Loading...
HomeMy WebLinkAboutApplication APPLICANT 11/22/2013 ;City of Springfield SPRINGFIELD Development Services Department 225 Fifth Street Springfield, OR 97477 ll/ Development Issues Meeting (DIM) Required Project Information (Applicant: complete this section) Prospective Brandon Olsen 503-691-4998 Applicant Name: one: Company: AT&T Mobility Fax: N/A Address: 19801 SW 72nd Ave, Tualatin, OR 97062 Prospective Steve Bodine 503-544-9695 Applicant's Rep.: Phone: Company: Lexcom Development Fax: -N/A Address: 9635 SW Washington St, Portland, OR 97225 Property Owner: Mr. Randy Cummings Phone: 541-913-6493 Company: TAJ Enterprises Inc Fax: N/A Address: 19110 E Poco Rio Drive, Rio Verde, AZ 85263 ASSESSOR'S MAP NO: 0188522 TAX LOT NO(S): 1703220002603 Property Address: 2728 Pheasant Blvd, Springfield, OR 97477 Size of Property: 3.02 Acres X Square Feet ❑ Description of If you are filling in this form by hand, please attach your proposal description to this application. Proposal: See attached Existing Use: Property currently maintains an athletic club on site # of Lots/Parcels: N/A Avg. Lot/Parcel Size: N/A sf Density: N/A du/acre Prospective Applicant: 11/21/13 ,�j lei> lip rP�,ort Date: Signature Stephen Bodine, Lexcom Development, For AT&T Mobility Print Required Project Information (City Intake Staff: complete this section) Case No.: pte (s- OOU yo Date: ((/221) 3 Reviewed by: Z/Z Application Fee: $ 5a i T is fiJp Postage Fee: $0 TOTAL FEES: $ Oa I o ''�NOV 2 2 f2OJECT NUMBER: P12- 13 —6t I Original Submittal Revised 5/21/13 KL 1 of 4 • • Table of Contents 1. Description of Proposal 2. Support Documentation a. Lease exhibit b. Survey c. Utility coordination report d. Initial photo sims 3. Initial (5) questions for jurisdiction feedback Date Received: NOV 2.2 2013 original Submittal Description of Proposal AT&T Mobility Site ID: EG34-Gateway Mall East AT&T Mobility is proposing to develop a 120' "moderate visibility"WTS facility featuring a stealth mono-pine tower application at 2728 Pheasant Blvd, Springfield, OR. The property currently maintains an athletic club and is located in the CC zone. Ground equipment to be housed within a new equipment compound placed in the parking lot and median area on the property. Proposed equipment shelter and related to be surrounded by slatted fencing and applicable landscaping to meet city code requirements while minimize visual impact. Support documentation is attached for review and reference. Date Received: NOV 2.2 2013 Original submittal_____ a. Lease Exhibit Date Received: NOV 2 2 2013 Original Submittal c " o — wN to co E- 3 is L� i= g-, < pr, '"ab ° Q N q Q 3 F °a 3(:16= z oe a w }� o h[ ally w J m ¢ a CO T "Ce- hp� ry e,o::� e co 06 6 R IV °w) o a Q zoo o �a =$.o - f°� is z �'.; N o o X w z o a_ 8 o w i Vt°oga'aa }, z > z: a U' a w u w °w f 3 w w W „. o >„ ow. a CO J . m 0: s' u- w } w w W og ,. 2/.>/P 3 oaW�g¢� w ' 1 ' `y Y , O u 7ou3 Q p LLU' Z u) '� Ed i o 6 el a zO¢~--NU 1- m W CO / rc • ?..1°� .°, m z_ .ai Q '� ° u w a ¢ :4-.9 ,¢ w N to ,e,\' a • a w O w ry p W I� I I - 7 �y p N n F u, w o Z I- r 6 re J Z oa��°�� r f U rc O m w az a.-c Z O•����� w L- a U m w 0 p a. o o _ w D _ °-u oap Z = —� Z w m 3 p K Z 3 i°u p O . 