HomeMy WebLinkAboutPermit Correspondence 2006-11-3
..
{., {P -/30-'1
l
November 3,2006
Mr. Dan Moore
Gateway Mall
3000 Gateway Street
Spnngfield OR 97478
Dear Dan:
Enclosed is a copy of our plan review comments resulting from the permIt application for
relocatmg a grease hood to tenant space 802. The comments address somewhat more
than Just the hood installation for this tenant space. Since you are usually mvolved in
these projects in one way or another, I would appreciate it if you would help to assure
that the plan review comments are satisfied for this project.
If you have any questions, please feel free to phone me at 726-3623.
Sincerely,
Donald Moore
Construction Representative/Plans Examiner
cc.
"
Development Services Department
Community Services Division
City of Springfield
Oregon Building Safety Section
(541) 726-3759
225 N. 5th Street, Springfield,
PLAN REVIEW COMMENTS
DATE: ,
November 3, 2006
JOB NO COM2006-0 1354
PROJECT
Type I hood for Space 802
LOCATED AT.
3000 Gateway Street
APPLICANT
Dennis Mancle
Phone. 953-0461
Plans submitted for the proposed construction at the above project address have
been revIewed for conformance WIth the City of Springfield buildIng safety codes
The follOWIng list of Items requIres correctIon, clarifIcation or addItIonal detailing
before they can be approved:
ISSUANCE OR GRANTING OF A PERMIT OR APPROVAL OF PLANS,
SPECIFICATIONS AND OTHER DATA SHALL NOT BE CONSTRUED TO BE A
PERMIT FOR, OR APPROVAL OF, ANY VIOLATION OF THE BUILDING SAFETY
CODES OR OF ANY OTHER ORDINANCE OF THE CITY OF SPRINGFIELD
ANY CHANGES OR ALTERATIONS made after the date of thIS revIew must be
approved by the BUilding OffiCIal
PLANS REVIEWED BY
Name
Signature
1. The termination point of the hood exhaust on the roof shall proVide a
minimum clearance of ten feet from openings into the building, including
HVAC equipment. (OMSC 502.7.2.6 #2)
.
.
2. The type I hood and duct shall be protected by an approved automatic
extinguishing system. Subcontractor shall provide submittal plans and cut
sheets of a commercial kitchen hood and duct fire suooression system(s)
meeting UL 300 to Springfield Development SeNlces Division Building
Permit Techmcian for review and approval by the Springfield Fire Marshals
Office for all cooking surfaces prodUCIng grease-laden vapors.
(2004 SFC 901.2)
3. An electncal permit Will be required for any addition to, extension of or
modification to the electrical wiring or electncal seNice equipment in the
tenant area, (OSSC 1 05.1
4. Any changes in lighting fixtures Will reqUire submission of lighting energy
code forms to demonstrate compliance with the connected lighting power
budget for the space.
Exceotion: Alterations to existing lighting systems that do not replace
more than 50% of the luminaries in the tenant space and do not increase
the existing total connected lighting power. (OSSC 1313.6)
5. ,An additional mechamcal permit will be required for any modifications to
the gas piping system for the tenant space. (OSSC 1 05.1)
6. A minimum bUilding permit is required for the minor framing modifications
needed for the new tenant. (OSSC 105.1)
7. Mall seating for the tenant space shall not encroach into the required mall
aisles There shall be a minimum of 10 feet clear eXit width between any
projection of a tenant space bordering the mall and nearest kiosk, vending
machine, bench, display opening, food court or other obstruction to means
of travel through the mall. (OSSC 402.5.1)