nIfShnitol NSPfCionSer„re technical&Constru on Services Daily Field Report
Client: Mr. Kelly Staines Project: LTD—Storage Shed Addition Date: 08-05-13
Lane Transit Dist. 3500 E. 17th Ave. Project No.: 2137074
PO Box 7070 Eugene, Oregon Report No.: E-34578
Eugene, Oregon 97401 Inspector: A. Fenstermacher
ID No.: 5258882-49
• ICC•
Inspection of: Wedge Anchors Weather: See Below Continuous Inspection: ❑
Contractor: Chambers Construction BP No.: 811-SPR2013-00496 Periodic Inspection:
08-01-13: Performed continuous inspection during installation of forty-eight(48) Powers
1/2” x 5 1/2" Power-Stud+ SD1 wedge anchors (ICC ESR 2818/2966) into existing floor
slab for connection of new storage racks inside new storage building. Two (2) anchors
were installed thru each base plate. Prior to installation, verified minimum embedment
depth of 3 1/4". Holes were drilled deeper to accommodate drilling fines. Verified
installation torque of 40 ft. lbs. using a calibrated torque wrench. (weather: inside).
08-05-13: Returned to jobsite and witnessed installation of sixteen (16) 1/2" x 7 1/2"
anchors securing exterior storage rack frames to existing concrete paving east of new
storage building. Anchors were installed and checked as noted above. (weather:
clear/60°).
Mike Kennedy (Galifco) was asked to notify our office when additional services are
needed.
To the best' of our knowledge, the work inspected was in accordance with RDE
drawings dated 06-19-13 and applicable workmanship provisions of the I.B.C., except if
noted above.
Reviewed By: •
Michael•zi
r
Technical Manager
c:
Chambers Construction —Shawn Hussey(email)
Chambers Construction —Chris Boyum (email)
City of Springfield — Robert Castile (email)
MLM:sn
•
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such,information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing&Inspection, Inc.'s written authorization.
750 NW Cornell Avenue•Corvallis,Oregon 97330.phone(541)757-4698•fax(541)757-2991
29540 B Airport Road•Eugene,Oregon 97402.phone(541)684-3849•fax(541)6843851
62979 NE Plateau Drive,Suite 3 Bend,Oregon 97701 phone(541)382-4844•fax(541)382-4846