Carlson Testing, Inc.
REPORT OF
6 X 12
CONCRETE
Main Office
POBox 23814
Tlgard, Oregon 97281
Phone (503) 684-3460
Fax (503) 684-0954
TEST SPECIMENS
Test Methods: ASTM C31/C172/C192/C617/C1064/C231/C143
Date Molded: 06/30/2006
Permit#: COM2005-01685
Client: BURT WALTER
Project: BAYBERRY COMMONS - SPRINGFIELD
Address: 2211 LAURA STREET - SPRINGFIELD, OR
Contractor: x
Snbcontractor:
Concrete Supplier: EUGENE SAND & GRAVEL INC
Truck #: 260 Load #: 31
Weather: SUNNY
Test Time:
Cylinders were cast for the following locations:
SLAB ON GRADE 12 @ L
Total Concrete Placement Location:
1-31 @ A-W
Strength Requirement:
Mix Number: 2144
Admix/Amt: P8G - 240 OZ
Register Number: 0002134
3000
psi r c @ 28
Cone. Temp: 78
ConstructIOn InspectIOns & Related Tests
Geotechnical Consulting
Salem Office
4060 Hudson Ave, NE
Salem, Oregon 97301
Phone (503) 589-1252
Fax (503) 589-1309
Bend Office
POBox 7918
Bend, Oregon 97708
Phone (541) 330-9] 55
Fax (541) 330-9163
Job Number: S0604278.
Jurisdiction: SPRINGFIELD
Cast By:
11:42 AM
Days Slump:
Cement Type: I
Lab Location: SALEM
C. BIDWELL
Ticket#: 301102
Air Temp. at Sampling Time:
79
4.000"
% Air:
.75
1. 40%
Max Agg:
. Cubic Yards:
Set Test @ Date Test Total Area Unit Type Of Tested
No. Days Rec'd Date Load PSI Fracture By
4 7 07/03/2006 07/07/2006 79520 27.69 2870 5 JDV
28 07/03/2006
28 07/03/2006
Please see reverse side for additional information.
Job Number: S0604278. Register Number: 0002134
Project: BAYBERRY COMMONS - SPRINGFIELD
Date Molded: 06/30/2006
--- ~ < I In [25 mm]
XA
AY{
t ,
':\
Type I
Reasonable well-fonned
cones on both ends, less
than I In [25 mm] of
cracking through caps
Type 2
Well-Fonned cone on one
end, vertical cracks runnmg
through caps, no well-defined
cone on other end
Type 3
Columnar vertical cracking
through both ends, no
well-fonned cones
\
/
1\
/
Type 4
Diagonal fracture with
no cracking through
ends, tap with hammer to
dlstmgmsh from Type I
Type 5
Side fractures at top or
bottom (occur commonly
with unbonded caps)
Type 6
SimIlar to Type 5 but
end of cylinder IS pomted
Astensked (*) umt PSI test results dId not meet lIsted acceptance cntena
Remarks:
The area of the cylmders IS based on an assumed value of 28 26 unless noted
cc: CITY OF SPRINGFIELD
DIAMOND ENGINEERING
TONY KOACH ARCHITECT
Project Manager:
S DUGGER
Reviewed By: ~ /I _ __ _ _ __ __ __
Ste.:.r~
Our report pertams to the matenal tested only. The mformatIon contamed m thIS report IS provIded subject to all terms and
condItIons of CTI's General CondItIons m effect at the tIme thIS report IS prepared No party other than those to whom
cn has dlstnbuted thIS report shall be entItled to use or rely upon the mformatIon contamed m thIS document