November 5, 2007
Chalet Village MHC LLC
,450 Newport Beach Drive, Ste 595
Newport Beach, CA 92660
RE: 205 South 54th Street, Springfield, Oregon
Dear Property Owner:
As a result.of a tenant complaint, the City of Springfield Community Services Division, Building
Safety, performed an electrical safety inspection at the above referenced location, also known as
Lane County Reference Number17023300, Tax Lot Number 01200, and found somespaces to
be, for reasons specified below, unsafe and hazardous. Lane County Assessment and Taxation
records reveal that you are the oWner of this property.
Space 1:
Space 2:
Space 3:
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
Electrical Service Equipment shall be firmly secured to the surfac'e on which it is
mounted. . The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
This unit is of immediate concemdue to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Insp~ctor due to the potential
electrical hazard. The electrical feeder from the service to the home needs to be
installed in a manner that conforms to the Oregon Electrical Specialty Code.
Section 230.24.B.l states 10 feet clearance shall be maintained at the lowest point
of the drip loop of the building electrical service and above areas or sidewalks
accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained
over residential property. Service conductors over residential property shall
maintain a minimum distance of 12 feet from the ground. Section 358.30A states
Electrical Metallic Tubing (EMT) shall be securely fastened in place at least every
10 feet and within three (3) feet of every box and/or termination. Section 358.42
states couplings and connectors used with EMT shall be made up tight. 'Where
installed in wet locations, boxes and fittings shall be listed for use in wet
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 2.
Space 5:
Space 6:
Space 8:
Space 10:
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
This unit is of immediate concern due to wires lying on the roof or very close to
. the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. Electrical' Service Equipment shall be firmly secur~d to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty Code Section 11O.13.A. The electrical feeder from the service to the
, '
home needs to be installed in a manner that conforms to the Oregon Electrical '
Specialty Code. Section 230.24.B.l states 10 feet clearance sh~l be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be
maintained over residential property. Service conductors over residential property
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) shall be securely fastened in place at least
every 1 b feet and within three (3) feet of every box and/or termination. Section
358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conduCtors and shall comply with the .
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be fmnly secur~d to the surface oJi which it is,
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A. This space also has a ground connection at the residence that needs re-
crimped.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure: Oregon Electrical Specialty Code Section
1I0.13.A. '
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 3.
Space 11:
Space 12:
Space 13:
, Space 14:
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. The electrical feeder from the service to the home needs to be
installed in a manner that conforms to the Oregon Electrical Specialty Code.
Section 230.24.B.l states 10 feet clearance shall be maintained at the lowest point
of the drip loop of the building electrical service and above areas or sidewalks
accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained
over residential property. Service conductors over residential property shall
maintain a minimum distance of 12 feet from the ground. Section 358.30A states
Electrical Metallic Tubing (EMT) shall be securely fastened in place at least every
10 feet and within three (3) feet of every box and/or termination. Section 358.42
states couplings and connectors used with EMT shall be made up tight. Where
installed in wet locations, boxes and fittings shall be listed for use ill wet..
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to th~ surface on which it is
mounted. The electri<fal service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subjectto being disconnected by Springfield.Utility Board at the
request of the City of Springfield Electrical Inspector due to the immediate
electrical hazard. Electric;;ti Service Equipment shall be firmly secured t~ the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. ,Oregon Electrical
Specialty Code Section 11O.13.A. .
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be sepured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 4.
Space 17:
Space 20:
Electrical Service Equipment shall be fIrmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A. The electrical feeder from the service to the home needs to be installed
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.1 states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fIttings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specifIc
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs. .
. This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) oris subject to being disconnected by SpringfIeld Utility Board at the
request of the City of SpringfIeld Electrical Inspector d\le to the potential
electrical hazard. Electrical Service Equipment shall be :firmly secured to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty Code Section 110.13 .A. The electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical
Specialty Code. Section 230.24.B.1 states 10 feet clearance shall be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. Section 230:24.B.2 states 12 feet shall be
maintained over residential property. Service conductors over residential property
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A,
states Electrical Metallic Tubing (EMT) shall be securely fastened in place at least
every 10 feet and within three (3) feet of every box and/or termination. Section.
358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fIttings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specifIc requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 5.
