HomeMy WebLinkAboutPermit Mechanical 2013-8-7 •
•
SPRINGFIELD' 225 Fifth St
`` CITY OF SPRINGFIELD Springfield,OR 97477
kr.
t Phone: 541-726-3753• OREGON Building / Commercial Permit Inspection Phone:541-726-3769
Fax: 541-726-3676
• PERMIT NO: 811-SPR2013-01770
www.springfieldar.gov permitcenter @spdngfield-or.gov
PROJECT STATUS: Issued ISSUED: 08/07/2013 EXPIRES: 02/02/2014
STATUS DATE: 08/07/2013 •APPLIED: 08/07/2013
SITE ADDRESS: 250 A ST,Springfield,OR 97477 SCOPE: Mechanical Only
ASSESOR'S PARCEL NO: 1703353202700 TYPE OF STRUCTURE: Commercial
PROJECT DESCRIPTION: HVAC Springfield Utility Board-Lower Offices
OWNER: CITY OF SPRINGFIELD Phone Number:
ADDRESS: 250 N A ST
SPRINGFIELD OR 97477
OWNER: SPRINGFIELD UTILITY BOARD Phone Number:
ADDRESS: 250 N A ST
SPRINGFIELD OR 97477 .
_ CONTRACTOR INFORMATION
Contractor Type Contractor Name Lic Type Lic No Lic Exp Phone
Mechanical Contractor MARSHALLS INC CCB ' 25790 12/23/2013 541-747-7445
INSPECTIONS REQUIRED
Inspections
2300 Rough Mechanical Rough Mechanical: Prior to Cover
2999 Final Mechanical Final Mechanical: When all mechanical work is complete.
By signature, I state and agree,that I have carefully examined the completed application and do hereby certify that all
•
information hereon is true and correct, and I further certify that any and all work performed shall be done in accordance with the
Ordinances of the City of Springfield and the Laws of the State or Oregon pertaining to the work described herein, and that NO
OCCUPANCY will be made of any structure without permission of the Community Services Division, Building Safety. I further
certify that only contractors and employees who are in compliance with ORS 701.005 will be used on this project. I further agree
to ensure that all required inspections are requested at the proper time, that each address is readable from the street,that the
permit card is located at the front of the property, and the approved set of plans will remain on the site at all times during
construction. .
•
•
Owner or Contractor Signature Date
le)
ONLY tt I 61
ATTENTION: Oregon law requires you to
J u Cc"
f^i follow rules adopted by the Oregon Utility
Notification Center. Those rules are set forth
kf ✓.if.- LeA in OAR 952-001-0010 through OAR 952-001- •
c ' oto 0090. You may obtain copies of the rules by
S
NOTICE' ti calling the center. (Note: the teleph;:at
number for the Oregon Utility Notification
THIS PERMIT SHALL EXPIRE IF THE WORK Center is 1-800-332-2344).
AUTHORIZED UNDER THIS PERMIT IS NOT
•
COMMENCED pO[R IS ABANDONED FOR
;''41.1gfield auiDRIYPbrrhI�IOD. 8/7/2013 1:47:41 PM Page 1 of 1
•
SPRINGFIELD - CITY OF SPRINGFIELD
225 Fifth St
" �t0 EGON TRANSACTION RECEIPT Sphngfield,OR 97477
541-726-3753
811-SPR2013-01770
www.springfield-or.gov 250 A ST - permitcenter @springfield-or.gov
RECEIPT NO: 2013001724 RECORD NO:811SPR2013-01770 DATE:08/07/2013
�1T�01' ' 01tf x$9.1' i ,5s .tE_st aiY..3:3"'= i .0 00 .._.S� i tplVt�k�1
�:__ r;t '-ie-_:w� ��:�__r - .T' n:: •NSCODE .`,�_.''�:���p. l o " i
Mechanical Permit fee(based on value of work) 224-00000-425604 1006 100.65
State of Oregon Surcharge(12%of applicable fees) 821-00000-215004 1099 12.08
Technology fee(5%of permit total) - 100-00000-425605 2099 5.03
TOTAL DUE: 117.76
PAY.MENTsTYPE la cases'` ER:JLAIRS - COMMENTS • AMOUNT PAID
Credit Card MARSHALLS INC 117.76
08473D
TOTAL PAID: 117.76
•
RUG-07-2013 13:05 MARSHALLS I NC.I 541 741 0821 P.02
•
Mechanical Permit Application DEPARTMENT USE ONLY
SPRINGFIELD
C11YOF SP121NC Ilk IA)4)R EC 0 N Permit no.:5117013 01770
225 Fifth Street •Springfield OR 97477 • P14(541)726 3753 • FAX(541)726 3689 )/7//•, •OREGON
•
This permit is issued under OAR 918-440-0050. Permits expire if work is not started within 180 days of issuance or if work is
suspended for 180 days.
