Loading...
HomeMy WebLinkAboutMiscellaneous Electrical 2013-12-13 S13° 62313 i 11 1 sPRINGFIEl.D UTILITY BOARD I:I.I:c7RIC S I:Itvlcli C I:NTI:It 1001 Main Street Springfield, OR 97477-4819 Tal 541.726.2395 Fax 541.726.2399 www.subutil.com 12/1 3/201 3 Chuck Arrera • Olson Electric Re: Fault current available at 66th & Thurston Road Monitoring Station Dear Chuck: The Proposed service has the following characteristics: Primary feed: Opal Circuit out of Mt. Vernon Substation at 12.47 kV Service: 120/240 Transformer: 50 kVA 1.4 % impedance . Transformer#1505 Given these criteria, the expected fault current is 14,881 Amps. These values may increase based on future system changes to either the Springfield Utility Board electric systems or the regional high voltage power system. rpared by, Tony Mot Engineering Technician •