Loading...
HomeMy WebLinkAboutPermit Field Test & Inspection Report 2006-8-16 / ;' C-' 1. 0 rr\J. ar sort ~estlng, Inc. Main Office P,O, Box 23814 Tigard, Oregon 97281 Phone (503) 684-3460 FAX (503) 684-0954 Salem Office 4060 Hudson Ave, NE Salem, OR 97301 Phone (503) 589-1252 FAX (503) 589-1309 Bend Office PO Box 7918 Bend, OR 97708 Phone (541) 330-9155 FAX (541) 330-9163 September 1, 2006 S0604278.CTI Permit No COM2005-01685 C-'Q - ,v<6tQ FIELD INSPECTION REPORT DATES COVERED: August 16th, 2006 PROJECT. Bayberry Commons - Springfield ADDRESS: 2211 Laura Street - Springfield, OR INSPECTOR: G. Keene OBOA #698 08/16/06: As requested CTI representative was on site this date for epoxy anchor Installation for seismic holddowns (PHD2 & PHD5). Contractor installed 5/8" all thread with 6" embedment into slab on grade. Contractor used Hllti Hy-150 Max batch #003219L4 expiration 2/2007, nylon brush and forced air used to clean holes, Contractor to re-drill (4) holes that did not meet embedment reqUIrement, (2) In east wing & (2) in south wing tracked on NCL Item #3. Note, holes at entryway for PHD15 appear to be diamond bit cored and the anchors are not yet installed. *** CHECK ONE BOX ONLY *** 1 This IS a preliminary inspection only - OR - 2 The work Inspected conforms to acceptance cntena listed above, If "No,' the portions of the work that are non-conforming items are clearly stated above and Will be ad ded to the NCL. Remaining portions of the work, which are not preliminary In nature, are to be considered-as conforming .""" YES NO o o ~ Our reports pertain to the matenal testedlinspected only. Information contained herein IS not to be reproduced, except in full, without prior authorization from this office If there are any further questions regarding this matter, please do not hesitate tOjJont this office Respectfully submitted, ~ ~ CARLSON TESTING, INC. "\ j 4L.~ Steven L. Dugger ~ Salem Branch Manager GKlls cc: Burt Walter City of Springfield Diamond Engineering Tony Koach Architect RECEIVED S(p 0 8 1006 Sep 06, 2006 80604278. Carlson Testing, Inc. Incompleted Items List (NCL) PrOject Name Project Address' Pemnt No PO No, BAYBERRY COMMONS - SPRINGFIELD 2211 LAURA STREET - SPRINGFIELD, OR COM2005-01685 Item # Insp. Date Item Description Compliance cn Sign-Off 1 JR 06/23/2006 MIX DESIGN 2144 NOT APPROVED 2 JR 07/19/2006 MIX DESIGN #4184 NOT APPROVED 3 GK 08/16/2006 INSTALLATION OF SEISMIC ANCHORS, (4) HOLES NEED TO BE RE-DRILLED TO PROPER EMBEDMENT DEPTH (2) EAST WING & (2) SOUTH WING, CC BURT WALTER CITY OF SPRINGFIELD DIAMOND ENGINEERING TONY KOACH ARCHITECT PrOject Manager S, DUGGER Date Corrected Page 1