CATEGORY OF CONSTRUCTION FEE SCHEDULE
❑ Residential • ❑Government [Commercial— Residential Qty. Cost Total
en. fast
JOB SITE INFORMATION AND LOCATION First Appliance $80.00 ~$
Job site address: ,Q5 Q 4 3.4-. Furnace/burner including ducts and vents
City: ✓Ihe� State: 87L I ZIP: y7q-77 llp to IOOk BTU/hr. I $16.50 $
5 Over IOOk BTU/hr. $22.00 $
Reference: Taxlot.:
DESCRIPTION OF WORK Unit Heaters/stoves/vents
,, /� a Unit heater $18.50 $
�Y1$4r OR&Hes ] - _ea Auk, Wood/pcllet/gas stove/clue $42.00 $
%L9 / d110� Repair/alter/add to heating appliance/
C refrigeration unit or cooling system/ $80.00 $
PROPERTY NER7777 absorption system
Name: cPvi'yws�-p Id ufi 175 �R/l.ei' Evaporated cooler $14.50 $
/ Vent fan with one ducVappliance vent $10.00 $
Address: 02 5 b� 4 5i--.
City: ✓t Vj`'t'trJ� C X4777 Hood with exhaust and duct $14.50 _ $$
Ci State: ZIP: Floor furnace including vent $80.00 $
Phone:S ! 95 r Fax: - - Gas piping
E-mail: ke t/ Yount L,Q. COMA One to four outlets $7.50 $
This installation is being made on property owned by me or a Additional outlets(each) $4.50 $
member of my immediate family, and is exempt'from licensing Mr-handling units,including ducts
requirements under ORS 701.010. i lip to 10,000 CFM $12.00 $
Signature: Over 10,000 CFM $22.00 S
CONTRACTOR INSTALLATION
I Compressor/absorption system/heat pump
Up to 3 7/ Q �" ac «�� Up to 15 Business name: hp/500k BTU $32.00 $
Address: 1/0 Up to 30 hp/1,750 BTli $47.50 $
City: '7/fly�,y,�lN P j 45_tate�: ...���rr���i ZIP: �� Up to 50 hp/1,750 BTI-1 $62.50 $
Phoney-. 7-74 5 Faj I7#/– Mi I Over 50 hell.750 BTU $104.50 $
E-mail: 04,4.1® 4i0ta.d ,;4c - CBN7 Incinerators
A• Z57 Domestic incinerator l I $22.50 $
CCB license no.: — Co_mmercial
Print name: 7iy% 5�ti t/6 e.// Enter total valuation of mechanical system
and installation costs$_
Signature: Enter fee based on valuation of mechanical system,etc. $
Miscellaneous fees Items Cost Total
eq. Cost
Reinspection $80.00 $
Specially requested inspections(per hr.) $80.00 $
Regulated equipment(unclasscd) $14.50 $
Each additional inspection:(I) $80.00 $
APPLICANT USE
(A)Enter subtotal of above fees(or enter set
minimum fee of $80.00) $
(B)Investigative fee(equal to[A]) $
(C)Enter 12%surcharge(.12 x(A+B]) $
(D)Seismic fee, 1%1.01 x[A]) $ _
(E)Technology Fee(5%of[A]) $ •
440-2545-.I(4/1/2013/COM) TOTAL fees and surcharges(A through E): 5#221:—
PUG-07-2013 13 06 MARSHALLS INC. 541 741 0821 P.03
SPRINGFIELD
CITY OF SPRINGFIELD, OREGON • ®�®
DEVELOPMENT SERVICES DEPARTMENT
Application Date: t2'5 . •' OREGON 225 FIFTH STREET
SPRINGFIELD, OR 97477
Permit II: - " " PHONE (541)726-3753
Installation Address: FAX (541)726-3676
www.spdngfeld-orgov
COMMERCIAL MECHANICAL PERMIT WORKSHEET
In order to determine code compliance of the proposed installation please provide the following information in
addition to the permit application: 1)Legible copies of the new equipment's manufacturer's listing,cutsheets
and installation instructions, 2)ComCheck energy compliance forms,and 3) *when required,wet-signed
engineering calculations and structural details for seismic bracing. Please complete all fields-use N/A where
not applicable. M sz&e!2 NA TO
Old Equipmmeennt/� New or Replacement EquiiPment*M u' -6(1.2 NA 00
Type& Model N? TDii-swbtsVt1 CuC1 It s nea_�' () p
Unit Weight* WPC 1Mooc 2 7 1 6s 101A-door go 16s
Capacity (BTU,Ton,etc.) /VA /07 k Coo /'r j 1! 3,1e N Pa+c,s
Efficiency Rating(HSPF,SEER,etc.) //1/1/1—I2' N SP F /w. S Sea.
