IESnnca/nsaECnon,,,r. Daily Field Report
G.ESTI,."l a Conwuction s...,.., Geotechnical&Cortsinxx�•on Services
• Client: Ms. Laura Farthing Project: Hayden Bridge Water Date: 02-05-14
EWEB Intake Improvements Project No.: 2127278
. . PO Box 10148 Springfield, Oregon Report No.: E-36015
•
Eugene, Oregon 97440 Inspector: A. Fenstermacher
ID No.: 5258882-49
ICC
Inspection of: Epoxy Anchors Weather: Clear Continuous Inspection: ❑
Contractor: John Hyland Construction BP No.: -- Periodic Inspection:
Performed continuous inspection during the installation of epoxy anchors as follows:
eight (8) 1 1/4" x 13" stainless steel all-thread anchors into north wall for hold-down
attachment and eight (8) 5/8" x 6" galvanized all-thread anchors into top of wall for
attachment of intake #1 roof structure. Prior to installation, the predrilled holes were
cleaned with a brush and compressed air. Verified minimum embedment depth of 4"
for 5/8" anchors. Measured an embedment of 10" to 10 1/2" for 1 1/4" anchors.
Anchors were secured with Hilti Hit RE 500SD (ICC — ES ESR 2322/ expiration date
09/2014).
•
Note: plans specify the use of epoxy thru-bolts with a plate and nuts on opposite side
of wall from hold-down. Due to inaccessibility of opposite side of wall (below grade);
Dave Shaw (JHC) stated that approval from EWER was obtained to eliminate thru-bolt
installation and use epoxy anchors.
To the best of our knowledge, the work inspected was in accordance with plans dated
04/2012 and applicable workmanship provisions of the I.B.C., except if noted above.
Reviewed By:
• Michael L. M er
Technical Manager
•
c:
John Hyland Construction— Dave Shaw(email)
OBEC—Pete Slocum (email)
City of Springfield
MLM:sc
•
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such,information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing&Inspection,Inc.'s written authorization.
7W NW Card Avenue Corvallis,Cregon 97330 phone(541)7574698.fax(541)757-2991
29540 B Airport Road•Eugene,Oregon 97402•phone(541)684-3849•fax(541)6843851
62979 NE Plateau Drive,Suite 3.Bend,Oregon 97701 .phone(541)382-4844•fax(541)382-4846
•