Loading...
HomeMy WebLinkAboutBuilding Miscellaneous 2014-6-9 s_i y- 0 ) 132-) PO Box 92126-Eugene-OR 97404 • �rCommercial,Industrial,Residential,Maintenance,Control and Data et.scrim in_,Plaone:(541)359-1192 Fax:(591)961-0507 CCB#149509 To: City of Springfield, Electrical inspector—Guy Dixon From: Rich Salahor, Owner, Supervisor—RS Electric LLC Project Address: 423 D Street Electrical Load Calculation for : A 2 Story Dwelling with the 1st Fir @ 1300 Sq Ft & 2nd Fir @ 1300 Sq Ft General Load: 2600 Sq Ft x 3VA 7800 VA 2 Appliance 3000 VA Laundry 1500 VA Range 12000 VA Water Heater 4500 VA Dishwasher 1500 VA Dryer 5000 VA Microwave 1200 VA 36500 VA Demand Factor: 36,500 VA= 1st 10, 00 VA @100% 10,000 VA Remaining 26,500 VA @ 40% 10,600 VA 20,600 VA Heating: 18,500 VA @ 40% 7,400 VA 28,000 VA Calculated Load for Service Size: 28,000 VA/240V= 116 Amps If you have any questions or concerns, please feel free to contact me. Sincerely, Rich Sa lahor RS Electric LLC (W)541-359-1192 (C) 541-228-0200 (F) 541-461-0507