Outdoor Air supplied(CFM)** /- /�/ A
Ventilation supplied(CFM)** �^(///" _ /A1//I
Exhaust Rate(CFM)** /1///"
" /" /v A
Structural Seismic Bracing* ❑Yes No ❑Yes)21/No
Is this installation within a Special Flood Hazard Area as determined by FEMA? ❑Yes`• ■lo
Prepared and signed by: Building Owner❑ Contractor, Design Professional❑
I certify that the information provided above is complete and accurate to the best of my knowledge:
•
Signed: *`✓G r Date: 2/6// 3
Print Name: per^ fc-rrasso
CCB or Design Professional License Number: 2C 7 c0
*New and replacement equipment shall have seismic bracing designed by an Oregon Registered Engineer and installed in accordance
with the Engineer's design per OSSC 1613.7.6, 1613.7.7 and ASCE 7-05 section 13.1.4.
Exceptions:
I. Equipment weighing 400 pounds or less and mounted 4 feet or less above a floor or roof level.
2. Components weighing 75 pounds or less.(5 pounds for distribution systems)
3. Replacement equipment which weighs the same or less than the equipment it replaces,uses the same seismic
attachment and bracing,and is installed in the exact same location as the old equipment will be field-evaluated by the
Inspector for compliance.Additional bracing and accompanying engineering may be required based on the
Inspector's evaluation.The original Engineering for the replaced equipment if provided for review may be
acceptable.
**If outdoor air supply,ventilation or exhaust rate is reduced,provide calculations,specifications and plans for the mechanical
ventilation system including the required outdoor air ventilation and the required exhaust ventilation showing compliance with OMSC
Section 403/Table 403.3
•
AUa-07-2013 13 07 MARSHALLS INC. 541 741 0821 P.04
•
ritir
1 .
COMcheck Software Version 3.9.1
II Mechanical Compliance Certificate
2009 IECC •
•
,Section 1 : Project Information
Project Type:Alteration
Project Title :Springfield Utility Board
Construction Site: Owner/Agent: . Designer/Contractor:
250 A St Marshalls
Springfield,OR 97477 4110 Olympic
Springfield,OR 97478
541-747-7445
•
Section 2: General Information
Building Location(for weather data): Eugene,Oregon
Climate Zone: 4c
Section 3: Mechanical Systems List
Quantity System Tyne&Description
1 HVAC System 1 (Single Zone):Split System Heat Pump
Heating Mode:Capacity= 13 kBtu/h.Efficiency=10.00 HSPF
Cooling Mode:Capacity=12 kBtu/h,Efficiency=20.50 SEER
Section 4: Requirements Checklist
Requirements Specific To: HVAC System 1 :
X. Equipment minimum efficiency; Heat Pump: 7.70 HSPF 13.00 SEER
Generic Requirements: Must be met by all systems to which the requirement is applicable:
ya 1. Plant equipment and system capacity no greater than needed to meet loads
(— Except/on(s):
❑ Standby equipment automatically off when primary system is operating
❑ Multiple units controlled to sequence operation as a function of load
A 2. Minimum one temperature control device per system
❑ 3. Minimum one humidity control device per installed humidification/dehumidification system
❑ 4. Load calculations per ASHRAE/ACCA Standard 183.
