CAlLY FIELD REPORT
Date Performed: September 19,2006 Report Number: 722-60145-49
Client: Mr John Helander Project Name: Regional Sports Center, Ph 2
Essex General Construction Basketball Building
4284 West 7th Avenue Project Location: 200 South 32nd Street
Eugene, OR 97401 Springfield, Oregon
P.O. No.: Permit No.:
Type of Structure: Weather: Rain
Type of Inspection: Structural Masonry
Field Observations and Comments
Performed visual inspection of reinforcing steel In the following locations grldllne 9-17/A top out Reinforcing steel was
inspected for Size, grade, lap, placement and clearances where applicable, Reinforcing steel was placed In accordance
with approved design drawings and specifications and detail 07/04. All cells were relatively clean and mortar projections
are withm the limits of the International BUlldmg Code. Performed continuous Inspection dunng placement of grout m the
locations listed above. Grout was placed by pump and mechanically consolidated, Only cells contalnmg relnforcmg
steel were grouted solid Empty cells were filled with wire mesh, To the best of our knowledge, the work Inspected
above was In accordance with the building department approved design drawings, specifications and applicable
workmanship prOVISions of the International BUlldmg Code Contractor was asked to notify our office when additional
services are needed.
~De of Materiaj
Supplier
Mix#
Slump
Air Content
Ambient Temperature
Material Temperature
Time Placed
Design Strength (PSI)
Number of Samples
Total Yardage Placed
Inspector: Jennifer Tran, ICC# 5282553-84
If you have any questions regarding this report, please feel free to contact us at 541-746-9649.
Grout
Morse Bros.
247KG3ROO
9"
680
750
11 40 AM
2500
3 yds
Respectfully Submitted,
Professional Service Industries, Inc.
~(.<
J nn r Tran
De ment Manager
c City of Springfield
Solarc Architecture - Galen Ohmart
Roy Gray
Branch Engineering - Rene Fabricant
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT. BY ANY METHOD, AND ITS TRANSMITTAL TO A THIRD
PARTY. BY ANY MEANS, EXCEPT IN FULL, WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
Professional Service Industries, Inc. 1040A Shelley St . Springfield, OR 97477. Phone 541/746-9649. Fax 541/746-7163
l- }!: ;llnf0171Ultion
~.,. .To Build On
Engineering. Consulting. Testing
DAILY FIELD REPORT
Date Performed:
September 20,2006
Mr John Helander
Essex General Construction
4284 West 7th Avenue
Eugene, OR 97401
Report Number:
722-60145-47
Client:
PrOject Name:
Regional Sports Center, Ph 2
Basketball BUilding
200 South 32nd Street
Springfield, Oregon
PrOject Location:
Contractor:
P.D No,:
Type of Inspection:
Essex General Construction
High Strength Bolts
Permit No.:
Weather:
COM2005-01773
Cloudy
Field Observations and Comments
Met on-site with Horning Construction representative to perform special Inspection on A~25 high strength bolts In the
primary structural roof connections Skidmore-Wilhelm test was performed and bolt crew was Instructed on "turn of the
nut" method of bolt tensioning Two (2) rafter/column lines were continuously Inspected dUring "snug tight" operation to
ensure compliance with AISC manual instructions by Horning Construction Additional Inspection Will be required upon
completion of "snug tight" tensioning (prior to final 1/3 turn) and again after final 1/3 turn has been performed To the
best of our knowledge, the work Inspected above was In accordance with the bUilding department approved deSign
draWings, specifications and applicable workmanship provIsions of the International BUilding Code The contractor was
asked to notify our office when additional services are needed
Inspector: Chris Thomason, ICC # 5069949-85
If you have any questions regarding thiS report, please feel free to contact us at 541-746-9649
Respectfully Submitted,
Professional Service Industries, Inc.
