HomeMy WebLinkAboutPermit Field Test & Inspection Report 1984-11-9
;---: -.,,'
..
/
...
5().001
@
Pittsburgh
Testing .
Laboratory
PTL-EUGENE
545 CONGER STREET
eUGENE. OREGON 97402
503/484-9212
[Rl~[pJ({5)[Rlu
# 2
DRDERND, EUG 3976
DATE November 14, 1984
Ross Building Systems
P,O. Box 713
Creswell, OR 97426
3~5'L
l4-~v)"\ S~
REPORT OF:
Welder Qualification Test
INSPECTION DATE: 11-9-84
~
PROJECT: Mohawk Valley Grille Works
PERMIT NUMBER: 840696
INSPECTOR:
Mike Mabrey, PTL
Visual inspection and guided bend tests ,were performed on sections of a
3/8" plate welded by Ralph Sackett, Jr. The specimen was groove'welded
using 1/8" E70l4 electrodes.
Face-bend, root-bend and weld appearance were all acceptable according
to AWS 01.1-84 criteria. Mr. Sackett 'is therefore qualified to weld
plate up to 3/4" thick using groove or fillet welds in the flat position,
Respectfully submitted,
PITTSBURGH TC\TING LABORATORY
~r-\A~r \, lI'-?-~)
~~rry [, Johnson, Manager
Eugene District
MGM:ab
AU. qePOATS ~ _ ..:- ~:~ AS n-E __ _...., ~ PROPERTY OF Cl..ENTS. PuBLCATlQN 01' STATEMENTS. CONC1...USIONS OR EXTRACTS IS RlESE':""EC PENOlNG c:lI.AWl'llTTEN APPROV~. .
I ',~ :;, ~::.,' , WELDER AND WELDER OPERATOR QUALIFICATION TEST REPORT'
I Welder/Welder Operator's Name
Ra10h Sackett. Jr,
I Welder Identification No.
530-74-1868
Client
.-" ;-;
...
.
t-n\ Pittsburgh
(g, Testing
Laboratory
Date Reported
1]-14-84
Date Tested
11-9-84
Welding Code (10 & year)
AWS 01.1-84
.
Ross Building Systems
P,O. Box 713
Creswell. OR 97426
Base Material Specification
ASTM A36
Specimen
j(J Plate D Pipe
Specimen Furnished
Ij(I PTL 0 Others
Specimens Machined
D PTL ~ Others
Thickness Range Qualified
3/4" Max,
I Process
SMAW
I Positi~nG F 1 at
I Weld Progression
I Welding Procedure
No, B-U2a
I Welding Procedure Data by:
I ~ . :. - ';'.'
,,,:: " ,:, ;"" '
.,"^'l "._' ,- ..
" ". LA". ,~,'_ . "_'
I Specification No. A - 5
I Backing 1/4" plate
I Shielding D Gas:
D Up
D Down
Dcw
Dccw
~ LtoR
D RloL
Current
Rev, No, AMPS: 120 D AC
ID PTL Wilnessed (Tech): M. G, Mabrey
FILLER METAL
I Classification E7014
Diameter 1/8"
1O Flux:
IF. No.
Trade Name
2
U.S. Alloy
VISUAL INSPECTION (AWS ONLY)
Appearance Good
I Undercut
Nonp
I Piping Porosity
Nnnp
<,
GUIDED BEND TEST RESULTS
. -
TYPE
RESULTS
O,K,
O,K,
TYPE
Face
Root
FILLET TEST RESULTS'
I Weld Appearance
D Pass D Fail
I Macro Etch Test Result,S
D Pass D Fail
I Fracture Test Results (Describe location, nature & size of any cracks or tearing of the specimen)
I Fillet Size .
Leg: In. x
in. .
o Conc~vity:
'''' ,
I Film
Identification
I
RADIOGRAPHIC TEST RESULTS
Remarks
Film
Identification
Results
Tests Witnessed by:
QUALIFICATION RESULTS
so..LPOOOl
PTL-EU13ENE
045 CONGER STREET
EUGENE. OREGON 87402
!5O:3/464-8212 .
PTL Order No,
EUG 3976
Lab No,
2032
Joint
j(J Groove D Fillet
Plate Thickness
3/8"
Diameter & Wall Thickness
I Polarity
:)(J DC XJ Direct
D Others:
o Reverse .
in.
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
RESULTS
in.
D Convexity:
The We1d.er/Operator identified above ~ DOES 0 DOES NOT meet the performance qualifications specified in the Code identified I
above for the variables stated.. .
Remarks & Report Disliibution ('denotes data not provided or not applicable) , \;~~~A~L~
A. j ,. \U Manager
\1 ~ -
Results
Remarks