'O p > a m w a u�Zai 4 3 n 5 m m w a rc w v rc Sawow„o a a w II I I I I I I I_I I I I—J I I1 I I I I_ I I p o a-a o z z ® a O. Q 1 < :f. re a ii ` ? ; en I a N o `_ N ,3_+ c, N E 4 I ® C Y O r I i I V IMITIT1, r > 461 J 1- w - I -i plTTTIT.i a i b. Survey Date Received: NOV 2 2 2013 Original Submittal z � m vl n m ryry —I�G Z 2S Ili++ lJ o � Ao- � � 0 _ IE4q w IL I 3 p 9ry P�j� IrOFJ� JT`J (� EgtlgA 1Ii ly /fga� ° E V w W CO • j �=44 ]3 `Rf€ W o m rc6 x)11 91 i39 ! mo ro , "E fi mo < [i w a p-p °N m i z u "' a F F $ m<� '^< ¢ 5 9'86 �rS f '" s €S , W Z y , > O j w w V ~ s 2 F < 1-°K �O > t5 [m5 ° - w ZZ < ..e0-8. > G x 2 a E > > o o s � Yi § Q 9 m m ` Hg d g<a4 § ` g m`-°§o 84F E< g > tl Oh o z >< >< °u p� g zg ? 3L = m = { <z=<zs Q�aso° '°8 xz '+ z! c°.mm $ 6. 0 mss m W W m °I rc w W e w e r z y , 8 wcwirc� 5nvl<z1 1,1119 i > i in $ ,$� �qe1< m o o a E o u s . H N 7 o i g - C g 3 G a cl °Tn m i.- o°OZO� J °=°° soinw g U <o ry5° 8 li <ap Z€•<> X g F �, I5 ° * a ® q❑ ® d • 6 < ac c 5 UJ'�� VVVYYYJJJ I-77..Z (z�m'gL3< a a a °< U' a m 'm o Jm m m J a a W 3 X W n gBJi10 m °'68.w om= °m°I m �Izw"J6oa NO kiN WI I I i I° 5. % S m , .. g<W9* W 5 *JPar . b ii z8 i =o�=�c0 8 4 6 5 , i1 P• I a < = FZ a e1 w s<� �" o ° 0<m 0 A m , a << $ a g , I �yoc� �vAi ugm <a � a 4� wp_,_g g�`3a Z ( I P S O F F U m J LLUnZi a Z7 OF C° Z �u TwO `61518 g222 i I a > > n ° k' k' � �o o Q7i cmi � czw< < o< °z°�° aarvs2 'Wag Fk'za nts 100 . 001 . ..205!- !QA f� n� °oz� mmw° >>N° w.c 0 izz° BFF I F po8 ii- g -6gm md — uQ 1`1p1 mi 6C _ _ _ _ .n lb Fwg l<.°O .<.. ra '� Gf m �l�amm "°05 1 44 WW¢¢ Z y1WOrOvW OU6 N<3 I 1<`2zs REecB -ezm e I °g "s J "g< oci y �i wogiiN 5,8 g j��xg ` I 68 I ii N AS o �$ FOa am„. -38 ,3w,9 m AOZi m aIP c..a, > 3 I �//:. N_ µI PK m nn < n s �t •p0M C_ w N • '< Ws I - n p, oszo I J C1 3 st I a ; ZD6bY O 3 R 2 ��O✓Yj 0.<t e uj ul s I I rag2 _ --- 3 °w I 'I S 8F ° _i PHEASANT ST F% 1 " M. g ❑ . g N r a a R 8; y$ a m ° I I Q � ° I �l n ° \`ON< N GATEWAY ST—S a$ / 3•n,6S ION a i~ p I U FN FM * la'/ H� ��I _ / 14 4 _ CC q cL 55 W I kr-- 12 y F g ,g aI I I I w r W° §U "15 •'b I °m 1, I m it n - I LPg w m I ..,.,..,ii..,.....,,, �. °i a a sE w Foa 7 ,id 1104 I O 8 I W W zF I a .c II TA a§ 0— i N.ce g Ia ,� l ®� l® f IT— ®� I —( � I _f 1 • j o g _ I tts H1• , j 1 tt ., j'I j i j I i ° V 1 igl, j �y ;F 4er*.w 1 ill ° as 1 Lam_ —1 — H§ww co c��� _ j - - � —or CIP re II 35tlHd V6YNVIp ZZ-171 / II 35VNd YOYN% YZ 10l I NI 6 II 3SVHd AOMIY GIV3 V 3)NOd 3HI 9101 JO 1YWJ6'9101 1 c. Utility coordination report Date Received: NOV 2 2 2013 Original Submittal i O Prelim: 11/15/13 FINAL: DATE a `� ` Revision: XX T` t Rev Date: DATE Utility Coordination Report EG34 Gateway Mall East FA: 10576512 USID: 154949 PRELIMINARY 4. r. Fr- Company: R&W Engineering Consultant: Heather Harris Phone Number: 503.726.3321 Email: hharris @rweng.com Site Status: 2013 SAO POWER: Springfield Utility Board ENET: NA TDM: CenturyLink(Qwest) :gate Receiver,- UCR:EG34 Gateway Mall East - 1 - 1321 027.001 ND 2 2 201 . 0 0 y 4 j •• AT&T to provide and I Existing instal(1)4'Schedule I Cenlurylink PVC Conduit with Pedestal (1)(1)1-114"innerduct . ' •- •. 650 and pulltape in a 36" I AT&I Lease below grade trench. I Area AT&T to , provide and AT&T to sweep(1)2"Schedule 40 PVC r ( install 3048 �:yt,. 1 •Conduit with pulliape up at existing Centurylink f handhole. I Pedestal#8650. re 1. �^ t" €4 AT&T to place the — J 1<4 conduit in a 36"below t I grade trench. — — — — - - *' Mil. .I' ' AT&T to provide and install ` Ara4,i 3048 handhole.Centurylink 11:,V-• / AT&T to bore or cut and ~ will bring future fiber/Ethernet • • ' patch existing paved surface ' i to this handhole. . •-a"-,4 t•• — - y — - 1 ( !