Space 23: This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the Ciry of Springfield Electrical Inspector due to the potential
electrical hazard. Electrical Service Equipment shall be. firmly secured to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty Code Section IIO.I3.A. The electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical
Specialty Code. Section 230:24.B.l states 10 feet clearance shall be maintained at
the lowest point of the dtip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. . SeCtion 230.24.B.2 states 12 feet shall be
maintained.over residential property. Service conductors over residential property ,
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) shall be securely fastened in place at least
every 10 feetand within three (3) feet of every box and/or termination. Section
. 358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs. .
~
Space 24:
This unit is of immediate concern dl.le to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City, of Springfield Electrical Inspector due to the potential
electrical hazard. Electrical Service Equipment shall be fIrmly secured to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty Code Section IIO.I3.A. The electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical
Specialty Code. Section 230.24.B.I states 10 feet clearance shall be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or 'sidewalks accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be
maintained over residential property. Service conductors over-residential property
shall maintain a miniminn distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) shall be securely fastened in place at least
every 10 feet and within three (3) feet of every box and/or termination. Section
. ,
358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
205 South 54th .Street
Electrical Hazards
November 5, 2007
Page 6.
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and diinensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 25: The electrical feeder from the service to the home needs to be installed in a
manner that cohforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
, Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 26: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building elec11jcal service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a'
minimum distance of 12 feet from the ground; Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10,feet
and within three' (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations. '
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 31 : The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l stites 10 feet clearance shall be maintained at the ,lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained oyer
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 7.
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations,. boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. - Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 34: This unit is of immediateconcem due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. The electrical feeder from the service to the home needs to be
installed in a manner that conforms to the Oregon Electrical Specialty Code.
Section 230.24.B.l states 10 feet clearance shall be maintained at the lowest point
of the drip loop of the building electrical service and above areas or sidewalks
accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained
over residential property. Service conductors over residential property shall _
maintain a minimum distance of 12 feet from the ground. Section 358.30A states
Electrical,Metallic Tubing (EMT) shall be secure~y fastened in place at least every
10 feet and within three (3) feet of every box and/or termination. Section 358.42
states couplings and connectors used with EMT shall be made up tight. Where
installed in wet locations, boxes and fittings shall be listed for use in wet
_ locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the .1
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 35: The electrical feeder from the service to the home needs to be installed ina
manner that conforms to the Oregon Electrical Specialty Code. Section
-. 230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or si<;lewalks.accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintai.rt. a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 8.
Space 36:
Space 38:
Space 39:
Space 41 :
Section 314}1 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
This unlt is of immediate concern due to wfres lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. Electrical Service Equipment shall be firmly secured to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty Code Section 11O.13.A. The electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical
Specialty Code. Section 230.24.B.1 states 10 feet clearance 'shall be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be
maintained over residential property. Service conductors over residential property
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) shall be securely fastened in place at least
every 10 feet and within three (3) feet of every box and/or termination. Section
358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded eIl,tries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mount~d. The ~lectrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty' Code Section
110.13.A.
Electrical Service Equipment shall be firmly secured to the surface on which it is
, .
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
205 South 54th Street
Electrical Hazards
November 5,2007
Page 9.
"
Space 45: Electrical Service Equipment shall be fIrmly secured to the surface on which it is I
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
lIO.B.A. .
. Space 46: .Electrical Service Equipment shall be fIrmly secured to the surface on which it is
mounted. The electrical service equipment ,has become lqose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
lIO.B.A. '
Space 72: Electrical Service Equipment shall be fIrmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty. Code Section
11O.13.A.
Space 50: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 fe~t shall be maintained o~er
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
. Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet.
and within three (3) feet of every box and/or termination. Section 358.42 states .
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fIttings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported.
enclosures shall have threaded entries or approved hubs. .
Space. 51: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of t4e building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residentiaI property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and witpin three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be. made up tight. Where installed
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 10:
Space 53:
Space 54:
Space 55:
Space 61:
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosUres shall have threaded entries or approved hubs.
Electrical Service Equipment shall be filmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Qregon Electrical Specialty Code Section
11O.13.A.
, '
Electrical Service Equipment shall be firmly secured to the surface op. which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
.electrical hazard; The electrical feeder from the service to the home needs to be
installed in a.manner that conforms to the Oregon Electrical Specialty Code.
Section 230.24.B.1 states 10 feet clearance shall be maintained at the lowest point
of the drip loop of the building electrical service and above areas or sidewalks
accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained
over residential property. Service conductors over residential property shall
maintain a minimum distance of 12 feet from the gr<?und. Section 358.30A states
Electrical Metallic Tubing (EMT) shall be securely fastened in place at least every
10 feet and within three (3) feet of every box and/or termination. Section 358.42
states couplings and connectors used with EMT shall be made up tight. Where
installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this' section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
th .
