DAilY FIELD REPORT
Date Performed:
Client:
July 11, 2006
Mr 'Denrlls Ehlle
Weyerhaeuser
1300 SW 5th Ave, SUite 500
Portland, OR 97201
Report Number:
722-60170-16
Project Name:
Chip Handling Project
785 North 42nd Street
Spnngfleld, Oregon
Project Location:
P.O. No.:
SCH-00019
Weather:
Overcast
Type of Inspection: Reinforcing Steel
Reinforced Concrete
Field Observations and Comments
, Performed preliminary Inspection of reinforCing steel In the following locations on dump truck foundation reclalmer wheel
nng section 5 and 6 and north truck dump foundation details Band C on 50068 and B-50060 Preliminary rebar
Inspection ReinforCing steel was checked for grade, Size, lap, placement, and clearances where applicable.
Reinforcing steel was placed In accordance With approved design drawings, specifications, and latest reVISions dated
July 10, 2006 at wheel ring Performed Visual inspection dUring placement of concrete In the above locations Concrete
was placed by truck chute and mechanically consolidated Cast one set of four (6x12) concrete test cylinders Note
verified rebar clearances pnor to concrete pour on wheel ring WIll perform final inspection on rebar at north truck
foundation pnor to pour To the best of our knowledge,-the work Inspected above was In accordance-with the bUilding
department approved deSign draWings, speCifications and applicable workmanship proVISions of the International
BUilding Code Contractor was asked to notify our office when additional services are needed
Ty~p of Material Concrete #1
Supplier Morse Bros
Mix # 2440N070RO
Slump 5"
Air Content 4 2%
Art:lpient Temperature 75
Material Temperature 75
Ti!'Tle Placed 10 45 AM
Design Strength (psi) 4000
Number of Samples 4 (6x12)
Total Yardage Placed 80
Inspector: David Smith, IcC# 0877340-88
If you have any questions regarding this report, please feel free to contact us at 541-746-9649
Respe tfully Submitted,
I
Prafe lonal S~stnes, Inc
__ fr~\--
.er Tran
tment Manger
~
c City of Spnngfleld
Sol arc Architecture - Galen Ohm art
Broad Base - Roy Gray
Branch Englneenng - Rene Fabricant
THIS REPORT IS PROVIDED FOR THE INFORMA TION OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT, BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
ProfeSSional Service Industries, Inc' 1040A Shelley St . Springfield, OR 97477' Phone 541/746-9649' Fax 541/746-7163
-----