HomeMy WebLinkAboutPermit Substandard Building 1981-2-12 . .- IClQI.\b CITY OF SPRINGFIELD SPRINGFIELD. OREGON 97477 PUBLIC WORKS February 12, 1981 346 MAIN STREET 726-3753 ./ Mr. & Mrs. Hubert Ray 81518 Lost Creek Road Dexter, Oregon 97432 Dear Mr. & Mrs. Ray: At the request of the Springfield Utility Board, the Springfield Building Division made an electrical inspection at 725 Fairview Drive on February 9, 1981. The following defects were found: 1. A safety hazard exists where the service entrance cable passes through the studs. This cable must have protection as provided for in Article 230-50 National Electrical Code. A 1/16 inch steel plate over the cable where it passes through the wood structural members is acceptable. It is my recommendation that the non-metallic cable on the outside of the upper plates going into the attic be notched into the upper place and covered with a 1/16 inch steel plate. Article 300-4 National Electrical Code. Please be advised that the above mentioned violations must be corrected within 15 days (February 27, 1981) of the date of this notice. Any structure for lease, sale or rent is required to be wired by a licensed electrical contractor and all required permits and inspections must be obtained. Please direct all inquiries to the Springfiel'd Building Div,ision at 726-3753. Sincerely, JamesR. Matteson Electrical Inspector JRM/cp j-I1 ,/J'11~~