Christopher Thomason
Structural Steel Field Supervisor
c City of Springfield
Solarc Architecture - Galen Ohmart
Roy Gray
Branch Engineering - Rene Fabricant
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT, BY ANY METHOD AND ITS TRANSMITTAL TO A THIRD
PARTY, BY ANY MEANS, EXCEPT IN FULL WITHOUT THE WRITTEN PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES, IS PROHIBITED
Professional Service Industrres, Inc. 1040A Shelley St . Sprrngfleld, OR 97477. Phone 541/746-9649. Fax 541/746-7163
l.... ~ ;1 Information
~...,. .To Build On
II!!nglneerlng. Con.uIf:Ing . TestIng
Client:
Address:
COMPRESSION REPORT
Mr John Helander
Essex General Construction
4284 West 7th Avenue
Eugene, Oregon 97401
Project No.:
Project Name:
Location:
Placement Data
6" S 0 G for basketball court
Matenal
Concrete
Location Sampled At Yardage
B 75/6 Load 25
Date Cast 08/24/06 Date Rec'd. 08/25/06 Total 254 25
Ticket No MIx No Weather Suppher
2617507 2440N05000 Overcast 1\ Morse Bras
722-60145-37
Regional Sports Center, Ph 2
Basketball Building
200 South 32nd Street
Springfield, Oregon
(
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477'
(541)746-9649 ph - (541)746-7163 fax
Date: September 11, 2006
B.P. No.:
P.O. No.:
Cast By: Jerry Adams
Field Test Data
Slump (m) ASTM C143 4 25"
Max Aggr Size,
Air Content ASTM C231
Air Temperature (F) 65
Matenal Temp (F) ASTM C1064 72
Max Temp (F)
Mm Temp (F)
Specimen Size 6x12
Umt Weight (pcf) ASTM C138
Time Cast 8 30 AM Curmg Conditions
Additives
Results Reported To Contractor
Design Strength (psi):
required 4,000
Compressive Strength Data ASTM C39
placed 4,000
Cylinder No
06-2615
06-2616
06-2617
06-2618
Test Date
Field Cure
(days)
Lab Cure DIameter or
DimenSIons
(days) (Inches)
6 600
27 598
27 600
2827
28 11
2827
Age (days)
Cross Sect Area (s I )
8/31 /006
9/21/2006
9/21/2006
Hold
7
28
28
Hold
Hold
.. 1 - Cone (both ends) 2 - ConeNertlcal Cracks (one end)
Remarks
C
\ ,
3 - Columnar
I
4 - Diagonal wIno craklng at ends
City of Spnngfleld
Solarc Architecture - Galen Ohmart
Roy Gray
Branch Engineering - Rene Fabricant
Morse Bras
Cylinder WT
(Ibs)
Max Load
(Ibs)
ASTM C31
Comp Strength Fracture Type" Test Time
(pSI)
Capping Method
C617.{13
C1231-lJ3
4,020
5,430
5,530
3
3
3
10 46 AM
3 27 PM
3 32 PM
x
x
X
6 - Top fractures (same as #5 but end of cylinder IS pOinted)
RlectfUIIY S mltted,
PI rJ eSSi~nal e ic~ustries, Inc.
!\J ( ,
/
Steven E Wilder
Laboratory Supervisor
THIS REPORT IS PROVIDED FOR THE INFORMA TlON OF THE CLIENT ONL Y THE REPRODUCTION OF THIS REPORT BY ANY METHOD AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL IS PROHIBITED
WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES
291
292
292
113,615
152,700
156,425
5 - Side fractures (at top of bottom)
IpsilJ::1Ji:::;:;~n
I!!!nglneerlng. ConsultIng . TestIng
Client:
Address'
Mr John Helander
Essex General Construction
4284 West 7th Avenue
Eugene, Oregon 97401
Placement Data
6" S 0 G for basketball court
COMPRESSION REPORT
Project No,:
Project Name:
location:
Matenal Concrete
Location Sampled At Yardage
B 75/3 Load 40
Date Cast 08/24/06 Date Rec'd 08/25106 Total. 410
Ticket No MIX No Weather Supplier
2617516 081-40N05000 Clear Morse Bras
Desi~)n Strength (psi):
Cylinder No
06-2623
06-2624
06-2625
06-2626
required 4,000
Test Date
Field Cure
(days)
Lab Cure
(days)
Age (days)
8/31/2006
9/21/2006
9/21/2006
Hold
7
28
28
6
27
27
Hold
Hold
722-60145-36
Regional Sports Center, Ph 2
Basketball Building
200 South 32nd Street
Spnngfleld, Oregon
~
SPRINGFIELD OFFICE
1040 - A Shelley Street
Springfield, Oregon 97477
(541)746-9649 - (541)746-7163 fax
September 29, 2006
Date:
B.P. No.:
P.O. No.:
Cast By,
Jerry Adams
Field Test Data
Slump (m) ASTM C143
Max Aggr Size
Air Content ASTM C231
Air Temperature (F)
Matenal Temp _ (F) ASTM C1064
Max Temp (F)
Mm Temp (F)
Specimen Size
Unit Weight (pct) ASTM C138
Time Cast 12 00 PM
Additives
Results Reported To
5"
1/2"
16%
75
78
6x12
Cunng Conditions
Gontractor
ASTM C31
Cylinder WT
(Ibs)
I
Gomp Strength
Max Load (Ibs ): (pSI) Fracture Type ..
Test Time
Capping Method
C617-Q3
C1231-Q3
Compressive Strength Data ASTM C39
placed 4,000
Diameter or
DimenSions Cross Sect Area (s I )
(Inches)
599
599
600
2821
2821
2827
294
294
294
117,755
153,430
150,685
4,170
5,440
5,330
3
3
10 19 AM
3 54 PM
3 57 PM
x
X
X
3 - Columnar 4 - Diagonal wino craklng at ends 5 - Side fractures (at top of bottom) 6 -iTop fractures (same as #5 but end of cylinder IS pOinted)
'1e~CtfUIIY Submitted,
Pr sio~al ~Services Industries, Inc.
1J~ '
Sti-Man E Wilder
Uaboratory Supervisor
I
THE REPRODUCTION OF THIS REPORT BY ANY METHOD AND ITS TRANSMITTAL TO A THIRD PARTY BY ANY MEANS EXCEPT IN FULL IS PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF PROFESSIONAL SERVICE INDUSTRIES
.. 1 - Cone (both ends) 2 - ConeNertlcal Cracks (one end)
Remarks: Set 5 of 5
c City of Spnngfleld
Solarc Architecture - Galen Ohmart
Roy Gray
Branch Englneenng - Rene Fabncant
Morse Bras
THIS REPORT IS PROVIDED FOR THE INFORMA nON OF THE CLIENT ONL Y