� ' I I AT&T 3 to place the conduc and conductors Existing SUB Pole#97138 11.f��aJ in a 36'bebw grade trench. AT&T to sweep(1)3"Schedule 40 PVC Conduit with(3)#3/0 copper conductors up at the base of existing SUB Pole#97138.The sweep to be a schedule 40 long sweep with 36"radius.AT&T to provide and install a new 3"Schedule 80 riser on the existing SUB pole. The riser will need to be 10'in length.AT&T to provide a 40'cod of spare conductors at the pole for SUB connections. Date Re - r' Nov 2 c ••.3 Original SubmI'.- .. ...------.. UCR:EG34 Gateway Mall East - 1 1 - 1321.027.001 S. • 0 AT&T to place AT&T to sweep(1)3"Schedule 40 PVC Conduit with(3)#310 copper conductors up at the conduit and the base of existing SUB Pole#97138.The sweep to be a schedule 40 long sweep conductors in a with 36"radius.AT&T to provide and install a new 3"Schedule 80 riser on the existing 36"below grade ) SUB pole. The riser will need to be 10'in length.AT&T to provide a 40'coil of spare trench. conductors att the pole for SUB connections. f 1_,_, \ , ,\ 1 • t i Sc AT&T to provide and AT&T to provide and install ` �.,; install(1)4"Schedule 3048 handhole.Centurylink ! T 40 PVC Conduit with will bring future fitter/Ethernet , 6ir (1)1-1/4"innerduct to this handhole. r`7 and pulttape in a 36" - below grade trench. - AT&T to place the \ } ° conduit in a 36"below \ grade trench. • \ y , „ . A t1 t-/ A s - �' I - AT&T to sweep(1)2°Schedule 40 PVC 1.r. cl ? : Conduit with pulttape up at existing Centurylink -+'r I - Pedestal#R650. '. ii Date Received: Gov 2 2 2013 oft. -r;ttai ilry�as ;..• UCR:EG34 Gateway Mall East - 12- 1321.027.001 • • • • .._. ,~ AT&T to provide and install(1)4"Schedule PVC Conduit with (1 • (1)1-1l4'innerduct • and pulftape in a 36" below grade trench. -- L ~� AT&T to provide and install (1)3'Schedule 40 PVC Conduit with(3)#3/0 copper conductors in a 36'below grade trench. Date Received: M0V 2 2 2013 UCR:EG34 Gateway Mall East - 13 - 1321.027.001 . • • .4 `. e I . ', AT&T to provide and - , , .1 install(1)2"Schedule AT&T to provide and _ 40 PVC Conduit with install new H-Frame • pulltape in a 36" with 200A Meterbase Future Fiber/Ethernet below grade trench. and 3'X3'X1'NEMA , Demarcation Enclosure 3R Hoffman _ Enclosure. AT&T to provide and install awlw (1)3°Schedule 40 PVC Conduit with(3)#3/0 copper AT&T to install a conductors in a 36"below 12"X12°X9" grade trench. weatherproof junction box. �� .�. Junction box to be IT`( mounted over _ •.. _ --■.- - — existing wall penetration into AT&T shelter. AT&T to AT&T to provide and AT&T to provide and provide and install install 3048 (1)4"Schedule install(1)2"Schedule 40 PVC Conduit with 40 PVC Conduit with handhole (1)1-1/4"innerduct pulltape in a 36"below and pulltape in a 36" grade trench. below grade trench. Date Received: NOV 2 2 2013 Original Submittal UCR:EG34 Gateway Mall East - 14- 1321.027.001 • d. Initial photo Sims Date Received: NOV 2 2 2013 Original Submittal fr ■ . ! • i ��� - V a I S �• co�wsvon,e EG34 GATEWAY MALL EAST f EXISTING NORTH ELEVATION *attAived: NOV 21 2013 Original Submittal • i • 1111111rit 10011111111==- CORNER-STONE EG34 GATEWAY MALL EAST Date � LNCIINCCRINCI INC PROPOSED NORTH ELEVATION et v 8tt NOV 2 2 2013 original Submittal._..__._. • • fE f aye �c. 4. o _ �� co�tN6r�ISTONE EG34 GATEWAY MALL E' ST EXISTING SOUTH ELEVATIrir to Receiv dt&t NOV 2 2 2013 Original Submittal _--. • • . 7k :c + - ti 1 l __ of �� COFWEaSTON@ EG34 GATEWAY MALL EAST PROPOSED SOUTH ELEVATION Date R e is NOV 2 2 2013 Original Submittal __ • 0 Ili x' ` dr 4 "'I - . .,:Ls � .x s F R n. ._---- _ w- _ % `ate ' _ .