REPORT OF
6 X 12
CONCRETE
TEST SPECIMENS
Test Methods: ASTM C31/C172/C192/C617/C1064/C231/C143
Date Molded: 06/30/2006
Permit #: COM2005-01685
Client: BURT WALTER
Project:BAYBERRY COMMONS - SPRINGFIELD
Address: 2211 LAURA STREET - SPRINGFIELD, OR
Contractor: X
Subcontractor:
Concrete Supplier: EUGENE SAND & GRAVEL INC
Truck #: 262 Load #: 10
Job Number: S0604278.
Jurisdiction: SPRINGFIELD
Cast By:
C. BIDWELL
Weather: SUNNY
Test Time: 7 : 42 AM
Ticket#: 301049
Air Temp. at Sampling Time:
68
Cylinders were cast for the following locations:
SLAB ON GRADE 31 @ V
Total Concrete Placement Location:
1-31 @ A-W
Strength Requirement:
Mix Number: 2144
3000 psi f'c @ 28 Days Slump:
Cone. Temp: 73 Cement Type: I
3 . 500 " % Air:
1. 40%
Admix/Amt: P80 - 240 OZ
Register Number: 0002132
Max Agg: .75
. Cubic Yards:
101
Lab Location: SALEM
Set Test @ Date Test Total Area Unit Type Of Tested
No. Days Rec'd Date Load PSI Fracture By
2 7 07/03/2006 07/07/2006 97855 27.69 3530 3 JDV
28 07/03/2006 I 07/28/20061 'I
28 07/03/2006 I 07/28/2006 I I
I I I
I I I
I I I
I I I
I I I
Please see reverse side for additional information.
Job Number: S0604278 Register Number: 0002132
Project: BAYBERRY COMMONS - SPRINGFIELD
Date Molded: 06/30/2006
---
A~
\
< I In [25 mm]
x
Type I
Reasonable well-fonned
cones on both ends, less
than I In [25 mm] of
crackIng through caps
Type 2
Well-Fonned cone on one
end, vertical cracks runmng
through caps, no well-defined
cone on other end
Type 3
Columnar vertical crackIng
through both ends, no
well-fonned cones
\
/
1\
.)"'
Type 4
Diagonal fracture with
no crackIng thr-ough
ends, tap wIth hammer to
distIngUish from Type I
Type 5
Side fractures at top or
bottom (occur commonly
wIth unbonded caps)
Type 6
SImIlar to Type 5 but
end of cyhnder IS pOInted
Astensked (*) umt PSI test results dId not meet lIsted acceptance cntena
Remarks:
The area of the cylInders IS based on an assumed value of 28 26 unless noted
cc: CITY OF SPRINGFIELD
DIAMOND ENGINEERING
TONY KOACH ARCHITECT
Project Manager:
S DUGGER
Reviewed By: ~ n/A.(',(J--__-
Steven 6rl"gger