall be graded so as to dram surface water away from foundatIon walls Said grade shall fall a mmlmum of SIX Inches wlfhm the fIrst ten 1eet, except as restricted by lot Imes where drains shall be prOVIded. G A foundation peflmeter dram shott be IOstal1ed whIch WIll dram roof dIscharge to a pomt at least tlve feet from the foundation walls or to an approved system 0202 BACKFILliNG A Backtlll adjacent to concrete walls shall not be placed until the wall hos suffICient strength or has been suffiCIently braced to prevent damage by the backfIll B Before plaCing backfill, remove all screeds. screed stakes. other wood, debriS and material subject 10 rot, corroSIon or subterranean termde attack C. Backtlll materlol shall be clean and granular, placed m 6-Inch hfts, and compacted o Dispose 01 all unSUitable and excess mateflQI off sIte Conform to local laws and ordinances relatmg to waste disposal on property of others DIVISION 0300 - CONrRFTF 0301 GENERAL REQUIREMENTS' A Concrete deSign, components, storage, mixture, placement and remforcement sholl contorm to Chapter 4 B Protect all concrete from damage and use speCIal care on all exposed concrete to prevent staining or discoloration C Damaged concrete shall be repaired. or removed and replaced wlfh new concrete at the discret,on of the owner o Form all concrete surfaces, except bottom of foot lOgs and top of slabs E Footings shall be placed on undisturbed soil or compacted fill. All fill materials sholl be free of vegetatIon and foreign material A SOIls investigation report and a report of satlsfac10ry placement of fill shall be submitted to the bUilding offiCial deSCribing fIlls greafer than 4" thick which 'WIll be used to support the foundatIOns 01 any bUilding or structure Except where approved, flll depths under slabs shall not exceed -24- for clean sand Of gravel and e~ tor earth.- F Stepped footings ore reqUired where the ground surface slopes more than one foot In fen feet. G Remove all foreIgn matter and wet down sod before placement of concrete H IsolatIon jomts sholl be prOVIded between all slabs and foundation walls. uSing (2) thicknesses of 30# builder's felt or 3/8" asphalt Impregnated sheeting 0302 FORM WORK A Forms shall be substantIal, suffiCiently tIght and properly braced to prevent leakage and maintain POSition and shope B Forms and shormg sholl nof be removed until the structure has suffICient strength to support safely Its weight and all loads placed thereon 0303 REINFORCEMENT' A Use only new, clean stock, free trom rust, scale, grease and olher coatlOgs Refer to ACI 3IB-77 B Remforcement shall conform to ASTM A-GIS wdh deformations 10 ASTM A-305. Grode 40 C Reinforcement Sizes ond locations sholl be os shown on plans or as noted below: SPLiCE LAP LENGTH Bar Size Concrete , :3 1'_6" # 4 21-0" #- 5 21_61' Masonry 2'_011 21_611 31-0" DIIVISION 1000 - SPECIAL TIES lOOl Cabmets, closet organizers. shelves and l::!ther bullf-ins shalj be as shown o-n plans ana-as arranged by owner. ..;lP.~ ~ \-J&tl', ~\tl\\j\P~V oP\~ ,\~ ~~\) ~b~~ CONCRETE COVER 3'1 Concrete depOSited agamst earth 201 Formed concrete agamst earth 3/4" To top of slab on grade 0304 CAST-IN-PLACE CONCRETE' A Basement walls and foundations not exposed to weather and basement slabs and mterlor slabs on grade, except garoge floor slabs. shall be 2500 pSI compressive strength concrete at 28 days. B Porches, carport slobs and steps exposed to the weather, basemenf walls, foundation walls, exterior walls, and other vertical concrete work exposed to 1he weather and garage floor slabs shall be 3000 PSI compressive strength concrete at 28 days C 3000 pSI concrete and other concrete whIch may be subject to treezmg and thawmg during constructIon shall be aIr entrained Total air content (percent by volume of concrete) shall be not less than five per cent or more than seven per cent. o The minimum cement content of concrete mIxtures for extenor porches, carport