REPORT OF EPOXY ANCHOR INSPECTION
TESTED FOR HA YDEN HOMES PROJECT HA YDEN GARDENS
3258 PINYON SPRINGFIELD
SPRING'FIELD. OR 97478
ATTN ALICIA WOBBE
DATE MARCH 16. 1999 REPORT NO 722-90044-2
AS REQUESTED. PSI REPRESENTATIVE RALPH TURNER WAS ON SITE THIS DATE FOR THE PURPOSE OF VISUALLY INSPECTING
ANCHORS AS FOLLOWS
USE OF ANCHORS (SELECT ONE)
1) IS REQUIRED BY DRAWINGS
DRAWING NO(S}
DATED . STAMPED APPROVED BY
2) IS REQUIRED BY APPROVED CHANGE ORDER 9911620 BY J R BONNET ENGINEERING
APPROVED CHANGE ORDER ATTATCHED
3) HAS NOT BEEN APPROVED IN WRITING BY PROJECT DESIGNER AS OF THIS INSPECTION
~~l
EPOXY DESCRIPTION
REQUIRED
SIMPSON STRONG-TIE
CONNECTORS
5/8" ALL THREAD
I ACTUAL
SIMPSON STRONG-TIE
CONNECTORS
5/8" ALL THREAD
ANCHOR DESCRIPTION
(DIAMETER, LENGTH, TYPE)
HOLE CLEANING METHOD
(I E . DRIED. BRUSHED, BLOWN)
HOLE DIAMETER
(INCHES)
MINIMUM ANCHOR EMBEDMENT
DEPTH (INCHES)
DRIED BLOWN
DRIED BLOWN
"j.,"
"j.,"
9"
9"
LOCATIONS AND QUANTITY INSPECTED
ALONG SHEAR WALL IN RESIDENCE 3342 PINYON AVE (9) 5/8" ALL THREADS
PLACED 9" DEEP WITH 1" OF THREAD SHOWING AFTER THE ANCHOR HAD BEEN
PLACED
REMARKS ANCHORS INSPECTED DO MEET THE REQUIREMENTS IDENTIFIED ABOVE_
RESPECTFULLY SUBMITTED.
PROFESSIONAL SERVICE INDUSTRIES, INC
CC CITY OF SPRINGFIELD - BOB BARNHART