Client: Ms. Loretta Davies Project: Jerry's—Springfield Date: 06-14-13
Jerry's Home Improvement Center 2525 Olympic Blvd. Project No.: 2137111
PO Box 2611 Springfield, Oregon Report No.: E-34134
Eugene, Oregon 97402 Inspector: D. Delatte
ID No.: 1080867-88
ICC
Inspection of: Masonry Weather: Clear Continuous Inspection: ❑
Contractor: Chambers Construction BP No.: COM2009-00184 Periodic Inspection:
Performed inspection on the reinforcing steel in 8" CMU infills on line 2, from D to F,
5'4" to one(1) course below top of infill that is a reinforced bond beam. The last course
will be slugged with mortar as blocks are installed per contractor. Reinforcing steel was
checked for grade, size, lap, placement, quantities and clearance, where applicable.
Reinforced cells appear relatively clean and free of excessive mortar projections.
Observed the placement of 4.5 yards of Knife River 7sk grout (mix 247KG3R200).
Grout was placed by pump and was mechanically consolidated. Walls were grouted
solid. Slump -±10"; air temperature—63F; grout temperature—66F.
Gabe Morse (Hap's Masonry) was advised of the on-site observations and was asked
to notify our office when additional services are needed.
To the best of our knowledge, the work inspected was in accordance with plans dated
01-30-09 and applicable workmanship provisions of the I.B.C., except if noted above.
•
Reviewed By:
•
Michael . M er
Technical Manager
c:
Robertson Sherwood Architects—Lana Sadler(email)
Endex Engineering— David Morris (email)
Chambers Construction Co. — David Bakke (email)
•
- City of Springfield
MLM:sc
This report and/or enclosed test data is the confidential property of the client to whom it is addressed and pertains to the specific
process and/or material evaluated. As such,information contained herein shall not be reproduced in part or full and/or any part
thereof be disclosed without FEI Testing&Inspection,Inc.'s written authorization.
• 750 NW Cornell Avenue•Corvallis,Oregon 97330 phone(541)757.4698 fax(541)757-2991
29540 B Ailuu t Road•Eugene,Oregon 97402 phone(541)684-3849 fax(541)684-3851
62979 NE Plateau Drive,Suite 3•Bend,Oregon 97701 •phone(541)382-4844•fax(541)382-4846