- a� � �� coaro�sTOnrE EG34 GATEWAY MALL EAST `� at&t • EXISTING EAST ELEVATION Date Received: NOV 2 2 2013 Original Submittal • • _ � .. . er' ; • • r 1 • [a • EG34 GATEWAY MALL EAST C-d at&t PROPOSED EAST ELEVATION Date Received: NOV 2 2 2013 Original Submittal_._.,____-_ i 0 • 1111r - ....._, CD NERSTONE EG34 GATEWAY MALL EAST `.00 at&t EXISTING WEST ELEVATION Date ived: NOV 2 2 2013 Original Submit. • • S . + k } a 1 _._..__ .. ?IF J 4 • COr7NERsTONE EG34 GATEWAY MALL EAST DeBatt, & d: PROPOSED WEST ELEVATION NOV 2 2 2013 Original Subm c;, Initial (5) questions for planner consideration DIM Site Plan Requirements-On site drainage collection system and flow patterns,size/location of drainage lines and catch basins,natural drainage ways to be retained Question#1: Existing cell tower and ground compound are not adjacent to waterways. Should I assume this line item is not relevant for insert into zoning drawings? Sub Section G.1.b-Geographic Service Area.The applicant shall identify the geographic service area for the proposed WTS facility,including a map showing all of the applicant's and any other existing sites in the local service network associated with the gap the facility is meant to close.The applicant shall describe how this service area fits into and is necessary for the service provider's service network. The service area map for the proposed WTS facility shall include the following: i. The area of significant gap in the existing coverage area; ii. The service area to be effected by the proposed WTS facility; iii. The locations of existing WTS tower facilities where co-location is possible within a 5-mile radius of the proposed WTS facility. Question#2: Does the city have a listing with this information? If not,I will utilize existing FAA website and related but want to be sure this will suffice to address the above requirement? Sec 12-Accessory Building Size.All accessory buildings and structures built to contain equipment accessory to a WTS facility shall not exceed 12 feet in height unless a greater height is necessary and required by a condition of approval to maximize architectural integration. Each accessory building or structure located on any residential or public land and open space zoned property is limited to 200 square feet,unless approved through the Discretionary Use process. Question#3: Industry standard pre-fab equipment shelter intended for the side maintains a dimension of 11.5'x 26'=299 sq.ft Is this OK via Discretionary Use process? Sec 22. Parking.No net loss in required on-site parking spaces shall occur as a result of the installation of any WTS facility. Question#4: Noting ground compound will be placed in parking space and median area while not impacting existing walkway,should we assume re-stripping will suffice to address no net loss in parking requirement? Date Received: NOV 2 Z 2013 Original Submittal • • G.2.L Visual Impact Study and Photo Simulations.The applicant shall provide a visual impact analysis showing the maximum silhouette,view shed analysis,color and finish palette,and screening for all components of the proposed WTS facility.The analysis shall include photo simulations and other information necessary to determine visual impact of the facility as seen from multiple directions.The applicant shall include a map showing where the photos were taken. Question#5: Can you help clarify the visual impact analysis requirement? Date Received: NOV 2 2 2013 Origir. oubmittai_ �___