slobs and steps 1hat Will be exposed 10 freezmg and thowmg m the presence of deiCing chemicals shall be 520 pounds of cement per cubiC yard of concrete E The top surface ot all footmgs shall be level The bottom surface of footings may have a slope not exceeding I m 10 Fooflngs shall be stepped where It II necessary to change the elevohon of the top surface of the footings or where the slope of the bottom surface of the footmg WIll exceed I in 10 F Fmishlng (vertIcal surfaces); Correct all oggregate pockets and other defects Grind off finS and projectIons and remove stains Exterior surfaces of foundahon walls enclOSing irving space or storage below tml!ilhed grade sholl be dampproofed uSing 'IThoroseal FoundatIon Cootmgll or equal. G. Fmrshmg (slabs). Surtace fmlshes shall be on plans Areas noted "Brush Fmlsh- shall hove 1/801 high attenuations, With pottern and style as approved by the owner. 0305 EMBEDMENTS' A Anchor bolts attochmg mud SIlls to concrefe foundatIons, sholl be one-half lOch diameter spaced at six feet maxImum on center, and extend at least seven inches Into the concrete There must be an anchor bolf Within twelve Inches at each corner and each piece of SIll shall hove at least two bolts B Post bases, hold-downs, vents, door openings and condults shall be located accurately os shown on plans DIVISION 0500 - MFT AL 0501 BOLTS: ASTM A-307 Heavy hex-head With heavy hex nuts and hardened flat washers unless noted otherWise 0502 STEEL: ASTM A-36 0503 MISCELLANEOUS SHEET METAL. Galvanized 26 gauge steel. Exte"or openings exposed to the weather sholl be flashed waterproof 0504 Fasteners. except one-half-Inch diameter or larger steel bolh, used for pressure preservative or f/(8 retardant-treated wood s.hall be hot-dipped galvanIzed steel. stainless steel, Silicon bronze or copper. OIlVISION 1500 - MECHANICAL 15101 GENERAL: All heatmg, ventilating, cooling and plumbmg components and installation shoJI comply chapters II through 28 and E501 and E601 and all other applicable regulatIons therem referenced. 15,02 HVAC SYSTEM: A HVAC system shall be on exfenslon of eXlstmg system. All equIpment shall be approved by 1he bulldmg offiCial or shall bear ihe label of an approved testing agency and sholl be permanently labeled as noted In Section 1303 B System shall be deSIgned and mstalled by a qualJfled contractor. Contractor shall supply HV AC duct diagrams or drawmgs and/or heat loss or energy use calculations, and equIpment speCI11cations, If reqUired by the bUIlding offiCial C. The temperoture of each HVAC 20ne shall be controlled by 0 thermostat. All thermostais must be numerically marked and capable of bemg set between 55 and 75 degrees for heatmg-only thermostats; between 70 and 85 degrees for cooling-only thermostats; and between 55 and 85 degrees tor thermostats that control both heatmg and cooling The sysfem control must hove o SWitch or other means of setting bock or shutting off heafmg and cooling durmg peflods of reduced need. O. Adjustable registers or space heaters sholl be Installed In all rooms except baths and utillfy area E Ducts, plenums. returns and enclosures Installed 10 unconditIoned space sholl be insulated to R-8 Ducts shall be sealed at 011 jomts and cornen (mcludmg prefabricated jOints), at Junctions between outlet registers and mterlor surfaces, and at all places where the ducts penetrate the bUIlding envelope. No ducts shall be run In exterior walls F Ouch penetrating the wall or ceiling separating the dwelling from the garage shall be constructed and Installed as noted m Section 309 II G. Non-combustIble fire-stopping shall be prOVided at all gops around mechanical lmes at ceilings and floor levels H Bathrooms shall be heoted and ventilated wIl.h combmohon heater/light/fan WIth model to be approved by owner Bathroom exhaust fans to hove (I capaclfy of at least 50 CFM and must Include back draft dampers. I- lL.J lL.J Ct:: I- U) I [<., ~i -C - If) ..