DAILY FIELD REPORT
Date Performed' July 12,2006 Report Number. 722-60170-18
Client: Mr Dennis Dille Project Name: Chip Handling Project
Weyerhaeuser
1300 SW 5th Ave, SUite 500 Project Location: 785 North 42nd Street
Portland, OR 97201 Springfield, Oregon
P.O. No.: Permit No.: CDM 'UJo(r 003,DD
Type of Inspection: Structural Masonry Weather: Overcast
Field Observations and Comments
Performed preliminary visual inspection of reinforcing steel In the follOWing locations MCC bUilding 8" CMU from 0' to 11'
4" from top of footing Reinforcing steel was checked for grade, Size, lap, placement and clearances where applicable.
All cells were relatively clean and mortar projections are within the limits of the International BUilding Code Note rebar
placement to be completed pnor to pour Clean outs proVided As per engineer of record Fred wIth B-Tec high 11ft
grouting acceptable To the best of our knowledge, the work Inspected above was In accordance with the bUilding
department approved design drawings, speCifications and applicable workmanship prOVIsions of the International BUilding
Code Contractor was asked to notify our office when additional services are needed
Inspector: David Smith, ICC# 0877340-84
If you have any questions regarding this report, please feel free to contact us at 541-746-9649
Respectfully Submitted,
ProfesslQ al Service Industnes, Inc
e-r-
c City of Spnngfield
Solarc Architecture - Galen Ohmart
Broad Base - Roy Gray
Branch Englneenng - Rene Fabncant
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS EXCEPT IN FULL WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
I
Professional Service Industries, Inc. 1040A Shelley St . Spnngfleld, OR 97477. Phone 541/746-9649. Fax 541/746-7163
----