Geotechnical & Construcbon SeMc:es
Daily Field Report
Client:
Ms Silva Sullivan PrOject
Chambers Development Co
2295 Coburg Road
SUite 200
Eugene, Oregon 97401
Sports Way Business Park-Ph 2
3783 International Way
Springfield, Oregon
Date.
Project No
Report No..
Inspector
ID No.:
04-04-07
2077031
E-15881
E MarJama
5235029-49
ICC
Inspection of. Reinforced Concrete
Contractor. Chambers Construction
Weather Partly Cloudy/Rain
BP No . C-06-01357
Continuous Inspection: D
Periodic Inspection. 0'
Performed final inspection on the reinforCing steel for slab on grade on line A to D and
1 to 8 Reinforcing steel was checked for grade, Size, lap, placement and clearance
ReinforCing steel was secured with tie-wire and supported above grade with doble
blocks
Observed the placement of 227 0 cu /yds of Eugene Sand and Gravel's 3000 pSI
concrete (MIX 2144) In areas listed above Concrete was placed by pump and was
consolidated by Vibratory laser screed Cast two (2) sets of four (4) 6" x 12" concrete
test cylinders Dave Krull (Chambers Construction) was notified of on-site test results
Set 1
Slump - 4 3/4"
Concrete Temperature - 72F
Air Temperature - 46F
Set 2
Slump - 31/2"
Concrete Temperature - 70F
Air Temperature - 47F
Mr Krull was asked to notify our office when additional services are needed
To the best of our knowledge, the work Inspected was In accordance with plans dated
01-22-07 and applicable workmanship provIsions of the I B C , except If noted above
Reviewed By
;/J. 7:(}~
Michael L Meyer
Technical Manager
c Cham bers Construction - Brian Erickson (e-mail)
Eric Hall Architects - Steven Cho/Annette Rohde (e-mail)
Endex Engineering - (e-mail)
City of Springfield
MLMJw
ThiS report and/or enclosed test data IS the confidential property of the eilent to whom It IS addressed and pertains to the specific
process and/or matenal evaluated As such, Information contained herein shall not be reproduced In part or full and/or any part
thereof be disclosed without FEI Testing & Inspection, Inc 's wntten authorization
750 NW Cornell Avenue Corvallis, Qegon 97330 phone (541) 757-4698 fax (541) 757-2991
29540 B Airport Road Eugene, Qegon 97402 phone (541) 684-3849 fax (541) 684-3851