HILL & DALE ENGINEERING, LLC
PO BOX 95
VIDA, OREGON 97488
(541) 868-0667
Feb. 28,2014 FAX: (541) 896-9205
� �' Slay` 2l3
7z3 g
Jim Porter
591 W. 10th Ave.,
Eugene, Oregon 97401
RE: 423 D Street, Springfield - Job # 196-13
The LTP4 connections between the "existing" rim joist and the 1" floor proposed walls are not
required to be installed if the following criteria is met:
-the wall sheathing extends from the existing rim to the framed walls below.
-the plywood edge is blocked at the framed wall.
-the nailing to the rim joist to the rim joist and blocking is a minimum of 8d @ 6 inches on center
or the specified nailing at the shear wall locations.
Thank you for this opportunity to be of service. If you have questions regarding this report,feel free
to contact us at 541-868-0667. p