Loading...
HomeMy WebLinkAboutOccupancy Housing Code 1978-10-2 -.~ . . CITY OF SPRINGFIELD SPRINGFIELD. OREGON 97477 DEPARTMENT OF PUBLIC WORKS October 2, 1978 346 MAIN STREET 726-3753 Ms. Lina Elliott 2449 Cora 1 Ori ve . Eugene, Oregon Re: Housing Inspection At 747 Kelly Blvd. : Dear Ms. Elliott: At your request, the Building Division of the City of Springfield made a housing inspection on September 29, 1978 at 747 Kelly Blvd., Springfield, Oregon. The following items must be repaired or replaced to conform with the Uni,form Housing Code as adopted by the City of Springfield. 1. All windows must open freely. 2. A firewall is required where the garage is attached to the-house. There must be a layer of 5/8 inch type x sheetrock installed on this wall. The sheetrock must run from the concrete foundation to the roof sheathing, on the garage side only, and all the joints must be filled with joint compound. 3. The water service must have a 3/4 inch gate valve. This 'valve must be in~ stalled on the property side of the meter in. the meter access .box. 4. A 3/4 inch gate valve must be installed on the inlet water line to the water heater. 5. A pressure and temperature relief valve must be installed on the water heater. A pipe must be connected to the relief valve, run down and to the. outside of the buil ding. 6. A number eight (8) copper wire must be connected to the common bar in the electrical service panel and connected with an approved clamp to the col~ water piping. 7. .A main breaker must be installed on the wires coming from the meter ahead of all other breakers in the electrical service panel. .... ." . . Housing Inspection Page 2. All necessary permits shall be obtained before work starts and all work shall be accomplished according to applicable codes and inspected before a Certifi- cate of Compl iance will be issued. Please direct all inquiries to the Springfield Building Division at 726-3753. S,incerely, . {9U&l_<:t/tc'd Dan Smith ! Building Inspector DS/l j