HomeMy WebLinkAboutMiscellaneous Field Test & Inspection Report 2013-5-28 (5) 2 `13 ° 6n 4u 1 p��g . Information �`�° TOBui1L/On Engineering•Consulting• Testing 51-1-01.9.7 O DAILY OBSERVATION REPORT OF SINGLE-PLY THERMOPLASTIC ROOFING Date: 5/28/13 PROJECT INFORMATION Client:Wal-Mart Stores, Inc. (Store#4178) Work Area:A to B from 1 to 2.6 Project Name: Roofing Project Manufacturer Johns Manville 60 mil reinforced TPO Location: Springfield, OR Insulation Type: JM Energy 3 Isocyanurate PSI Report No.: 654137-82-11 Contractor: Central Oregon Roofing PSI Hours Worked: 10.0 Approximate Contractor Hours Worked: 10.0 SIGNATURES Sam Stoner Isaac Doug Roth, RRO PSI Quality Assurance Observer Roofing Contractor Reviewed By: Representative PSI Project Manager PROJECT STATUS AT-A-GLANCE Today's Performance Comment Construction today? ®Yes ❑ No If No Construction, Inspection Done?❑Yes ❑ No Contractor performance issues? ❑Yes 0 No Schedule/scope issues? ❑ Yes ® No DAILY PRODUCTION Total Square Feet Completed To Date Previously Today's Total Square Total Square Roof Section Completed Square Feet Feet Feet in % Complete Square Feet Completed Completed Section Main Roof Area 35,295' 3,249 38,544 39,049 98.7 38,544 39,049 98.7 Roofers—4 • Crew Size—4 Sheet Metal Workers—0 'Square foot totals were adjusted on this reporting date and are believed to be accurate Page 1 of 4 PSI Project No:654137 Date: 5-28-13 WEATHER CONDITIONS & EMERGENCY COVER ® Dry ❑ Sunny ® Cloudy ❑Windy ❑ Rain ❑ Snow Temp Range (low-high) 52° to 65° F Emergency cover/protection on-site? ®Yes ENo Type of Protection - TPO& EPDM membrane MATERIALS CONTROL & STORAGE In original identified packaging? ®Yes❑ No Off ground or deck? ®Yes❑ No Covered and vented? ®Yes ❑ No Roll goods stored on side? ®Yes ❑ No Adhesive storage temperature ❑ Yes® No Unapproved, damaged, or wet ❑Yes No maintained? material? If Yes, how disposed? Comments: Stored material protection appears adequate. SUBSTRATE PREPARATION Night tie-in removed? ®Yes❑ No Substrate clean and debris ® Yes❑ No removed? Substrate and penetrations ready? ®Yes❑ No Substrate tested for dryness? 0 Yes❑ No Comments: Substrates that received new roofing components appeared clean and dry. COVER BOARD APPLICATION (1" ENERGY 3) Correct Number of fasteners &Rhino Plates?(12 in corners, 9 at perimeter, 0 Yes❑ No Additional fasteners at ® Yes❑ No 6 in the field) perimeters and corners? Fasteners checked by technician? ®Yes ❑ No Short insulation joints ® Yes ❑ No staggered? New/Existing Insulation joints tight? ®Yes ❑ No All joints staggered between layers? 0 Yes❑ No Gaps filled with spray foam? ®Yes❑ No Drainage crickets installed per plans and specifications? ®Yes ❑ No Comments: The isocyanurate was fastened per the roofing manufacturer's specified fastener frequency. SINGLE-PLY MEMBRANE APPLICATION (60 MIL REINFORCED JOHNS MANVILLE TPO) Membrane allowed to relax prior to ®Yes❑ No Membrane fully welded to Rhino ❑Yes 0 N attachment? Plates? Membrane/plate welds checked by technician? ®Yes❑ No Membrane properly lapped? ®Yes❑ No Seams clean prior to welding? ®Yes❑ No Continuous weld achieved? 0 Yes❑ No Page 2 of 4 PSI Project No:654137 Date: 5-28-13 SINGLE-PLY MEMBRANE APPLICATION (60 MIL REINFORCED JOHNS MANVILLE TPO) (CONT'D) Membrane flow at lap welds? ® Yes❑ No Seams probed by technician ®Yes❑ No Cut edge sealant installed? ❑Yes 0 No T-patches installed? ❑Yes® No Primary field membrane termination ❑ Yes® No (T-bar) installed? Comments: Not all induction welds were completed today(work in progress). BASE FLASHING APPLICATION (60 MIL REINFORCED JOHNS MANVILLE TPO) Substrate clean and prepared? ❑Yes❑ No Adhesive applied to substrate ❑Yes❑ No and allowed to dry? Adhesive applied to back of base ❑Yes❑ No Adhesive allowed to flash off? ❑ Yes❑ No flashing? Flashing pressed onto substrate to ❑ Yes ❑ No Flashing properly lapped onto ❑Yes❑ No promote adhesion? field membrane? Seams cleaned prior to welding? ❑Yes ❑ No Membrane flow at welds? ❑ Yes❑ No Continuous weld achieved? ❑ Yes❑ No Manufacturer's approved corner ❑Yes❑ No patches installed? Seams probed by technician ❑ Yes❑ No Cut edge sealant installed? ❑ Yes ❑ No Termination bars installed? ❑Yes ❑ No Counterflashings installed? ❑ Yes❑ No Comments: None installed today. NIGHT TIE-IN/ DAMAGE /SITE CLEANUP INSPECTION Night seal installed? 0 Yes❑ No Roofing appears watertight? 0 Yes❑ No Roof drain fleshings completed? ❑Yes 0 No Damage to property? ❑Yes 0 No Damage to client's equipment? ❑Yes® No Site broom clean? ❑ Yes® No All debris removed from roof? ❑Yes 0 No Roof materials and equipment ®Yes❑ No appear secured? Comments:Areas of new TPO roofing appear to be watertight. The roof needs to be cleaned off. Page 3 of 4 PSI Project No:654137 Date: 5-28-13 DETAIL INSTALLATION (NOTE DRAWINGS USED AS REFERENCE) Detail# Detail Name Construction Summary(Quantity/Description/Comment) SUMMARY OF TODAY'S WORK/DEVIATIONS/ SPECIAL NOTES: Summary Comments: Work completed today appeared to conform to project plans and specifications. Unresolved EVOCO Deviation Number(s):0 Special Notes: None today. Respectfully Submitted, PROFESSIONAL SERVICE INDUSTRIES,INC. PSI Roof Observer: Sam Stoner CC: Portland, OR—One copy electronically Reviewed By: Doug Roth, RRO • Page 4 of 4