-- No-re.' WlAb+.er.;okU. MoJ~ --\D E/}Cisti ~ pt"l V cUt.., ~1V)S}erl\ <;He., ArJcJJ. ~ ~ ~ J mu~~,,~ -v,6i&h~ I priV~,;~ir' ~t'I"- Wo..~ . \ SJ ~~ .J ~ 11lY\ IY wl1'Nn b Dr ~ N\lA~-r ~ ~ro.tW --v- ~bt,~t. ~S~ ,..I_Vl r - , ~ AJJ ",^-\W'OIt. ~. 1503 PLUMBING A Plumbing installation shall be In accordance With Part Two of the dwellmg requirements of the Uniform Plumbmg Code, 1991 EdItion, Including Oregon amendments B System shall be deSIgned and Installed by 0 qualIfIed contractor Contractor sholl supply detaIled plans, calculat!ons and speCifications of all proposed equIpment If reqUired by Building Offlc,al. C WASTE AND VENT SYSTEM' ABS or PVC plastiC D. WATER PIPING: Copper tubing E All appliance model1i. 1ityles. colors, etc. shall be approved by owner F. Non-combustible fire-stopping shall be prOVided at all gaps around plumbing tmes at ceilings and floor levels. Seal all penetratIons through bUilding envelope With caulkmg. G All water pIpes sholl be IOsulated In accordance wrth sectIOn E601 DIVISION 1600 - ELECTRICAL A. All work shall meet the requirements and inspectIons of Chapter1i 15 and 39 through 46 and the 1993 NotIonal Elecincal Code. B Electncal systems sholl be deSigned and JOstolled by 0 qualified contractor Contractor sholl supply detailed plans, calculations and speCIfIcatIOns of all proposed equIpment If required by the building oiflCIOI. C. Wiring shall be done with 3-wlre nonmetalliC cable wl1h all outlets properly grounded All W!fes shall be copper and none shall be less than 114 gauge Swdches and duplex outlets shall be Urst grade SWitches shall be Silent type. D Suitable connections shall be prOVided for 011 new electrlcal outlets and fIxtures as shown on the plans E Smoke detectors. shall be Installed inSide and outSide of all sleeping rooms and on each floor 0$ noted In Section 316 and as shown on plans F Non-combustible fire-stopping shall be prOVided at all gaps around electrlcalllnes at ceIlings and floor levels Seal all penetrations fhrough the bulldmg envelope With caulking G Wiring shall be Installed 10 a monner to allow for as much wall msulatlon 08 pOSSIble H Recessed lights Installed In extenor vaulted ceilings (Without an attic space above) shall be rated to allow direct contact With insulatIOn ( "--// ., -,.... "Ll".ll.~__".. ~..~ '.. -........... " ",,' ,_,." ,....,., ...", . '.L, , . ",.." ,,' '" ,. ~ d. ,,_ .'.. ,," ... j t/ iN) ~ ~ > <[ z o <f) IX: W o z W 1: J- (I) <[ u w Z w <f) 14TH AVE -~ <[ Z o J- '" ~ X W .J I I - - J EXI&TING--...... -.--1 r-l TOOL '- ~ <U &I-4ED 1 I .L '~'/f SITE VICINITY MAP NO SCALE EXI&TINC. ~-lOME F'ROPO&ED\ REMODEL \ :W'~------ -I ~- - - -:ffi-- l!d--:!J ~, EXI&TINC.\ C.A~Ac.E -T--------, I I I I I I I I I 1" I I I I I I .l___~------l 1----11- I II I II EXI&TINC.,~, II &1-40F ~7 II I II - - - """",,--=--JJ , , L.......-- EXI&TINc. Y C.RAVEL DRIVE ~ 13;l..-5,;z.' LEXINGTON SITE PLAN SCALE. '''=20' -0" TAX LOT 17-03-34-43-128 ~ c- ~ I -':' I~ I; > :;::::- ~ /' F'T I I I I I L____--l - I I I I ~ ~ All lots or development sites in the AG RA R I R.2. R.3. and R-4 DIS!r; Is h II '.' , ~~!~:~~fr:~~:~s:o !t~~n/;~.:i~ a~:~I~~:~n~~;i~;ngs, or no Intenor yards if the buildm P M!y Imes, a common wall. Utliity oasom !IS abut or .have distance greater than io f;etebnlst may reguJre a EC 9.542 e ween bUlldmgs. CALL OPJE rJPJa08E~ Fr 1-800-332-2344 ~ 4B ~gu~~~~~i~~~~Q \\ /' REVISIONS 8;" \", /' ./ " z w zZ C) 00 Ct: 0 f-O 0 - OW LL cr: zO:::: ....J 0..- -0 w X 0 W 0 L Z -.-JW w Z Ct: - > OW w W COO L ~:=> 0 ~ I -r- W If) O..-Z Z<r::O :S2~ O..->-<r:: I--U W-lL. Z- ~-U If)UW >0..- If) \.. ,/ '\ , ill 0 J/) ill I J/) '<I ~ J/) ~ C\I 0 ,~ c,,, '<I ~ " III Ir l5 0 B, w z ij w ~ :J @!J w eJ l- III ~ Ir W ~ Z ~ 0 "- '; () ill er " " c~ c r { , } ~ ~ - 1 1 ~ ) C ~ ~ L. _ c ~ c _L.-O' cO _ )00,,"_,- ,,-oe \, " , ... Date 1 -14-98 Scale 1/4"=1'-0" PLOT Scole 1 =240 Drawn RMR Job 2645 Sheet A ~ Of 2 S"~eejs . 0-- "- ,/