•
❑ 5. Automatic Controls:Setback to 557(heat)and 857(cool);7-day dock,2-hour occupant override,10-hour backup
Exception(s):
. ❑ Continuously operating zones
❑ 2 kW demand or less,submit calculations
❑ 6. Outside-air source for ventilation;system capable of reducing OSA to required minimum
❑ 7. R-5 supply and return air duct insulation in unconditioned spaces
• R-8 supply and return air duct Insulation outside the building
R-8 insulation between ducts and the building exterior when ducts are part of a building assembly
Exception(s):
yf ce Ducts located within equipment
/❑ Ducts with interior and exterior temperature difference not exceeding 15°F.
❑ 8. Mechanical fasteners and sealants used to connect ducts and air distribution equipment
❑ 9. Ducts sealed-longitudinal seams on rigid ducts;transverse seams on all ducts; UL 181A or 181B tapes and mastics
Project Title: Springfield Utility Board Report date: 08/0603
Data filename: Untitled.cck Page 1 of 6
RLIC-07-2013 13 07 MARSHALLS INC. 541 741 0821 P.O5
' Exception(s): •
❑ Continuously welded and locking-type longitudinal joints and seams on ducts operating at static pressures less than 2 Inches w.g.
pressure classification
❑ 10.Hot water pipe insulation: 1.5 in.for pipes<=1.5 in.and 2 in.for pipes>1.5 in,
Chilled wafer/refrigeranVbrine pipe insulation: 1.5 in.for pipes<=1.5 in.and 1.5 in.for pipes>1.5 In.
Steam pipe insulation: 1.5 in.for pipes<=1.5 in.and 3 in.for pipes >1.5 in.
Exception(s):
❑ Piping within HVAC equipment.
❑ Fluid temperatures between 55 and 1057. •
❑ Fluid not heated or cooled with renewable energy.
❑ Piping within room fan-coil(with AHRI440 rating)and unit ventilators(with AHRI840 rating).
❑ Runouts<4 It in length. •
11.Operation and maintenance manual provided to building owner
• 12.Balancing devices provided in accordance with IMC(2006)603.17
• ❑ 13.Demand control ventilation(DCV)present for high design occupancy areas(>40 person/1000 ft2 In spaces>500 ft2)and served by
• systems with any one of 1)an air-side economizer,2)automatic modulating control of the outdoor air damper,or 3)a design outdoor
airflow greater than 3000 cfm.
Exception(s):
❑ Systems with heat recovery.
❑ Multiple-zone systems without DDC of individual zones communicating with a central control panel. •
Systems with a design outdoor airflow less than 1200 cfm.
❑ Spaces where the supply airflow rate minus any makeup or outgoing transfer air requirement is less than 1200 cfm.
❑ 14.Motorized,automatic shutoff dampers required on exhaust and outdoor air supply openings
Exception(s):
❑ Gravity dampers acceptable in buildings<3 stories
❑ Gravity dampers acceptable in systems with outside or exhaust air flow rates less than 300 cfm where dampers are interlocked
with fan
❑ 15.Automatic controls for freeze protection systems present
❑ 16.Exhaust air heat recovery included for systems 5,000 cfm or greater with more than 70%outside air fraction or specifically exempted
Exception(s): .
❑ Hazardous exhaust systems,commercial kitchen and clothes dryer exhaust systems that the International Mechanical Code
prohibits the use of energy recovery systems.
❑ Systems serving spaces that are heated and not cooled to less than 60°F.
❑ Where more than 60 percent of the outdoor heating energy Is provided from site-recovered or site solar energy.
❑ Heating systems in climates with less than 3600 HDD.
❑ Cooling systems in climates with a 1 percent cooling design wet-bulb temperature less than 64°F.
❑ Systems requiring dehumidification that employ energy recovery in series with the cooling coil.
❑ Laboratory fume hood exhaust systems that have either a variable air volume system capable of reducing exhaust and makeup air
volume to 50 percent or less of design values or,a separate make up air supply meeting the following makeup air requirements:
a)at least 75 percent of exhaust flow rale,b)heated to no more than 2°F below room setpoint temperature,c)cooled to no lower
than 37 above room setpoint temperature,d)no humidification added,e)no simultaneous heating and cooling.
Section 5: Compliance Statement .