205 South 54 Street
Electrical Hazards
November 5, 2007
Page 11.
Space 62:
Space 63:
Space 67:
The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.1 states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. SerVice conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locatio~s.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
. requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) ods subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. The electrical feeder from the service to the home needs to be
installed in a manner that conforms to the Oregon Electrical Specialty Code.
Section 230.24.B.1 states 10 feet clearance shall be maintained at the lowest point
of the drip loop of the building electrical service and above areas or sidewalks
accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained
over residential property. Service conductors over residential property shall
maintain a minimum distance of 12 feet from the ground. Section 358.30A states
Electrical Metallic Tubing (EMT) shall be securely fastened in place at least every
10 feet and within three (3) feet of every box and/or termination. Section 358.42
states couplings and connectors used with EMT shall be made up tight. Where
installed in wet locations, boxes and fittings shall be listed for use in wet
- locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of cOl"l:ductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.B.A.
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 12.
Space 70:.
Space 75:
Space 76:
The electrical feeder from the service to the home needs to be installed in a
manner that conforms to .the Oregon Electrical Specialty Code. Section
230.24.B.1 states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
. ,
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has.become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A. The electrical feeder from the service to the home needs to be installed
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
This unit is of immediate concern due to wires lying on the roof or very close to
the roof This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential
electrical hazard. Electrical Service Equipment shall be firmly secured to the
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 13. .
Space 78:
Space 79:
Space 81:
Space 82:
Space 83:
surface on,which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electncal
Specialty Code Section 110.13.A. The electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical
Specialty Code. Section 230.24.B.l states 10 feet clearance shall be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. Section 230.24.B.2 states 12 feet shall be
mamtained over residential property. Service conductors over residential property
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) shall be securely fastened in,place at least
every 10 feet and within three (3) feet of every box rind/or termination. Section
358A2 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and shall comply with the
specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs. .
Electrical Service Equipment shall be frrmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section .
11O.13.A.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The e}(~ctrical service equipment has become loose over time and needs /
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
Electrical Service Equipment shall be frrmly secured to the. surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1 IO.13.A.
Electrical Service Equipment shall be frrmly secured to the surface on which it is
mounted. The electrical serVice equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1 10. B.A.
Electrical Service Equipment shall be fmrily secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1l0.13.A.
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 14.
Space 84: .
Space 85:
\
\
This unit is of immediate concern due to wires lying on the roof or very close to
the roof. This unit needs to be repaired immediately (within 20 days of receipt of
this letter) or is subject to being disconnected by Springfield Utility Board at the
request of the City of Springfield Electrical Inspector due to the potential .
electrical hazard. Electrical Service Equipment shall be firmly secured to the
surface on which it is mounted. The electrical service equipment has become
loose over time and needs to be secured to the structure. Oregon Electrical
Specialty C.ode Section 110.13.A. Th~ electrical feeder from the service to the
home needs to be installed in a manner that conforms to the Oregon Electrical,
Specialty Code. Section 23024.B.l states 10 feet clearance shall be maintained at
the lowest point of the drip loop of the building electrical service and above areas
or sidewalks accessible to pedestrians. Section 230.24.B.2 states '12 feet shall be
maintained over residential property. Service conductors over residential property
shall maintain a minimum distance of 12 feet from the ground. Section 358.30A
states Electrical Metallic Tubing (EMT) 'shall be securely fastened in place at least
every 10 feet and within three (3) feet of every box and/or termination. Section
358.42 states couplings and connectors used with EMT shall be made up tight.
Where installed in wet locations, boxes and fittings shall be listed for use in wet
locations. Section 314.71 states pull and junction boxes shall provide adequate
space and dimensions for installation of conductors and.shall comply with the
. specific requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A. The electrical' feeder from the service to the home needs to be installed
ina manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
topedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMt shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use ip wetlocations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
"
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 15.
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries' or approved hubs. .
Space 86: Electrical Service Equipment shall be fIrmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
Space 87: Electrical Service Equipment shall be fIrmly secured to the surface on which it is .
mounted. The electrical serv~ce equipment has become loose over time and needs.
to be secured to the structure. Oregon Electrical Specialty Code Section
I 10. 13.A.
Space 88: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.1 states 10, feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed..
in wet locations, boxes and fIttings shall he listed for use in wet locations.
