HomeMy WebLinkAboutPermit Field Test & Inspection Report 2001-10-18
(j
l.}~;l Information
~~. .10 Build On
Engineering. Consulting. Testing
DAILY FIELD REPORT
Date Performed. October 18, 2001 Report Number: 722-10168-6
Chent: Mr Mike Ferchland Project Name: Ferchland Residence
327 South 58th Street, #C
Springfield, OR 97478 Project Location: 6947 Ivy Street Springfield,
Oregon
P.O, No:
Type of Structure.
Type of Inspection:
Permit No.:
Weather:
00-01441-01
Clear
Walls
Reinforcing Steel
Reinforced Concrete
Field Observations and Comments
Performed visual inspection of reinforcing steel In the follOWing locations, 2nd floor walls from bedroom #2 and #3 to east
wall Reinforcement was placed per details from sheets 4 and 9, general notes and typical details, Reinforcing steel
was checked for grade, Size, lap, placement and clearances where apphcable Reinforcing steel was secured uSing tie
wire and supported on concrete doble blocks ReinforCing steel was placed In accordance with approved deSign
draWings and specifications Performed visual inspection dUring placement of concrete In the locations listed above
Concrete was placed by boom pump and manually consolidated Cast one set of four (6x12) concrete test cylinders
Plans drawn by Great Home Design, manufacturer of home To the best of our knowledge, the work Inspected above
was In accordance With the bUilding department approved deSign draWings, speCIfications and apphcable workmanship
'rOVISlons of the Uniform BUilding Code Contractor was asked to notify our office when additional services are needed
Tv De of MatenCll ~oncrete
Supplier Morse Bros
Mix # 712
Slump 5 3/4"
Air Content
Ambient Temperature
Material Temperature
Time Placed
DeSign Strength (psi)
Number of Samples
Total Yardage Placed
Inspector. -Greg Goudie, ICBO# 0853601-88
50
69
11 00 AM
3000
4 (6x12)
19
If you have any questions regarding thiS report, please feel free to contact us at 541-746-9649
Respectfully Sub Itted,
]fiit:rt~ In:rtt 1n )
Department Manager
c C,ty of Springfield
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
ProfeSSional Service Industries, Inc. 1040A Shelley St . Springfield, OR 97477. Phone 541/746-9649. Fax 541/746-7163