Loading...
HomeMy WebLinkAboutComments FLS 6/11/2013 METZGER Mark From: GORDON Gilbert Sent: Tuesday, June 11,2013 8:48 AM To: METZGER Mark Subject: RE: WiecherUMallard View Subdivision Comments Fire Department comments are as follows: • Access: 1. The fire apparatus access road for this proposal shall be 26 feet clear width due to the length of this road exceeding 500"feet per 2010 Springfield Fire Code Table D103.4. Parking can be allowed on either side provided it is outside that 26 foot clear width. Otherwise, no parking signage shall be required on either or both sides where parking may encroach on the required fire apparatus access width. 2. The turn radii to access this road and for the proposed turnaround shall be not less than 30 inside and 50 feet wall to wall outside (SFC 503.2.4). 3. Fire apparatus access roads shall be an all weather surface capable of supporting an 80,000 lb. imposed load. Water Supply: Two fire hydrants are required due to the length of this proposal. Contact Bart McKee at SUB Water for further information. - • Hope that helps. Gilbert R. Gordon Deputy Fire Marshal Springfield Fire and Life Safety • 225 Fifth Street • Springfield, Oregon 97477 Office Phone: 541-726-2293 Please note my new e-mail address: • ggordon(a springfield-or.gov - From: METZGER Mark • Sent: Tuesday, June 11, 2013 7:58 AM To: GORDON Gilbert Subject: Wiechert/Mallard View Subdivision Comments Thanks for meeting with me yesterday. I believe I understand your comments from our discussion before Al dropped by. Could you confirm your comments in an e-mail. I'd be glad to drop off the plan set if that would be helpful. Mark Metzger, Planner III City of Springfield 225 Fifth Street • Springfield, OR 97477 (541) 726-3775, Fax (541) 726-3689 Date Received: Chili ; ( ; Planner: MM 1