Compliance Statement: The proposed mechanical alteration project represented In this document Is consistent with the building plans,
specifications and other calculations submitted with this permit application.The proposed mechanical alteration project has been designed
to meet the 2009 IECC,Chapter 8,requirements in COMcheck Version 3.9.1 and to comply with the mandatory requirements in the
Requirements Checklist. ,.t -Pa
yrl &skrin. sx, 4 3/6 /1 3
Name-Ti0e Signature Date
Section 6: Post Construction Compliance Statement
HVAC record drawings of the actual Installation,system capacities,calibration information,and performance data for each equipment
provided to the owner,
AHVAC O&M documents for all mechanical equipment and system provided to the owner by the mechanical contractor.
Written HVAC balancing and operations report provided to the owner.
Project Title: Springfield Utility Board Report date:08/06/13
Data filename: Untitled.cck Page 2 of 6
AUG-07-2013 13:08 MARSHALLS INC. 541 741 0821 P.06
' Thg�bove post construction requirements have b completed.
ilL 61?-4-2^ s D - — 5/6/13
Principal Mechanical Designer-Name Signature Date .
Project Notes:
Install ductless heat pump for office space.Indoor unit is a high wall,out door unit to be set on ground.
•
•
Project Title: Springfield Utility Board Report date:08/06/13
Data filename: Untitled.cck Page 3 of 6
RUG-07-2013 13 08 MARSHALLS INC. 541 741 0821 P.07
•
mars all's
•
August 1,2013
CCB025790
Keith Lockhart
Springfield Utility Board
541-744-3776
541-913-6976 cell
541-744-3654 fax
keithl(a?subuta.com
Re:250 A Street(NW Lower office)
Ductless Heat Pump by Mitsubishi 7661443
I-MSZGEI2NA indoor high wall unit
1-MUZGE12NA 12 KBTU 20.Ssecr/10 hspf heat pump
1-Refrigerant line set
I-Condensate drain
I-Conde or pad
1-Hand held remote
-Installation of balancing dampers to this office
1-High voltage fee
1-Peril Ste
-7 year parts and I year labor warranty
-Labor to install 53654.00
Options: •
Upgrade to M23R1 wall mount 7 day programmable t-stat Add 5267.00
ACCOUNTS ARE TO BE PAW EN FULL EACH MONTH,NET 10'"OF MONTH. PAYMENTS SHALL BE BASED ON TOE PERCENTAGE OF THE WORK
COMPLETED KETTLE TIME OF THE INVOICE PRICE QUOTES ARE GOOD FOR 30 DAYS. MARSHALL'S,INC RESERVES THE RIGHT TO CEASE
WORKING IF NOT PAID WHEN DUE AND FURTHER RESERVES THE RIGHT TO FILE A LIEN AS PROVIDED UNDER OREGON.LAW. THERE WILL
BE A 2%PER MONTH CARRYING CHARGE ON PAST DUE ACCOUNTS. CUSTOMER AGREES THAT N THE EVENT COLLECTION EFFORTS ARE
REQUIRED,REGARDLESS OF WHETHER A LAWSUIT OR OTHER ACTION IS COMMENCED,MARSHALL'S,NC.SHALL BE ENTITLED TO RECOVER
IN ADDITION TO THE AMOUNT OWING,THE COSTS OF THE COLLECTION EFFORTS.INCLUDING ANY ATTORNEY FEES INCLRFED WHETHER
BEFORE TRIAL,AT TRIAL OR ON APPEAL MARSHALL'S,INC.PROVIDES A LIMITED WARRANTY FOR ONE YEAR ON ITS LABOR.
MARSHALL'S,INC.WILL PASS ALONG ANY MANUFACTURER'S WARRANTIES TO THE OWNER. Other than the tome des shred shove.
MARSHALL'S, darkling nod eadudea en wart-modes,whether apron,oral,or implied,Includingwarrooaes of merchantability or timers for a
particular purpose nha0's Inc.further disclaims all liability for any cousaauential or Incidental damages.
SIGNATURE:
NAME: iT {,O C- Pra t _
DATE: / /2013 •
Quote good for 30 days.
Respectfully-Submitted,
�
Dra Gi
Mkt s fie 1 4110 O$yinpc Si*Spr gief,OR 97478 oGke 5L1.747-7445 I fax 541.7414821 I wardshaltinc.con I CCB#25790
TOTAL P.07