Section 314.71 states pull ahdjunction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specifIc
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have ,threaded entries or approved hubs;
Space 89: Electrical Service Equipment shall be fIrmly secured to the surface on which itis
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A. The electrical feeder from the service to the home ne'edsto be i~stalled
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
. residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. . Where installed
205 South 54th Street
Electrical Hazards
November'S, 2007
Page 16.
Space 94:
Space 95:
Space 97:
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs. -
Electrical Service Equipment shall be firmly secured to the sUrface on which it is
mounted. The electrical service equipment h~ become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1 10. 13.A.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A. The electrical feeder from the service to the home needs to be installed'
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and conneCtors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
,dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Elel;trical Specialty C.ode. SeCtiori
230.24.B.l states 10 feet clearance shall be maintained 'at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24~B.i states 12 feet shall be maintained over
residential' property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30Astates Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every'l 0 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
th
205 South 54 Street
Electrical Hazards,
November 5, 2007
Page 17.
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 98: Electrical Service Equipment sp.all be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
Space 99: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feetshall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittirigs shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 100: Electrical Service,Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A.
Space 101: Electrical Service Equipment shall be firmly secured to the surface on which itis
,mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A. '
Space 105: Electrical Service Equipment shall be fmnlysecured to the surface on which it is
mounted. The electrical service equipment has become,loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
UO.13.A. '
Space 106: Electrical Service Equipment shall be fmnly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
th
205 South 54 Street
Electrical Hazards
November 5,2007
Page 18.
,
Space 110:
to be secured to the structure. Oregon Electrical Specialty Code Section
1 10. 13.A.
Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
Space 111: Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has-become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1 10. 13.A. The electrical feeder from the service to the home needs to be installed
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.1 states lO-feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service <;onductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Space 112: Electrical Service Equipment shall be frrmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
1 10. 13.A.
Space 114: Electrical Service Equipment shall be frrmly secured to the surface on which it is
mounted. The electrical- service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A. The electrical feeder from the service to the home needs to be installed
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.1 states 10 feet clearance shall be maintained atthe lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
205 South 54th Street
Electrical Hazards
November 5,2007
Page 19.
-,
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used ,with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the.specific
requirements of this section. Section 314.23.E states Raceway supported'
enclosures shall have threaded entries or approved hubs.
Space 116: Electrical Service Equipment shall be firmly secured to the surface on which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
110.13.A.
Space 117: Electrical Service Equipment shall be firmly secured to the surface on'which it is
mounted. The electrical service equipment has become loose over time and needs
to be secured to the structure. Oregon Electrical Specialty Code Section
11O.13.A. The electrical feeder from the service to the home needs to be installed
in a manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip IQop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a.
minimum distance of 12 feet from the ground. Section 358.30A states Electrical
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
couplings and connectors used with EMT shall be made up tight., Where installed
in wet locations, boxes and fittings shall be listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported,
enclosures shall have threaded entries or approved hubs.
Space 121: The electrical feeder from the service to the home needs to be installed in a
manner that conforms to the Oregon Electrical Specialty Code. Section
230.24.B.l states 10 feet clearance shall be maintained at the lowest point of the
drip loop of the building electrical service and above areas or sidewalks accessible
to pedestrians. Section 230.24.B.2 states 12 feet shall be maintained over
residential property. Service conductors over residential property shall maintain a
minimum distance of 12 feet from the ground. Section 358.30A states Electric81
Metallic Tubing (EMT) shall be securely fastened in place at least every 10 feet
and within three (3) feet of every box and/or termination. Section 358.42 states
205 South 54th Street
Electrical Hazards
November 5, 2007
Page 20.
couplings and connectors used with EMT shall be made up tight. Where installed
in wet locations, boxes and fittings shallbe listed for use in wet locations.
Section 314.71 states pull and junction boxes shall provide adequate space and
dimensions for installation of conductors and shall comply with the specific
requirements of this section. Section 314.23.E states Raceway supported
enclosures shall have threaded entries or approved hubs.
Oregon Revised Statute 479.540 states in part that an electrical contractor is required to perform
'electrical work on property that is for rent, sale, or lease. Therefore, an electrical contractor must
be hired by your company to obtain a permit for the replacement and/or repair of the above
mentioned items. A separate permit will be required for each service.
Due to the hazardous nature of these violations, all work must be performed and an inspection
conducted within 60 days from the date of this letter, unless otherwise noted.
If you have any questions, please feel free to contact me at 541-726-3663.
SinCerj) ., /
~A
Guy Dixon ..
Electrical Inspector
~